UTY-RNRYZ*
Setting procedure by using wired remote controller
The function number and the associated setting value are displayed on the LCD of the remote
controller. Follow the instructions written in the local setup procedure supplied with the remote
controller, and select appropriate setting according to the installation environment.
Before connecting the power supply of the indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
1.
Connect the power supply.
2.
When the “Function Setting” on the “Maintenance” screen is touched, the “Installer Pass-
word Verification” screen is displayed. After enter the installer password, and touch the “OK”,
“Function Setting” screen is displayed.
Previous
Page
Back
Next
Page
Page 2/ 3
Maintenance
Test Run
R.C. Address
Setting
Function Setting
I.U. Address
Setting
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back
Setting
Address setting mode initial display
3.
Touch the “Address” on the “Function Setting” screen.
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back
Setting
4.
“Address” screen is displayed. Select the address of the indoor unit whose function number
is be set by touching or . When setting at all the indoor units, touch “All”.
002–01
Address
Cancel
OK
All
When the “OK” is touched, the display returns to the “Function Setting” screen.
5.
Touch the “Function No.” on the “Function Setting” screen.
[002–01]
[00]
[00]
Address
Function No.
Setting No.
Function Setting
Back
Setting
- 231 -
MULTI TYPE
5, 6 ROOMS TYPE
Содержание agyg09lvca
Страница 8: ......
Страница 52: ...4 4 Wall mounted type Models ASYG07LUCA ASYG09LUCA ASYG12LUCA and ASYG14LUCA 44 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 54: ... Models ASYG18LFCA ASYG24LFCA and ASYG24LFCC 46 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 55: ...4 5 Floor Ceiling type Models ABYG14LVTA and ABYG18LVTB 47 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 56: ...4 6 Floor type Models AGYG09LVCA AGYG12LVCA and AGYG14LVCA 48 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 141: ...8 7 Sound level check point Compact cassette type Microphone Microphone 1 5m 133 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 281: ...Part 2 OUTDOOR UNIT 5 ROOMS TYPE MULTI TYPE AOYG36LBLA5 ...
Страница 289: ...5 Wiring diagram 5 1 Model AOYG36LBLA5 281 OUTDOOR UNIT AOYG36LBLA5 ...
Страница 352: ... 344 OUTDOOR UNIT AOYG36LBLA5 ...
Страница 353: ...Part 3 OUTDOOR UNIT 6 ROOMS TYPE MULTI TYPE AOYG45LBLA6 ...
Страница 360: ...5 Wiring diagram 5 1 Model AOYG45LBLA6 352 OUTDOOR UNIT AOYG45LBLA6 ...