Wall mounted type (For KGTB)
•
Rotation number range of compressor
Unit: rps
Connected outdoor unit model
name
Minimum rotation number
Maximum rotation number
AOHG14KBTA2
12
110
AOHG18KBTA2
8
120
•
Limit of maximum speed based on outdoor temperature
A zone
26°C
B zone
C zone
D zone
23°C
20°C
Unit: rps
– Model: AOHG14KBTA2
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASHG07KGTB
ASHG09KGTB
ASHG12KGTB
ASHG14KGTB
A zone
89
67
58
50
B zone
89
77
67
58
C zone
110
96
83
72
D zone
110
110
110
110
– Model: AOHG18KBTA2
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH
MED
LOW
QUIET
ASHG07KGTB
ASHG09KGTB
ASHG12KGTB
ASHG14KGTB
A zone
94
68
58
50
B zone
94
80
68
58
C zone
120
102
87
74
D zone
120
120
120
120
1-1. Cooling operation
- (04-5) -
1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание AGHG09KVCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 15 SR_CH01_MU001EG_04 ...
Страница 40: ...2 6 Outdoor unit 01 34 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 41: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 15 SR_CH02_MU001EG_05 ...
Страница 44: ......
Страница 161: ...3 TROUBLESHOOTING 2022 04 13 SR_CH03_MU001EG_04 ...
Страница 164: ......
Страница 259: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU001EG_06 ...
Страница 262: ......
Страница 351: ...5 FILED WORKING 2022 04 13 SR_CH05_MU001EG_05 ...