1. Specifications
Type
Inverter heat pump
Model name
AOYG36LBLA5
Power supply
230 V ~ 50 Hz
Available voltage range
198—264 V
Standard combination of indoor unit
Wall mounted
ASYG07LMCA × 4
ASYG09LMCA × 1
Capacity
Cooling
Rated
kW
10.0
Btu/h
34,100
Min.—Max.
kW
3.5—12.5
Btu/h
11,900—42,700
Heating
Rated
kW
12.0
Btu/h
41,000
Min.—Max.
kW
3.5—14.0
Btu/h
11,900—47,800
Input power
Cooling
Rated
kW
2.44
Max.
4.04
Heating
Rated
2.79
Max.
3.98
Current
Cooling
Rated
A
10.6
Max.
20.6
Heating
Rated
12.3
Max.
20.6
EER
Cooling
kW/kW
4.10
COP
Heating
4.30
Starting current
A
12.3
Maximum operating current *
1
A
20.6
Fan
Airflow rate
Cooling
m
3
/h
4,200
Heating
Type × Q'ty
Propeller × 1
Motor output
W
111
Sound pressure level*
2
Cooling
dB (A)
53
Heating
55
Heat exchanger type
Dimensions
(H × W × D)
mm
966 × 922 × 55
Fin pitch
1.45
Rows × Stages
3 ×46
Pipe type
Copper
Fin type
Type (Material)
Corrugate (Aluminum)
Surface treatment
Corrosion resistance (Blue fin)
Compressor
Type × Q'ty
DC twin rotary × 1
Motor output
W
2,100
Refrigerant
Type (Global warming potential)
R410A (2088)
Charge
g
4,000
Refrigerant oil
Type
RB68
Amount
cm
3
1,150
Enclosure
Material
Steel sheet
Color
Beige
(Approximate color of Munsell 10YR 7.5/1.0 NN)
Dimensions
(H × W × D)
Net
mm
998 × 970 × 370
Gross
1,162 × 1,150 × 478
Weight
Net
kg
94
Gross
104
Connection pipe
Size
Liquid
mm
Ø 6.35 (Ø 1/4) x 5
Gas
Ø 9.52 (Ø3/8) x 3 + Ø 12.70 (Ø 1/2) x 2
Method
Flare
Pre-charge length (Total)
m
50
Maximum length (Total)
80
Maximum length (Each)
25
Minimum length (Total)
15
Minimum length (Each)
5
Maximum height difference between out-
door unit and each indoor units.
15
Maximum height difference between in-
door units.
10
Operation range
Cooling
°C
-10 to 46
Heating
-15 to 24
NOTES:
• Specifications are based on the following conditions:
– Power source of specifications: 230 V
– Pipe length: 5 m, Height difference: 0 m [Outdoor unit—Indoor unit]
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
• *1: The maximum current is the maximum value when the operated within the operation range.
• *2: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *3: Connect to connection valve by the adapter.
• For other combination, refer to the combination table.
• The protective function might work when using it outside the operation range.
DESIGN & TECHNICAL MANUAL
- 274 -
OUTDOOR UNIT
AOYG36LBLA5
Содержание agyg09lvca
Страница 8: ......
Страница 52: ...4 4 Wall mounted type Models ASYG07LUCA ASYG09LUCA ASYG12LUCA and ASYG14LUCA 44 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 54: ... Models ASYG18LFCA ASYG24LFCA and ASYG24LFCC 46 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 55: ...4 5 Floor Ceiling type Models ABYG14LVTA and ABYG18LVTB 47 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 56: ...4 6 Floor type Models AGYG09LVCA AGYG12LVCA and AGYG14LVCA 48 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 141: ...8 7 Sound level check point Compact cassette type Microphone Microphone 1 5m 133 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 281: ...Part 2 OUTDOOR UNIT 5 ROOMS TYPE MULTI TYPE AOYG36LBLA5 ...
Страница 289: ...5 Wiring diagram 5 1 Model AOYG36LBLA5 281 OUTDOOR UNIT AOYG36LBLA5 ...
Страница 352: ... 344 OUTDOOR UNIT AOYG36LBLA5 ...
Страница 353: ...Part 3 OUTDOOR UNIT 6 ROOMS TYPE MULTI TYPE AOYG45LBLA6 ...
Страница 360: ...5 Wiring diagram 5 1 Model AOYG45LBLA6 352 OUTDOOR UNIT AOYG45LBLA6 ...