11. External input and output
11-1. Compact cassette, slim duct, wall mounted, floor/ceiling,
and floor types
Indoor unit
type
External input
External output
Control input
Operation
status output
Fresh air
control output
Auxiliary
heater output
Error status
output
Compact
cassette
●
●
●
―
―
Slim duct
●
●
●
●
―
Wall mounted
●
●
―
―
●
(LU/LM types)
Floor/Ceiling
●
●
―
―
―
Floor
●
●
―
―
―
¢
External input
With using external input function, some functions on this product can be controlled from an exter-
nal device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor
unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
Control input (Operation/Stop or Forced stop)
Indoor unit type
Connector
Compact cassette
CN102
Slim duct
Wall mounted
LU/LM
CNA01
LF
CN14
Floor/Ceiling
CN102
Floor
CN14
The air conditioner can be remotely operated by means of the following on-site work.
Operation is started at the following contents by adding the contact input of a commercial on/off
switch to a connector on the external control PCB and turning it on.
Unit operation
Initial setting after power is on
Starting mode other than initial
setting
Operation mode
Auto changeover
Mode at previous operation
Set temperature
24 °C
Temperature at previous operation
Airflow mode
AUTO
Mode at previous operation
Air direction (swing)
Standard air direction (swing: off)
Air direction at previous operation
DESIGN & TECHNICAL MANUAL
- 138 -
MULTI TYPE
5, 6 ROOMS TYPE
Содержание agyg09lvca
Страница 8: ......
Страница 52: ...4 4 Wall mounted type Models ASYG07LUCA ASYG09LUCA ASYG12LUCA and ASYG14LUCA 44 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 54: ... Models ASYG18LFCA ASYG24LFCA and ASYG24LFCC 46 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 55: ...4 5 Floor Ceiling type Models ABYG14LVTA and ABYG18LVTB 47 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 56: ...4 6 Floor type Models AGYG09LVCA AGYG12LVCA and AGYG14LVCA 48 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 141: ...8 7 Sound level check point Compact cassette type Microphone Microphone 1 5m 133 MULTI TYPE 5 6 ROOMS TYPE ...
Страница 281: ...Part 2 OUTDOOR UNIT 5 ROOMS TYPE MULTI TYPE AOYG36LBLA5 ...
Страница 289: ...5 Wiring diagram 5 1 Model AOYG36LBLA5 281 OUTDOOR UNIT AOYG36LBLA5 ...
Страница 352: ... 344 OUTDOOR UNIT AOYG36LBLA5 ...
Страница 353: ...Part 3 OUTDOOR UNIT 6 ROOMS TYPE MULTI TYPE AOYG45LBLA6 ...
Страница 360: ...5 Wiring diagram 5 1 Model AOYG45LBLA6 352 OUTDOOR UNIT AOYG45LBLA6 ...