2-10. E: 33. Indoor unit motor electricity consumption detection
error (Indoor unit)
Indicator
Indoor unit
Operation indicator
3 time flash
Timer indicator
3 time flash
Economy indicator
Continuous flash
Error code
E: 33
Detective actuator
Indoor unit motor electricity
consumption detection
When the voltage value or the current value of the motor
go beyond the limits
Forecast of cause
Fan motor failure
Main PCB failure
Check point 1. Check the rotation of fan
Rotate the fan by hand when the operation is off. (Check if fan is caught, drop off or locked motor)
→ If fan or bearing is abnormal, replace it.
↓
Check point 2. Check ambient temperature around the motor
Check excessively high temperature around the motor. (If there is any surrounding equipment that
causes heat.)
→ Upon the temperature coming down, restart operation.
↓
Check point 3. Check indoor unit fan motor
Check indoor unit fan motor. (Refer to indoor unit fan motor in
03-78.)
→ If indoor unit fan motor is abnormal, replace it.
↓
Check point 4. Replace the main PCB
If check point 1-3 does not improve the symptom, replace the main PCB.
↓
End
2-10. E: 33. Indoor unit motor electricity consumption detection error (Indoor unit)
- (03-23) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание AGHG09KVCA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 03 15 SR_CH01_MU001EG_04 ...
Страница 40: ...2 6 Outdoor unit 01 34 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 41: ...2 TECHNICAL DATA AND PARTS LIST 2022 03 15 SR_CH02_MU001EG_05 ...
Страница 44: ......
Страница 161: ...3 TROUBLESHOOTING 2022 04 13 SR_CH03_MU001EG_04 ...
Страница 164: ......
Страница 259: ...4 CONTROL AND FUNCTIONS 2022 04 13 SR_CH04_MU001EG_06 ...
Страница 262: ......
Страница 351: ...5 FILED WORKING 2022 04 13 SR_CH05_MU001EG_05 ...