background image

En-15

7.   FIELD SETTING

 CAUTION

Discharge the static electricity from your body before setting up the DIP switches.
Never touch the terminals or the patterns on the parts that are mounted on the PC 
board.

7.1.  Field setting switches

Remove the service panel of the outdoor unit and the cover of the electrical component 
box to access the PC board of the outdoor unit.
PC board switches for various settings and LED displays are shown in the figure.

7.2.  DIP switch setting

7.2.1  List of Settings

SET3 and SET5 must be set for the 
DIP switch.
Configure the settings before turning 
on the power. Settings for SET1, 
SET2, and SET4 DIP switches are 
factory default ones. Do not change 
them.

DIP Switch

Function

SET 1

1-4

Prohibited

SET 2

1-4

Prohibited

SET 3

1

Outdoor unit address setting

2
3

Setting for number of slave 
units

4

SET 4

1-4

Prohibited

SET 5

1-2

Number of outdoor units 
installed

3

Prohibited

4

Terminal resistor setting

7 Segment
LED indicator

Push button

LED lamp

Rotary switch

Outdoor unit PC board

DIP switch

7.2.2  Settings to be confi gured locally

(1)  Outdoor unit address setting
When 2 or 3 outdoor 
units are installed to 1 
refrigerant system, set the 
address for each outdoor 
unit. 
Set the address for all 
outdoor units.

SET3

Outdoor unit 

address

Remarks

1

2

OFF

OFF

0

Master unit 
(Factory setting)

OFF

ON

1

Slave unit 1

ON

OFF

2

Slave unit 2

ON

ON

-

Prohibited

(2)  Number of slave units setting for outdoor unit
Set the number of slave 
units connected to 1 
refrigerant system.
Set only the master unit.

SET3

Number of 

connectable 

outdoor units

Remarks

3

4

OFF

OFF

0

Master unit only 
(Factory setting)

OFF

ON

1

1 slave unit connected

ON

OFF

2

2 slave unit connected

ON

ON

-

Prohibited

(3)  Number of outdoor units installed
The number of outdoor 
units installed in 1 refriger-
ant system must be set.
Set for all outdoor units.

SET5

Number of 

outdoor units

Remarks

1

2

OFF

OFF

1

(Factory setting)

OFF

ON

2

-

ON

OFF

3

-

ON

ON

-

Prohibited

Operation behavior

Each input terminal works as follows.

Connector

Input 

signal

Status

Outdoor unit

Master Slave

Input 1 
CN131 (Yellow)

OFF

Normal operation

O

ON

Low noise mode operation

Input 3 
CN133 (White)

OFF

Normal operation

O

ON

Outdoor unit operation peak 
control

Input 4 
CN134 (Red)

OFF

Normal operation

O

ON

Batch stop or Emergency 
stop operation (*1, *2)

Input 5 
CN135 (Orange) (*3)

No pulse

No information from electric-
ity meter

O

O

Pulse

Power usage information 
from electricity meter

Slave unit can connect only input5 (CN135).

The operations of each input terminal and the selection of function are set with the push 
button on the PC board of outdoor unit. About the setting, please refer to “7. 4. Push but-
ton setting”.

NOTES:

*1:  The “external input priority mode” must be set by pressing push button on PC board 

of outdoor unit. (Refer to “7. FIELD SETTING”.)

*2:  Batch stop or Emergency stop pattern can be selected by outdoor unit PC board 

push button. (Refer to “7. FIELD SETTING”.)

*3:  The emergency stop function mounted in this model does not guarantee the regula-

tions of each country. For this reason, sufficient checking is necessary regarding 
use. 
Especially, since the fact that the equipment may not be emergency-stopped in the 
case of breaking of the wiring to the external input terminals and communication 
line, communication error due to noise, VRF external input circuit trouble, etc. must 
be considered, the provision of double measures that add direct interruption of the 
power supply by switch, etc. is recommended as a precaution.

6.7.3  External output terminal (master unit only)

• You can detect the operation condition of outdoor unit and the abnormal situation of both 

indoor and outdoor unit.

• The external output terminal is only valid for Master unit.
Wiring method and specifications

Error status

This output indicates the outdoor unit 
and connected indoor unit's “Normal” or 
“Error” status.

Operation status

This output indicates the outdoor unit's 
“Operation” status.

Connector

Output 

voltage

Status

Output 1
CN136 
(Black)

0 V

Normal

DC 12-24 V 

(*1)

Error

Output 2
CN137 
(Blue)

0 V

Stop

DC 12-24 V 

(*1)

Operation

P.C.B.

CN136 (Black) or 
CN137 (Blue)

DC power supply 
(External) 12-24 V

Connected load (Operation Indica-
tor or Error Indicator)

Connected unit

*1:  Provide a DC 12 to 24 V power supply. 

Select a power supply capacity with an ample surplus for the connected load.

*2:  The allowable current is 30 mA or less. 

Provide a load resistance such that the current becomes 30 mA or less.

*3:  Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.

Do not impress a voltage exceeding 24 V across pins 1-2.

*  A twisted pair cable (0.33 mm² (22AWG)) should be used. 

Maximum length of cable is 150 m.

*  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

6.7.4  Base heater terminal

This is the output signal for base heater. Output signal ON, when the outdoor temperature 
goes down below 2°C, and signal OFF at the outdoor temperature 4°C.

  

Voltage: 
power supply input voltage

Cable

(0.82 mm² (18AWG))

P.C.B.

Base heater (*2)

CN115 

(Black)

(*1)

*1:  Connect to pin 1 and pin 3. No connection pin 2 and pin 4.
*2:  The allowable current is 1 A or less.

9378945630-02_IM.indb   15

9378945630-02_IM.indb   15

3/6/2020   11:55:24 AM

3/6/2020   11:55:24 AM

Содержание Airstage AJ 072GALBH Series

Страница 1: ...NLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Только д...

Страница 2: ... it can withstand earthquakes and typhoons or other strong winds Improper installation can cause the unit to topple or fall or other accidents Ensure that the outdoor unit is securely installed at a place that can withstand the weight of the unit Improper installation will cause injuries caused by falling unit If there is a refrigerant leakage make sure that it does not exceed the concentration li...

Страница 3: ...ns When the energizing time is short it may cause failure Be sides please do not turn off power during the busy season Children should be monitored to ensure they do not play with the device This product is not intended to be used by people including children with physical sen sory or mental disability or persons lacking experience or knowledge unless they have been given by the through a person r...

Страница 4: ...9 For External output Base heater CN115 3 INSTALLATION WORK Please obtain the approval of the customer when selecting the location of installation and installing the main unit 3 1 Selecting an installation location WARNING Install the unit in a location that can withstand its weight and where it will not topple or fall Calculate the proper refrigerant concentration if you will be installing it in ...

Страница 5: ... 500 or less L2 100 When H2 is 500 or more L2 100 h2 2 Fig 1 Side view Front Rear Wall Wall Fig 2 Single installation 30 mm or more 10 mm or more Top view Front Rear Fig 3 Multiple installations Top view 30 mm or more 20 mm or more 10 mm or more Front Rear 20 mm or more 2 Concentrated installation Provide installation spaces L3 L4 and L5 in accordance with the table below according to the wall hei...

Страница 6: ...ause to damage or deform During the hanging unit make sure to keep the unit level to prevent from falling To prevent the unit swing ac cident or falling down of the unit do not apply any impact to the unit when it is hanging Opening space Protective boards Product mass kg AJ 072GALBH 262 AJ 090GALBH 262 AJ 108GALBH 262 AJ 126GALBH 286 AJ 144GALBH 286 Lifting by forklift When using the forklift to ...

Страница 7: ...al pipe length 1000 m or less Total Between outdoor unit and outdoor unit branch kit 3 m or less a b Allowable height difference Between outdoor unit and indoor unit When indoor unit is installed below 50 m or less H1 Between outdoor unit and indoor unit When outdoor unit is installed below 40 m or less Between indoor units 15 m or less H2 H3 Between outdoor units 0 5 m or less H4 Between RB unit ...

Страница 8: ...8 56 1 to 80 0 15 88 5 8 28 58 1 1 8 34 92 1 3 8 UTP BX567A 80 1 to 95 0 19 05 3 4 28 58 1 1 8 34 92 1 3 8 95 1 or more 19 05 3 4 28 58 1 1 8 41 27 1 5 8 If the selected pipe diameter between separation tubes based on table C becomes larger than the pipe diameter between outdoor unit branch kit and the first separation tube based on table B please select the pipe whose diameter is equal to the one...

Страница 9: ... film This can degrade performance or damage the parts in the unit such as the compressor or valves Do not use flux to braze pipes If the flux is the chlorine type it will cause the pipes to corrode In addition if the flux contains fluoride it will affect the refrigerant piping system due to deterioration of refrigerant oil For brazing material use phosphor copper that does not require flux 5 2 In...

Страница 10: ...ke sharp bends Bend the pipe at a radius of 70 mm or greater Do not bent pipe many times at same part to prevent break After completing all the pipe connection by brazing perform the indoor unit pipe connec tion with a flare joint When removing the pinch pipe or brazing the joint pipe carry out the work while cooling down the 3 way valve sufficiently Braze the joint pipe onto the 3 way valves at t...

Страница 11: ...prevent the oil from settling in the stopped unit install the pipes between the outdoor units so that they are level or are tilted upward to the outdoor units Installable patterns GOOD GOOD GOOD Master unit Slave unit 1 Slave unit 2 Master unit Slave unit 1 Slave unit 2 Master unit Slave unit 1 Slave unit 2 To indoor unit To indoor unit To indoor unit Non install able patterns PROHIBITED Master un...

Страница 12: ...h leakage circuit breaker in a location that is not exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency breaker is necessary to prevent a malfun...

Страница 13: ... trapped in the outdoor unit may cause a short circuit in the electrical component box Be careful not to deform or scratch the panel while opening the knockout holes After opening the knockout holes remove burr on the edges and attach the conduit or grommet edging accessories to prevent damaging the cables It is recommended to apply rust proof paint on the edges to prevent rust Electric wires can ...

Страница 14: ...c address setting for the indoor unit connect the indoor unit to outdoor units under the same refrigerant system Example Disable Auto matic Address setting Refrigerant system 1 Refrigerant system 2 Transmission line Transmission line Example Enable Auto matic Address setting Refrigerant system 1 Refrigerant system 2 Transmission line Transmission line 6 6 Wiring procedure Remove the cover of the e...

Страница 15: ...sted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of shielded wire to earth Ground RB IN Cable clip Cable tie accessory 40 mm or more 8 to 10 mm 6 7 External input and external output 6 7 1 Terminal position Input 5 CN135 ORANGE Outdoor unit PC board CN131 YELLOW CN136 BLACK CN137 BLUE CN134 RED CN115 BLACK CN133 WHITE Inpu...

Страница 16: ...erminal and the selection of function are set with the push button on the PC board of outdoor unit About the setting please refer to 7 4 Push but ton setting NOTES 1 The external input priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SET...

Страница 17: ...em when necessary 12 Heating capacity shift 1 Normal mode 1 2 0 0 z Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Set this item when necessary 13 Prohibited Factory default 1 3 0 0 z 14 Prohibited Factory default 1 4 0 0 z 15 Prohibited Factory default 1 5 0 0 z 20 Switching be tween batch stop or emergency stop 1 Batch stop 2 0 0 0 z Emergency stop 0 1 This mode selects the pat...

Страница 18: ...ohibited Factory default 6 3 0 0 z 70 Electricity meter No setting 1 2 Setting number x00 7 0 0 0 z Setting number x01 0 1 Setting number x98 9 8 Setting number x99 9 9 Set the ones digit and tens digit of the No of the electricity meter connected to CN135 71 Electricity meter No setting 2 2 Setting number 0xx 7 1 0 0 z Setting number 1xx 0 1 Setting number 2xx 0 2 Set the hundreds digit of the No...

Страница 19: ...ed Refer to the indoor unit installation manual for the procedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the indoor and outdoor units When the system is norm...

Страница 20: ...iping follow below i e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter the pipes during work etc After operating the vacuum pump for 2 hours pressurize to 0 05 MPa i e vacuum breakdown with nitrogen gas then depressurize down to 100 7 kPa 755 mmHg for an hour using the vacuum pump vacuum process If...

Страница 21: ... an M4 hexagon wrench for liquid pipe Use an M8 hexagon wrench for suction gas pipe and discharge gas pipe If you cannot charge the specified amount of refrigerant with the above method be sure to charge the refrigerant through the gas pipe while operating in cooling mode In order to prevent liquid back flow carefully operate the refrigerant cylinder valve so that the refrigerant will flow in cert...

Страница 22: ...r unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water Putty Insulation Table Selection of insula tion Use an insulation material with equal heat transmis sion rate or below 0 040 W m k When the ambient tempera ture and relative humid ity exceed 32 C DB and 85 respectively please strengthen heat insulation of refrigerant pipe Relative humidity Ins...

Страница 23: ...tor error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchronization E 9 7 1 Outdoor unit fan motor lock error E 9 7 5 Outdoor unit fan motor temperature error protec tive action E 9 7 9 Outdoor unit fan motor driver error E 9 A 1 Outdoor unit coil 1 expansion valve 1 error E 9 A 2 Outdoor unit coil 2 ex...

Отзывы: