10) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
Setting value
Setting description
Factory setting
44
00
A
♦
01
B
02
C
03
D
11) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number
Setting value
Setting description
Factory setting
46
00
Operation/Stop mode 1
♦
01
(Setting prohibited)
02
Forced stop mode
03
Operation/Stop mode 2
NOTE:
If this function is necessary, the rotary switch on the External input and output PCB should
be set to 1.
12) Room temperature sensor switching (Aux.) (for other than Floor type)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired re-
mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting 30 and 31 too.
Function number
Setting value
Setting description
Factory setting
48
00
Both
♦
01
Wired remote controller
13) Indoor unit fan control for energy saving for cooling (for other than Floor type)
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number
Setting value
Setting description
Factory setting
49
00
Disable
01
Enable
02
Remote controller
♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTE:
Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for
energy saving function or connecting a network converter. To confirm if the remote con-
troller has this setting, refer to the operating manual of each remote controller.
1-5. Function details
- (05-45) -
1. Function settings (for indoor unit)
FIELD
WORKING
FIELD
WORKING
Содержание AGHG09KVCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 15 SR_CH01_MU001EG_04 ...
Страница 40: ...2 6 Outdoor unit 01 34 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 41: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 15 SR_CH02_MU001EG_05 ...
Страница 44: ......
Страница 161: ...3 TROUBLESHOOTING 2022 04 13 SR_CH03_MU001EG_04 ...
Страница 164: ......
Страница 259: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU001EG_06 ...
Страница 262: ......
Страница 351: ...5 FILED WORKING 2022 04 13 SR_CH05_MU001EG_05 ...