6.4. Transmission 

line

 CAUTION

Caution when wiring cable:
When stripping off the coating of lead wire, always use the exclusive tool such as a 
wire stripper. If there is no exclusive tool available necessarily, carefully strip the coat-
ing by a cutter etc. so that the conductive wire is not damaged.
If it is damaged, it may lead to an open circuit and a communication error.

Pay attention to the following points while attaching wires on the terminal board.
• Do not attach 2 wires on one side.
• Do not twist wires.
• Do not cross the wires.
• Do not shorted at edge at root.

GOOD

PROHIBITED

1 wire

2 pcs at one side

Wires twisted

2 wires

Shorted at edge

Shorted at root

6.4.1  Transmission wiring speci

fi

 cations

Follow the specifications below for the transmission cable.

Use

Size

Cable type

Remarks

Transmission cable

0.33 mm²

22AWG LEVEL 4 (NEMA) 
non-polar 2 core, twisted pair 
solid core diameter 0.65 mm

LONWORKS ® 
compatible cable

Twisted pair with shielded type.
Use the shielded wire specified and always ground it both ends.

6.4.2 Wiring rules

(1) Total length of transmission cable

Total transmission line length: MAX 3,600 m

EF + EG + GH + HJ + HK + KL < 3,600 m (Fig. 2)

In the following cases, Signal amplifier is required.
1)

When the total length of the transmission line exceeded 500 m.
AB + BC + BD > 500 m (Fig. 1)

2)

When the total number of units* is over 64.

3)

Transmission line length between each unit* 

 400 m

(2) Length of transmission cable between 1 network segment (NS)

EF + EG + GH + HJ + HK 

 500 m (Fig. 2)

KL 

 400 m (Fig. 2)

Unit* means indoor unit, outdoor unit, Touch panel controller and System controller, Signal 
amplifier, Single split adaptor, Network convertor etc.

Fig. 1

Transmission line

System 
controller

Touch panel 
controller

When AB + BC + BD > 500 m
: Signal amplifier is required.

Outdoor unit

Indoor unit

Terminal resistor

Fig. 2

Outdoor unit

Indoor unit

Signal amplifier

System 
controller

Touch 
panel 
controller

Transmission line

Terminal resistor

Terminal resistor

NS 1

NS 2

NOTES:

Do not use loop wiring. This 
may lead to parts damage and 
erroneous operation.

6.4.3  Enabling/Disabling automatic address setting

You can enable/disable automatic address setting for the indoor unit and the signal ampli-
fier.
To enable automatic address setting for the indoor unit, connect the indoor unit to outdoor 
units under the same refrigerant system.

Example: Disable Automatic Address setting

Refrigerant 
system 1

Refrigerant 
system 2

Refrigerant 
system 3

Transmission line

Transmission line

Transmission line

Example: Enable Automatic Address setting

Refrigerant 
system 1

Refrigerant 
system 2

Refrigerant 
system 3

Transmission line

Transmission line

Transmission line

6.5. Wiring 

method

6.5.1 Connection diagrams

N

L1 L2 L3

L1 L2 L3

N

*1

*2

*2

*2

*1

*1

To other refrigerant circuit outdoor unit

Transmission

Transmission

Transmission

Transmission

Remote control

Remote control

Remote control

Power supply

Power supply

Power supply

Indoor unit

Indoor unit

Indoor unit

Power supply

230V 1

Φ

 50 Hz

Power supply

230V 1

Φ

 50 Hz

Power supply

230V 1

Φ

 50 Hz

Remote 
controller
(2-wire)

Remote 
controller
(2-wire)

Remote 
controller
(3-wire)

Outdoor 
unit

Breaker

Breaker

Breaker

Power supply: 400V 3

Φ

 50 Hz

Breaker

Power supply

Breaker: 
(1)  Earth leakage circuit breaker 
(2)  Current breaker (over current)

*1:  The number of power supply terminals is different depending on the indoor unit 

model. For the wiring, refer to the indoor unit installation manual.

*2:  Earth (Ground) the remote controller if it has an earth (ground) cable.
• There are two types of remote controller: the 2-wire type and the 3-wire type. For details, 

see the relevant remote controller installation manual. (When connecting the 2-wire type 
remote controller, Y3 is not used.)

The wiring example for outdoor and indoor units is shown in figure.

9380545347-01_IM.indb   9

9380545347-01_IM.indb   9

11/29/2019   8:49:53 AM

11/29/2019   8:49:53 AM

Содержание AIRSTAGE AJ 072LELBH Series

Страница 1: ...or authorized service personnel only Nur für autorisiertes Fachpersonal Pour le personnel de service agrée uniquement Únicamente para personal de servicio autorizado A uso esclusivo del personale tecnico autorizzato Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό Somente para o pessoal do serviço técnico autorizado Только для авторизованного обслуживающего персонала Yalnızca yetkili servis personeli iç...

Страница 2: ...all the electrical box cover on the unit An improperly installed electrical box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Do not turn ON the power until all work has been completed Turning ON the power before the work is completed can cause serious accidents such as electric shock or fire After the installation make sure there is no refriger...

Страница 3: ... start or stop the operation of air conditioning with power breaker Other wise it may cause malfunction or water leakage When setting it up near the equipment that generates electromagnetic waves and the equipment that generates the higher harmonics wave be sure to take measures against noise Otherwise it may cause malfunction or failure When energizing to the crankcase heater please turn on the p...

Страница 4: ...por soot dust or debris Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 meter away from a television or radio The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 meter apart you could still receive noise under some signal conditions Keep the length of the piping of the indoo...

Страница 5: ... unit WARNING Do not touch the fins Otherwise personal injury could result CAUTION When carrying the unit hold the handles on the right and left sides and be careful If the outdoor unit is carried from the bottom hands or fingers may be pinched Hoisting method When hoisting the outdoor unit hook the rope on the outside of the foot as shown in the figure Use sufficiently strong rope to bear the uni...

Страница 6: ... local rules 1 Allowable tensile stress 33 N mm2 2 Allowable tensile stress 61 N mm2 3 Endurance pressure of the pipes 4 2MPa 3 5 Installing the unit Please install the outdoor unit without slant within 0 3 degrees Install 4 anchor bolts at the locations indicated with arrows in the figure To reduce vibration do not install the unit directly on the ground Install it on a secure base such as concre...

Страница 7: ...090 96 096 Capacity kW 1 1 2 2 2 8 3 6 4 5 5 6 7 1 9 0 10 0 11 2 12 5 14 0 18 0 22 4 25 0 28 0 In the case of ARXD007GLEH equivalent to model code of indoor unit Model code 007 Capacity 2 2kW 4 3 Protection of pipes Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes Protect the pipes to prevent the entry of...

Страница 8: ... valves Use a hexagon wrench Liquid valve size 4 mm Gas valve size 8 mm Opening 1 Insert the hexagon wrench into the valve shaft and turn it counterclock wise 2 Stop turning when the valve shaft can no longer be turned Open position Closing 1 Insert the hexagon wrench into the valve shaft and turn it clockwise 2 Stop turning when the valve shaft can no longer be turned Closed position Opening dire...

Страница 9: ...he temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency earth leakage circuit breaker is necessary to prevent a malfunction of the breaker itself When the electrical switchboard is ...

Страница 10: ...door unit Signal amplifier System controller Touch panel controller Transmission line Terminal resistor Terminal resistor NS 1 NS 2 NOTES Do not use loop wiring This may lead to parts damage and erroneous operation 6 4 3 Enabling Disabling automatic address setting You can enable disable automatic address setting for the indoor unit and the signal ampli fier To enable automatic address setting for...

Страница 11: ...l 126 144 162 model 162 model How to connect wiring to the terminal Caution when wiring cable 1 Use ring terminals with insulating sleeves as shown in the figure to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cables do not come loose 3 Use the specified cables connect them securely and fasten them so that there is no stress ...

Страница 12: ...tton setting NOTES 1 The external input priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SETTING 3 The emergency stop function mounted in this model does not guarantee the regula tions of each country For this reason sufficient checking ...

Страница 13: ...ressure 1 equivalent to 072 090 model 30 Pa 108 model 40 Pa 126 144 162 model 60 Pa 0 1 25 Prohibited Factory default 2 5 0 0 26 Prohibited Factory default 2 6 0 0 27 Prohibited Factory default 2 7 0 0 28 Prohibited Factory default 2 8 0 0 29 Prohibited Factory default 2 9 0 0 7 FIELD SETTING CAUTION Discharge the static electricity from your body before setting up the DIP switches Never touch the...

Страница 14: ...ectricity meter No is set to 000 and 201 to 299 the pulses input to CN135 become ineffective Available setting number is 001 to 200 3 When the electricity meter pulse setting is set to 0000 the pulses input to CN135 become ineffective Available setting number is 0001 to 9999 4 This item is not displayed for 072 090 and 108 models 1 Turn on the power of the outdoor unit and enter standby mode When ...

Страница 15: ...cedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the indoor and outdoor units When the system is normal nothing will be displayed on the 7 segment display When ...

Страница 16: ...ocedure 1 Remove the blank caps of the gas pipe and liquid pipe and check that the valves are closed 2 Remove the charging port cap 3 Connect a vacuum pump and a pressure gauge to a charging hose and connect it to the charging port 4 Activate the vacuum pump and vacuum the indoor unit and connection piping until the pressure gauge becomes 100 7 kPa 755mm Hg Evacuate from both the gas pipe and the ...

Страница 17: ... caused near electrical components in the service panel If the outdoor unit is installed at a level that is higher than the indoor unit the water that has condensed in the 3 way valve of the outdoor unit could travel to the indoor unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water to the indoor units 9 TEST RUN 9 1 Indoor unit connection check N...

Страница 18: ...rror codes can be confirmed by pressing the SELECT button Example When Indoor unit capacity error E221 and Indoor unit duplicate address error E261 occurred 1 When the address of the overlap indoor unit is displayed press and hold the ENTER button for more than 3 seconds 2 When errors other than the address of the overlap indoor unit exist press SELECT but ton to switch to the next error If error ...

Страница 19: ...ssor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchroniza tion E 9 7 1 Outdoor unit fan motor 1 lock error E 9 7 4 Outdoor unit fan motor 1 undervoltage error E 9 7 5 Outdoor unit fan motor 1 temperature error protective action E 9 7 9 Outdoor unit fan motor 1 driver error E 9 8 1 Outdoor unit fan motor 2 lock error E 9 8 5 Outdoor unit fan m...

Отзывы: