4) Room temperature control for heating
Depending on the installed environment, correction of the room temperature sensor may be
required.
Select the appropriate control setting according to the installed environment.
(
. . .Factory setting)
Setting Description
Function Number
Setting Value
Standard
31
00
Lower control
01
Slightly higher control
02
Higher control
03
5) Auto restart
Enable or disable automatic restart after a power interruption.
(
. . .Factory setting)
Setting Description
Function Number
Setting Value
Enable
40
00
Disable
01
* Auto restart is an emergency function such as for power outage etc. Do not attempt to use this
function in normal operation.
Be sure to operate the unit by remote controller or other external input device.
6) Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperture sensor, change the setting to "Both" (01).
(
. . .Factory setting)
Setting Description
Function Number
Setting Value
Indoor unit
42
00
Both
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller is active.
7) Remote controller signal code
(Only for wireless remote controller)
The indoor unit signal code can be changed. Select the appropriate signal code.
(
. . .Factory setting)
Setting Description
Function Number
Setting Value
A
44
00
B
01
C
02
D
03
Содержание AG*G09LVCA
Страница 2: ...1 INDOOR UNIT FLOOR TYPE AG G09LVCA AG G12LVCA AG G14LVCA DTR_AG005E_02 2013 07 19 ...
Страница 31: ...2 OUTDOOR UNIT SINGLE TYPE AO G09LVCA AO G12LVCA AO G14LVLA DTR_AO129E_01 2012 12 04 ...
Страница 36: ... 02 04 OUTDOOR UNIT AO G09 14LV OUTDOOR UNIT AO G09 14LV WIRING DIAGRAMS 444 MODEL AO G09LVCA AO G12LVCA ...
Страница 37: ... 02 05 OUTDOOR UNIT AO G09 14LV OUTDOOR UNIT AO G09 14LV MODEL AO G14LVLA ...
Страница 45: ... 02 13 OUTDOOR UNIT AO G09 14LV OUTDOOR UNIT AO G09 14LV SOUND LEVEL CHECK POINT 88888 ...