En-12

(2)  Selecting main breaker and main power supply cable when connecting multiple 

outdoor units

In case of connected 3 outdoor unit

GOOD

Sub 
breaker

Outdoor unit power supply cable

400 V 3ø 
50 Hz

Main 
breaker

Main breaker: Main breaker ≥ Total Sub breaker 
(Refer to the table in item (1) for the sub breaker 
capacity)

PROHIBITED

400 V 3ø 

50 Hz

Outdoor unit power supply cable
PROHIBITED: crossover power 
supply wiring prohibited

Breaker

PROHIBITED: install a breaker for 

each outdoor unit

6.5.  Transmission line

 CAUTION

Caution when wiring cable:
When stripping off the coating of lead wire, always use the exclusive tool such as a 
wire stripper. If there is no exclusive tool available necessarily, carefully strip the coat-
ing by a cutter etc. so that the conductive wire is not damaged.
If it is damaged, it may lead to an open circuit and a communication error.

Pay attention to the following points while attaching wires on the terminal board.
• Do not attach 2 wires on one side.
• Do not twist wires.
• Do not cross the wires.
• Do not shorted at edge at root.

GOOD

PROHIBITED

1 wire

2 pcs at one side

Wires twisted

2 wires

Shorted at edge

Shorted at root

6.5.1  Transmission wiring specifi cations

Follow the specifications below for the transmission cable.

Use

Size

Cable type

Remarks

Transmission cable

0.33 mm²

22AWG LEVEL 4 (NEMA) 
non-polar 2 core, twisted pair 
solid core diameter 0.65 mm

LONWORKS ® 
compatible cable

Twisted pair with shielded type.
Use the shielded wire specified and always ground it both ends.

6.5.2  Wiring rules

(1)  Basic wiring rules

Total transmission line length: MAX 3600 m 
(A + C + D + E + F + G + H + J + K + N + W ≤ 3600)
Transmission line length between each unit: MAX 400 m
Transmission line length between outdoor units in a refrigerant system MAX 18 m 
(L ≤ 18 m, M ≤ 18 m)
Be sure to set 1 terminal resistor in a network segment.

Indoor unit

Transmission line

RB unit

Terminal resistor

System controller

Touch panel controller

A (a to b)

6.3.  Knockout hole

CAUTION

Seal the wiring route hole with putty (Locally purchased) such that there are no gaps.
Small insects or animals that are trapped in the outdoor unit may cause a short circuit in the 
electrical component box.

Be careful not to deform or scratch the panel while opening the knockout holes.

After opening the knockout holes, remove burr on the edges, and attach the conduit or 
grommet edging (accessories) to prevent damaging the cables.
It is recommended to apply rust proof paint on the edges to prevent rust.

Electric wires can be connected from the front or from the left.
(Knockout holes are prepared so that wiring can be made from 2 different directions.)
Use the knockout holes on the front and the left separately when necessary.

< Left view >

< Front view >

(Unit: mm)

(Unit: mm)

Length of the grommet edging

Mounting the grommet edging

Grommet edging 
(accessories)

Knockout hole

Knockout hole 
diameter (mm)

Dimension L 

(mm)

Ø 50

147

Ø 43.7

130

Ø 34.5

100

Ø 22.2

60

6.4.  Selecting power supply cable and breaker

CAUTION

Obtain the distribution network operator's agreement about the power capacity of the 
power supply system, specification of the cable and the harmonic current, and etc. 
when you connect the outdoor unit with the power supply.

Regulation of wire size and circuit breaker differs from each locality, please refer in ac-
cordance with local rules.

Refer to the table for the wiring and breaker specifications of each installation condition.
(1)  Selecting power supply cable and breaker when connecting 1 outdoor unit

Model

Breaker (Time delay fuse 

or circuit capacity)

Outdoor unit power supply cable

Recommended cable size 

(mm²)

Limited wir-

ing length 

(m)

Fuse capac-

ity (A)

Leakage 

current

Power cable

Earth 

(ground) 

cable

AJ*072GALBH

20

100 mA 

0.1 sec or 

less

4

4

51

AJ*090GALBH

25

6

6

62

AJ*108GALBH

25

6

6

62

AJ*126GALBH

40

10

10

64

AJ*144GALBH

40

10

10

64

These values are recommended data.
• Specification: Use conformed cord with Type 60245 IEC66
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire 

diameter when the wire length is long.

In case of connected outdoor unit

GOOD

Breaker

Transmission cable

Remote controller cable

Breaker

400 V 3ø 50 Hz

230 V 1ø 50 Hz

Outdoor unit 

power supply cable

RB unit 

power supply 

cable

Indoor unit 

power supply 

cable

230 v 1ø 50 Hz

9378945630-02_IM.indb   12

9378945630-02_IM.indb   12

3/6/2020   11:55:23 AM

3/6/2020   11:55:23 AM

Содержание Airstage AJ 072GALBH Series

Страница 1: ...NLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Только д...

Страница 2: ... it can withstand earthquakes and typhoons or other strong winds Improper installation can cause the unit to topple or fall or other accidents Ensure that the outdoor unit is securely installed at a place that can withstand the weight of the unit Improper installation will cause injuries caused by falling unit If there is a refrigerant leakage make sure that it does not exceed the concentration li...

Страница 3: ...ns When the energizing time is short it may cause failure Be sides please do not turn off power during the busy season Children should be monitored to ensure they do not play with the device This product is not intended to be used by people including children with physical sen sory or mental disability or persons lacking experience or knowledge unless they have been given by the through a person r...

Страница 4: ...9 For External output Base heater CN115 3 INSTALLATION WORK Please obtain the approval of the customer when selecting the location of installation and installing the main unit 3 1 Selecting an installation location WARNING Install the unit in a location that can withstand its weight and where it will not topple or fall Calculate the proper refrigerant concentration if you will be installing it in ...

Страница 5: ... 500 or less L2 100 When H2 is 500 or more L2 100 h2 2 Fig 1 Side view Front Rear Wall Wall Fig 2 Single installation 30 mm or more 10 mm or more Top view Front Rear Fig 3 Multiple installations Top view 30 mm or more 20 mm or more 10 mm or more Front Rear 20 mm or more 2 Concentrated installation Provide installation spaces L3 L4 and L5 in accordance with the table below according to the wall hei...

Страница 6: ...ause to damage or deform During the hanging unit make sure to keep the unit level to prevent from falling To prevent the unit swing ac cident or falling down of the unit do not apply any impact to the unit when it is hanging Opening space Protective boards Product mass kg AJ 072GALBH 262 AJ 090GALBH 262 AJ 108GALBH 262 AJ 126GALBH 286 AJ 144GALBH 286 Lifting by forklift When using the forklift to ...

Страница 7: ...al pipe length 1000 m or less Total Between outdoor unit and outdoor unit branch kit 3 m or less a b Allowable height difference Between outdoor unit and indoor unit When indoor unit is installed below 50 m or less H1 Between outdoor unit and indoor unit When outdoor unit is installed below 40 m or less Between indoor units 15 m or less H2 H3 Between outdoor units 0 5 m or less H4 Between RB unit ...

Страница 8: ...8 56 1 to 80 0 15 88 5 8 28 58 1 1 8 34 92 1 3 8 UTP BX567A 80 1 to 95 0 19 05 3 4 28 58 1 1 8 34 92 1 3 8 95 1 or more 19 05 3 4 28 58 1 1 8 41 27 1 5 8 If the selected pipe diameter between separation tubes based on table C becomes larger than the pipe diameter between outdoor unit branch kit and the first separation tube based on table B please select the pipe whose diameter is equal to the one...

Страница 9: ... film This can degrade performance or damage the parts in the unit such as the compressor or valves Do not use flux to braze pipes If the flux is the chlorine type it will cause the pipes to corrode In addition if the flux contains fluoride it will affect the refrigerant piping system due to deterioration of refrigerant oil For brazing material use phosphor copper that does not require flux 5 2 In...

Страница 10: ...ke sharp bends Bend the pipe at a radius of 70 mm or greater Do not bent pipe many times at same part to prevent break After completing all the pipe connection by brazing perform the indoor unit pipe connec tion with a flare joint When removing the pinch pipe or brazing the joint pipe carry out the work while cooling down the 3 way valve sufficiently Braze the joint pipe onto the 3 way valves at t...

Страница 11: ...prevent the oil from settling in the stopped unit install the pipes between the outdoor units so that they are level or are tilted upward to the outdoor units Installable patterns GOOD GOOD GOOD Master unit Slave unit 1 Slave unit 2 Master unit Slave unit 1 Slave unit 2 Master unit Slave unit 1 Slave unit 2 To indoor unit To indoor unit To indoor unit Non install able patterns PROHIBITED Master un...

Страница 12: ...h leakage circuit breaker in a location that is not exposed to high temperatures If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease Use a breaker Included with earth leakage circuit breaker that is capable of handling high frequencies Because the outdoor unit is inverter controlled a high frequency breaker is necessary to prevent a malfun...

Страница 13: ... trapped in the outdoor unit may cause a short circuit in the electrical component box Be careful not to deform or scratch the panel while opening the knockout holes After opening the knockout holes remove burr on the edges and attach the conduit or grommet edging accessories to prevent damaging the cables It is recommended to apply rust proof paint on the edges to prevent rust Electric wires can ...

Страница 14: ...c address setting for the indoor unit connect the indoor unit to outdoor units under the same refrigerant system Example Disable Auto matic Address setting Refrigerant system 1 Refrigerant system 2 Transmission line Transmission line Example Enable Auto matic Address setting Refrigerant system 1 Refrigerant system 2 Transmission line Transmission line 6 6 Wiring procedure Remove the cover of the e...

Страница 15: ...sted pair cables Wind with insulation tape to prevent short circuit Use one side of the twisted pair cable Connect both ends of shielded wire to earth Ground RB IN Cable clip Cable tie accessory 40 mm or more 8 to 10 mm 6 7 External input and external output 6 7 1 Terminal position Input 5 CN135 ORANGE Outdoor unit PC board CN131 YELLOW CN136 BLACK CN137 BLUE CN134 RED CN115 BLACK CN133 WHITE Inpu...

Страница 16: ...erminal and the selection of function are set with the push button on the PC board of outdoor unit About the setting please refer to 7 4 Push but ton setting NOTES 1 The external input priority mode must be set by pressing push button on PC board of outdoor unit Refer to 7 FIELD SETTING 2 Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button Refer to 7 FIELD SET...

Страница 17: ...em when necessary 12 Heating capacity shift 1 Normal mode 1 2 0 0 z Save energy mode 0 1 High power mode 1 0 2 High power mode 2 0 3 Set this item when necessary 13 Prohibited Factory default 1 3 0 0 z 14 Prohibited Factory default 1 4 0 0 z 15 Prohibited Factory default 1 5 0 0 z 20 Switching be tween batch stop or emergency stop 1 Batch stop 2 0 0 0 z Emergency stop 0 1 This mode selects the pat...

Страница 18: ...ohibited Factory default 6 3 0 0 z 70 Electricity meter No setting 1 2 Setting number x00 7 0 0 0 z Setting number x01 0 1 Setting number x98 9 8 Setting number x99 9 9 Set the ones digit and tens digit of the No of the electricity meter connected to CN135 71 Electricity meter No setting 2 2 Setting number 0xx 7 1 0 0 z Setting number 1xx 0 1 Setting number 2xx 0 2 Set the hundreds digit of the No...

Страница 19: ...ed Refer to the indoor unit installation manual for the procedures to check the addresses 7 6 2 Procedures to enable automatic address setting on indoor units Check that the rotary switch IU AD on the indoor unit PC board is set to 00 If it is not set to 00 it means the address of that device is not set Factory default is 00 Turn on the power of the indoor and outdoor units When the system is norm...

Страница 20: ...iping follow below i e if doing work during the rainy season if the actual work takes long enough that condensation may form on the inside of the pipes if rain might enter the pipes during work etc After operating the vacuum pump for 2 hours pressurize to 0 05 MPa i e vacuum breakdown with nitrogen gas then depressurize down to 100 7 kPa 755 mmHg for an hour using the vacuum pump vacuum process If...

Страница 21: ... an M4 hexagon wrench for liquid pipe Use an M8 hexagon wrench for suction gas pipe and discharge gas pipe If you cannot charge the specified amount of refrigerant with the above method be sure to charge the refrigerant through the gas pipe while operating in cooling mode In order to prevent liquid back flow carefully operate the refrigerant cylinder valve so that the refrigerant will flow in cert...

Страница 22: ...r unit Therefore use putty in the space between the pipe and the insulation to prevent the entry of water Putty Insulation Table Selection of insula tion Use an insulation material with equal heat transmis sion rate or below 0 040 W m k When the ambient tempera ture and relative humid ity exceed 32 C DB and 85 respectively please strengthen heat insulation of refrigerant pipe Relative humidity Ins...

Страница 23: ...tor error E 9 3 1 Outdoor unit inverter compressor start up error E 9 4 1 Outdoor unit trip detection E 9 5 5 Outdoor unit compressor motor loss of synchronization E 9 7 1 Outdoor unit fan motor lock error E 9 7 5 Outdoor unit fan motor temperature error protec tive action E 9 7 9 Outdoor unit fan motor driver error E 9 A 1 Outdoor unit coil 1 expansion valve 1 error E 9 A 2 Outdoor unit coil 2 ex...

Отзывы: