5) Auto restart
Enable or disable automatic system restart after a power outage.
(
... Factory setting)
Setting description
Function number
Setting value
Yes
40
00
No
01
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate using the remote controller, or external input device.
6) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller
temperature sensor.
(
... Factory setting)
Setting description
Function number
Setting value
No
42
00
Yes
01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote controller
unit sensor.
7) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(
... Factory setting)
Setting description
Function number
Setting value
A
44
00
B
01
C
02
D
03
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
... Factory setting)
Setting description
Function number
Setting value
Operation/Stop mode
46
00
(Setting forbidden)
01
Forced stop mode
02
9) Indoor unit fan control for energy saving (Only cooling mode)
Enable or disable indoor unit fan control when the outdoor unit is stopped.
(
... Factory setting)
Setting description
Function number
Setting value
No
49
00
Yes
01
* If setting value is “00”:
When the outdoor unit is stopped, the indoor unit fan operates following the setting on the
remote controller continuously.
* If setting value is “01”:
When the outdoor unit is stopped, the indoor unit fan operates at very low speed intermittently.
Содержание AG G09LVCB series
Страница 2: ...1 INDOOR UNIT FLOOR TYPE AG G09LVCB AG G12LVCB AG G14LVCB DTR_AG004E_03 2013 01 21 ...
Страница 33: ...2 OUTDOOR UNIT SINGLE TYPE AO G09LVCN AO G12LVCN AO G14LVCN DTR_AO094E_02 2013 01 21 ...
Страница 39: ... 02 05 OUTDOOR UNIT AO G09 14LVCN OUTDOOR UNIT AO G09 14LVCN WIRING DIAGRAMS 444 MODEL AO G09LVCN AO G12LVCN ...
Страница 40: ... 02 06 OUTDOOR UNIT AO G09 14LVCN OUTDOOR UNIT AO G09 14LVCN MODEL AO G14LVCN ...
Страница 47: ... 02 13 OUTDOOR UNIT AO G09 14LVCN OUTDOOR UNIT AO G09 14LVCN SOUND LEVEL CHECK POINT 88888 ...