background image

En-7

Remote controller holder fi xing

Remote controller mounting

Remote controller 
holder

Tapping 
screw 
(small)

Remote 
controller

(1) Set

(2) Push

11. OPTIONAL KIT INSTALLATION (OPTION)

This air conditioner can be connected with the following optional kits. Refer to each 
installation manual for the method of installing optional parts.
•  Wired remote controller
•  Simple remote controller
•  External connect kit

]

11.1.  Before install optional remote controller

•  When you use optional remote controller, some functions may not be used.
•  Please use the recommended optional remote controller.

 CAUTION

Before installing, be sure to disconnect all power supply.

Don’t touch the heat exchanger.

During installing or removing operation, be sure not to have wire caught by parts or 
draw it hard. Or it may result troubles to the air-conditioner.

Avoid place in direct sunlight.

Select place that will not be affected by the heat from a stove, etc.

Before setting up the optional kit, please confi rm whether air-conditioner can receive 
the signal.

Do not connect the optional remote controller to the terminal for power supply.

When connecting the optional remote controller with the indoor unit, please use the 
connecting cable packaged up with the optional remote controller.

Recommended cable length of optional remote controller is 10 m (33 ft). Make sure to 
do insulate of connecting part when extended the cable.

]

11.2.  Remote controller cable modifi cation

1

(1)  Use a tool to cut off the terminal on the end of the remote controller cable, and then 

remove the insulation from the cut end of the cable.

(2)  Connect the remote controller cable and connecting cable. (supplied with wired remote 

controller) 

Important:

  Be sure to solder wires to connect. Be sure to insulate the connection between 

the wires.

Connecting cable

White

Red

White

Red

Black

Black

Insulated 
connection

Remote 
controller cable

Remote 
controller cable

20 mm

11.3.  External input / output Wire modifi cation

(1)  Remove insulation from wire attached to wire kit 

connector. Remove insulation from fi eld supplied 
cable. Use crimp type insulated butt connector to 
join fi eld cable and wire kit wire.

(2)  Connect the wire and Field supply wire. 

(supplied with external connect kit)

Important:

Be sure to solder wires to connect. Be sure to 
insulate the connection between the wires.

Option parts 
External input/
output wire

Cable 
(Field supply)

Insulated 
connection

]

Check the following:

GOOD

NO GOOD

NO GOOD

Accumulated 
drain water

No upward 
slope

50 mm or less from 
earth (ground)

Stopping 
downward

No upward 
slope

End of drain hose 
is immersed in 
water.

Drainage 
channel

Air

NO GOOD

NO GOOD

NO GOOD

9. TEST RUN

 WARNING

Do not turn on the power until all installation work is complete.

 CAUTION

When restarting after a long period of disuse in the winter, turn the power switch on at 
least 12 hours before starting the unit.

Check items

(1)  Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do air fl ow direction louvers operate normally?
(4) Is the drain normal?
(5)  Do not have an error noise and vibration during operation?

 Do not operate the air conditioner in test run for a long time.

[Operation method]

  For the operation method, refer to the operating 

manual.

  The outdoor unit may not operate depending on 

the room temperature. In this case, press the 
test run button on the remote controller while the 
air conditioner is running. (Point the transmitter 
section of the remote controller toward the air 
conditioner and press the test run button with the 
tip of a ballpoint pen, etc.)

  To end test operation, press the remote controller 

START/STOP button. (When the air conditioner 
is running by pressing the test run button, the 
OPERATION Lamp and TIMER Lamp will 
simultaneously fl ash slowly.)

Transmitter section

Test run button

[Using the wired remote control] (Option)

  For the operation method, refer to the operating 

manual.

(1) Stop the air conditioner operation.

(2)  Press the master control button and the fan 

control button simultaneously for 2 seconds or 

more to start the test run.

(3) Press the start/stop button to stop the test run.

Test run display

10. REMOTE CONTROLLER INSTALLATION

 CAUTION

Check that the indoor unit correctly receives the signal from the remote controller, then 
install the remote controller holder.

Select the remote controller holder selection site by paying careful attention to the 
following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from a stove, etc.

10.1.

 

Remote controller holder installation

•  Install the remote controller a maximum distance of 7 m from the remote control 

receiver. However, when installing the remote controller, check that it operates correctly.

•  Install the remote controller holder to a wall, pillar, etc. with the tapping screw.

9378533028-03_IM.indb   7

9378533028-03_IM.indb   7

2011-10-08   11:08:54

2011-10-08   11:08:54

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание agyg09lvca

Страница 1: ...l autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir AIR CONDITIONER INDOOR UNIT Floor Type PART NO 9378533028 03 9378533028 03_IM indb 1 9378533028 03_I...

Страница 2: ...pecially when replacing a conventional refrigerant R22 model with a new refrigerant R410A model always replace the conventional piping and flare nuts with the R410A piping and flare nuts Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread d...

Страница 3: ...he entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning 1 3 1 Type of copper pipe and insulation material CAUTION Refer to the installation manual for the outdoor unit for description of allowable pipe length and height difference MODEL Diameter Liquid pipe Gas pipe 9 000 Btu h model 6 35 mm 1 4 in 9 52 mm 3 8 in ...

Страница 4: ...the upper or lower air outlet is blocked the air conditioner will not be able to cool or warm the room well Do not block the receiver with the grating Otherwise the grating will interfere with the remote controller signal and significantly reduce the distance and area angle from which the signals can be received Use a grating with vertical bars etc that has at least 75 open area If the grating has...

Страница 5: ...ccording to the direction of piping Rear piping Left piping Center of wall holl 130 mm Floor 280 mm 245 mm Back wall 100 mm Back wall 690 mm Right piping 30 mm Back wall 6 6 Note on drain hose CAUTION Insert drain hose and drain cap securely Drain should slope down to avoid water leakage When inserting be sure not to attach any material besides water If any other material is attached it will cause...

Страница 6: ...rm the flare processing with a flare tool Use the special R410A flare tool or the conventional flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked or scratched Pipe Die Pipe outside diameter mm in Dimension A mm Dimension ...

Страница 7: ...e tool so that the wires do not come loose Strip 10 mm Sleeve Crimp type terminal 3 Use the specified wires connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 ...

Страница 8: ...supply Insulated connection Check the following GOOD NO GOOD NO GOOD Accumulated drain water No upward slope 50 mm or less from earth ground Stopping downward No upward slope End of drain hose is immersed in water Drainage channel Air NO GOOD NO GOOD NO GOOD 9 TEST RUN WARNING Do not turn on the power until all installation work is complete CAUTION When restarting after a long period of disuse in ...

Страница 9: ...mode STEP 1 Selecting the Remote Controller Signal Code Use the following steps to select the signal code of the remote controller Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code The signal codes that are set through this process are applicable only to the signals in the FUNCTION SETTING For details on how to set the signal cod...

Страница 10: ...ption Function Number Setting Value Yes 40 00 No 01 Auto restart is an emergency function such as for power failure etc Do not start and stop the indoor unit by this function in normal operation Be sure to operate by the control unit or external input device Indoor room temperature sensor switching function Only for Wired remote controller The following settings are needed when using the Wired rem...

Страница 11: ...ter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor e...

Отзывы: