14-4. Pump down
WARNING
During the pump down operation, make sure that compressor is off before you remove the refrig-
erant piping. Do not remove the connection pipe while the compressor is in operation with valve
open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and
even injury.
¢
Pump down operation
When moving or discarding the air conditioner, in order to consider the environment and avoid the
discharge of refrigerant to the atmosphere, pump down according to the following procedure.
1. Connect the pressure gauge to the charging port.
2. Change the DIP switch on the board (SET1-2) to On*1
*Be sure the power supply is disconnected on the breaker is turned off when changing the
DIP switch.
*1: DIP switch
(SET1-2)
ON
1 2 3 4
SET1
3. To start operation, press the [PUMP DOWN] switch*2 for 3 seconds or press after the power
has been on for 3 min.
PUMP DOWN
1
W
S
TEST
RUN
*2: Push switch (SW1)
During pump down, the LED (POWER/MODE) will flash 3 times consecutively.
(3-blink)
F
E
D
C
MONITOR
ERROR
B
A
POWER
MODE
NOTE:
If the [PUMP DOWN] switch is pressed during compressor operation, the compres-
sor will stop, and the operation will start after about 3 min.
4. Close the liquid pipe valve.
5. When the value between 7.3 psi and 0 psi (0.05 Mpa to 0 Mpa) is shown, close the gas pipe
valve.
6. Stop pump down by pressing the [PUMP DOWN] switch for 3 seconds.
The LED will light as follows.
F
E
D
C
MONITOR
ERROR
B
A
POWER
MODE
(3-blink)
- 413 -
OUTDOOR UNIT
AOYG45LBLA6
Содержание agyg09lvca
Страница 8: ......
Страница 52: ...4 4 Wall mounted type Models ASYG07LUCA ASYG09LUCA ASYG12LUCA and ASYG14LUCA 44 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 54: ... Models ASYG18LFCA ASYG24LFCA and ASYG24LFCC 46 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 55: ...4 5 Floor Ceiling type Models ABYG14LVTA and ABYG18LVTB 47 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 56: ...4 6 Floor type Models AGYG09LVCA AGYG12LVCA and AGYG14LVCA 48 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 141: ...8 7 Sound level check point Compact cassette type Microphone Microphone 1 5m 133 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 281: ...Part 2 OUTDOOR UNIT 5 ROOMS TYPE MULTI TYPE AOYG36LBLA5 ...
Страница 289: ...5 Wiring diagram 5 1 Model AOYG36LBLA5 281 OUTDOOR UNIT AOYG36LBLA5 ...
Страница 352: ... 344 OUTDOOR UNIT AOYG36LBLA5 ...
Страница 353: ...Part 3 OUTDOOR UNIT 6 ROOMS TYPE MULTI TYPE AOYG45LBLA6 ...
Страница 360: ...5 Wiring diagram 5 1 Model AOYG45LBLA6 352 OUTDOOR UNIT AOYG45LBLA6 ...