background image

En-4

Screw

[

] mark

Side panel R

Base

Base

Side panel R

 CAUTION

Install the SIDE PANEL L, R and INTAKE GRILLE securely. If installation is imperfect, 
the SIDE PANEL L, R or INTAKE GRILLE may fall off and cause injury.

]1

6.4.  Cutting the hole in the wall for the connecting piping

(1)  Cut a 65 mm diameter hole in the wall at the position shown in the fi gure.
(2)  Always align the center of the wall hole. If misaligned, water leakage will occur.
(3)  Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap 

with vinyl tape, and stick the pipe through the hole. (The connection pipe is supplied in 
the installation set.)

(4)  For left piping and right piping, cut the hole a little lower so that drain water will fl ow 

freely.

For RIGHT REAR or LEFT REAR piping

(The following fi gure is a front view of the indoor unit installation location.)

Unit: mm

FOR RIGHT 
REAR PIPING

48

59

550

59

Ø65

Ø65

FOR LEFT 
REAR PIPING

For RIGHT or LEFT piping

8

16

5

54

54

8

16

5

FOR RIGHT 
PIPING

FOR LEFT 
PIPING

Unit: mm

For RIGHT BOTTOM or LEFT BOTTOM piping

29

64

182

29

5

3

1

0

5

FOR RIGHT 
BOTTOM 
PIPING

Unit: mm

FOR LEFT 
BOTTOM 
PIPING

 

5 to 10 mm

Fasten with 
vinyl tape

Wall cap*

Wall pipe*

*Field supplied

(Inside)

Wall

(Outside)

 WARNING

If the wall pipe is not used, 
the wire interconnecting the 
indoor and outdoor units may 
touch metal and cause electric 
leakage.

6.5. Forming piping

(1) Pass the refrigerant pipe through the piping hole to indoor side.
(2) Arrange the pipes according to the direction of piping.

Rear piping

Left piping

Center of 
wall holl

130 mm

Floor

280 mm

245 mm

Back wall

100 mm

Back wall

690 mm

Right piping

30 mm

Back wall

6.6.  Note on drain hose

 CAUTION

Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage.

When inserting, be sure not to attach any material besides water. If any other material 
is attached, it will cause deterioration and water leakage.

After removing drain hose, be sure not to forget mounting drain cap.

Be sure to fi x the drain hose with tape to the bottom of piping.

Prevent drain water freezing under low temperature environment.
When installing indoor unit’s drain hose outdoors, necessary measure for frost 
protection should be taken to prevent drain water freezing.
Under low temperature environment (when outdoor temperature under 0 °C), after 
cooling operation is executed, water in the drain hose could be frozen.
Once drain water is frozen, the drain hose will be blocked and water leakage may 
result at the indoor unit.

The drain hose can be connected at either side of the indoor unit.

The unit has been shipped with the drain hose connected at left (viewed from the back of 
the unit) and the drain cap applied at right.
(1) Remove the both side panels.
(2) Remove the screw and remove the drain holder from drain pan.
(3) Pull out the drain cap.
(4)  Connect the drain hose to the right, attach the screw and insert the drain cap to the left.

DRAIN 
HOSE

DRAIN CAP

Drain pan

DRAIN HOSE

Drain holder

Screw

Drain pan

DRAIN CAP

9378533028-03_IM.indb   4

9378533028-03_IM.indb   4

2011-10-08   11:08:46

2011-10-08   11:08:46

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание agyg09lvca

Страница 1: ...l autorizado MANUALE D INSTALLAZIONE Ad uso esclusivo del personale autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir AIR CONDITIONER INDOOR UNIT Floor Type PART NO 9378533028 03 9378533028 03_IM indb 1 9378533028 03_I...

Страница 2: ...pecially when replacing a conventional refrigerant R22 model with a new refrigerant R410A model always replace the conventional piping and flare nuts with the R410A piping and flare nuts Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread d...

Страница 3: ...he entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning 1 3 1 Type of copper pipe and insulation material CAUTION Refer to the installation manual for the outdoor unit for description of allowable pipe length and height difference MODEL Diameter Liquid pipe Gas pipe 9 000 Btu h model 6 35 mm 1 4 in 9 52 mm 3 8 in ...

Страница 4: ...the upper or lower air outlet is blocked the air conditioner will not be able to cool or warm the room well Do not block the receiver with the grating Otherwise the grating will interfere with the remote controller signal and significantly reduce the distance and area angle from which the signals can be received Use a grating with vertical bars etc that has at least 75 open area If the grating has...

Страница 5: ...ccording to the direction of piping Rear piping Left piping Center of wall holl 130 mm Floor 280 mm 245 mm Back wall 100 mm Back wall 690 mm Right piping 30 mm Back wall 6 6 Note on drain hose CAUTION Insert drain hose and drain cap securely Drain should slope down to avoid water leakage When inserting be sure not to attach any material besides water If any other material is attached it will cause...

Страница 6: ...rm the flare processing with a flare tool Use the special R410A flare tool or the conventional flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes L Check if L is flared uniformly and is not cracked or scratched Pipe Die Pipe outside diameter mm in Dimension A mm Dimension ...

Страница 7: ...e tool so that the wires do not come loose Strip 10 mm Sleeve Crimp type terminal 3 Use the specified wires connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 ...

Страница 8: ...supply Insulated connection Check the following GOOD NO GOOD NO GOOD Accumulated drain water No upward slope 50 mm or less from earth ground Stopping downward No upward slope End of drain hose is immersed in water Drainage channel Air NO GOOD NO GOOD NO GOOD 9 TEST RUN WARNING Do not turn on the power until all installation work is complete CAUTION When restarting after a long period of disuse in ...

Страница 9: ...mode STEP 1 Selecting the Remote Controller Signal Code Use the following steps to select the signal code of the remote controller Note that the air conditioner cannot receive a signal code if the air conditioner has not been set for the signal code The signal codes that are set through this process are applicable only to the signals in the FUNCTION SETTING For details on how to set the signal cod...

Страница 10: ...ption Function Number Setting Value Yes 40 00 No 01 Auto restart is an emergency function such as for power failure etc Do not start and stop the indoor unit by this function in normal operation Be sure to operate by the control unit or external input device Indoor room temperature sensor switching function Only for Wired remote controller The following settings are needed when using the Wired rem...

Страница 11: ...ter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way valve temp sensor error 3 way valve temp sensor error 7 7 Heat sink temp sensor e...

Отзывы: