MODEL

„

„

 : AO

G14LVLA

Cooling

„

z

Heating

„

z

Number of 

rotations 

(r.p.m.)

Airflow

820

1,910

m

3

/h

531

l/s

1,124

CFM

Number of 

rotations 

(r.p.m.)

Airflow

750

1,750

m

3

/h

486

l/s

1,030

CFM

Содержание AG*G09LVCA

Страница 1: ...AIR CONDITIONER Floor type INDOOR OUTDOOR AG G09LVCA AG G12LVCA AG G14LVCA AO G09LVCA AO G12LVCA AO G14LVLA DESIGN TECHNICAL MANUAL ...

Страница 2: ...1 INDOOR UNIT FLOOR TYPE AG G09LVCA AG G12LVCA AG G14LVCA DTR_AG005E_02 2013 07 19 ...

Страница 3: ...AN PERFORMANCE AND CAPACITY 01 11 7 1 AIR VELOCITY DISTRIBUTION 01 11 7 2 AIRFLOW 01 12 8 OPERATION NOISE SOUND PRESSURE 01 14 8 1 NOISE LEVEL CURVE 01 14 8 2 SOUND LEVEL CHECK POINT 01 16 9 ELECTRIC CHARACTERISTICS 01 17 10 SAFETY DEVICES 01 18 11 EXTERNAL INPUT OUTPUT 01 19 11 1 EXTERNAL INPUT 01 19 11 2 EXTERNAL OUTPUT 01 21 12 FUNCTION SETTINGS 01 22 12 1 INDOOR UNIT Setting by remote controll...

Страница 4: ...iciency class z z MODEL AG G09LVCA AG G12LVCA AG G14LVCA Cooling A A A Heating A A A All DC z z Up and down twin fan operation z z Up to every corner of the room especially around the feet is heated evenly by two direction up and down discharge Cooling Heating DC Fan motor a DC compressor b a DC fan motor DC compressor b DC fan motor a AO G09 12LVCA AO G14LVLA ...

Страница 5: ...in hose Piping 1 6 5 2 3 4 Super quiet operation z z Airflow mode can be set in 4 steps and more detailed airflow setting is possible 10 C heating operation z z Operates in the 10 C heating mode so that the room does not become too cold even when you are absent during the winter etc Economy operation z z Example Cooling operation Temp Economy operation Shift setting temp Control maximum current No...

Страница 6: ...corrects the temperature thermostat setting according to the timer setting to prevent excessive cooling and heating while sleeping 60min 1 C 2 C Timer setting Set temp 1 C 30min 60min 90min 2 C 3 C 4 C Set temp Timer setting Cooling operation dry operation When the sleep timer is set the set temperature automatically rises 1 C every hour The set temperature can rise up to a maximum of 2 C Heating ...

Страница 7: ... 13 CLOCK ADJUST button 14 TEST RUN button This button is used when installing the air conditioner and should not be used under normal conditions as it will cause the indoor unit s thermostat function to operate incorrectly If this button is pressed during normal operation the indoor unit will switch to test operation mode and the Indoor Unit s OPERATION Indicator Lamp and TIMER Indicator Lamp wil...

Страница 8: ... Min Max 0 25 2 10 0 25 2 15 0 25 2 95 Current Cooling Rated A 2 6 4 4 5 2 Heating Rated 3 8 5 5 6 4 EER Cooling kW kW 4 91 3 72 3 68 COP Heating 4 43 3 78 3 61 Sensible capacity Cooling kW 2 33 2 66 3 15 Power factor Cooling 90 93 96 Heating 90 94 98 Moisture removal l h pints h 1 3 2 3 1 8 3 2 2 1 3 7 Maximum operating current Cooling Max A 7 0 7 0 9 0 Heating 10 0 10 0 13 5 Fan Airflow rate Coo...

Страница 9: ...ling A A A Heating Average A A A Pdesign Cooling kW 2 6 35 C 3 5 35 C 4 2 35 C Heating Average 2 9 10 C 3 8 10 C 4 7 10 C SEER Cooling kWh kWh 7 00 6 50 6 40 SCOP Heating Average 4 20 4 00 4 00 Annual energy consumption QCE kWh a 130 188 230 QHE Average 967 1330 1645 Sound power level Cooling High dB A 55 55 58 Heating 56 56 58 ...

Страница 10: ... view Side view INSTALLATION PLACE 10 cm or more 8 cm or more 8 cm or more 5 cm or more 15 cm or below from the floor AG G09LVCA AG G12LVCA AG G14LVCA Refrigerant pipe flare connection Liquid Ø 6 35 mm Ø 1 4 in Gas Ø 9 52 mm Ø 3 8 in Ø 12 7 mm Ø 1 2 in Drain hose connection Drain hose Ø 13 8 I D Ø 15 8 to Ø 16 7 O D Drain hose L 600 mm ...

Страница 11: ... 01 08 FLOOR TYPE AG G09 14LVCA FLOOR TYPE AG G09 14LVCA WIRING DIAGRAMS 555 MODEL AG G09LVCA AG G12LVCA AG G14LVCA TO OUTDOOR UNIT ...

Страница 12: ... 2 98 2 19 0 45 3 08 2 38 0 45 3 28 2 39 0 46 3 38 2 58 0 46 3 59 2 57 0 47 3 79 2 73 0 47 25 3 05 2 48 0 74 3 40 2 50 0 75 3 52 2 72 0 75 3 75 2 73 0 76 3 87 2 94 0 76 4 10 2 93 0 77 4 33 3 12 0 78 30 2 91 2 37 0 82 3 24 2 38 0 83 3 36 2 59 0 84 3 58 2 60 0 85 3 69 2 81 0 85 3 91 2 79 0 86 4 13 2 98 0 87 35 2 76 2 25 0 91 3 08 2 26 0 92 3 18 2 46 0 93 3 39 2 47 0 94 3 50 2 66 0 94 3 71 2 65 0 95 ...

Страница 13: ...door temperature CDB CWB TC IP TC IP TC IP TC IP TC IP 15 16 3 34 1 40 3 26 1 43 3 18 1 46 3 10 1 49 3 02 1 52 10 11 3 91 1 52 3 82 1 55 3 73 1 58 3 63 1 62 3 54 1 65 5 7 4 47 1 65 4 36 1 69 4 26 1 72 4 15 1 75 4 04 1 79 0 2 4 99 1 80 4 87 1 84 4 76 1 87 4 64 1 91 4 52 1 95 5 3 5 76 2 01 5 62 2 05 5 48 2 10 5 35 2 14 5 21 2 18 7 6 5 57 1 90 5 43 1 94 5 30 1 98 5 17 2 02 5 04 2 06 10 8 6 39 1 92 6 ...

Страница 14: ...ect UPPER LOWER UPPER FAN LOWER FAN 0 5 UPPER LOWER 1 0 2 1 0 1 2 Unit m s m m TOP VIEW FLOW CONTROL PANEL Horiz LOUVER Center 0 1 2 3 4 0 5 1 0 0 5 1 0 2 1 0 1 2 Unit m s m m TOP VIEW FLOW CONTROL PANEL Horiz LOUVER Right Left 0 1 2 3 4 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW FLOW CONTROL PANEL Vert LOUVER Center m 0 1 2 3 4 1 0 0 5 3 2 1 0 Unit m s m SIDE VIEW FLOW CONTROL PANEL Horiz LOUVER Center...

Страница 15: ...OWER Airflow HIGH 1190 1000 m h 570 l s 158 CFM 335 MED 1000 850 m h 460 l s 128 CFM 271 LOW 820 690 m h 360 l s 100 CFM 212 QUIET 660 560 m h 270 l s 75 CFM 159 Fan speed Number of rotations r p m UPPER LOWER Airflow HIGH 1240 1040 m h 600 l s 167 CFM 353 MED 1040 880 m h 480 l s 133 CFM 282 LOW 840 700 m h 370 l s 103 CFM 218 QUIET 660 560 m h 270 l s 75 CFM 159 ...

Страница 16: ... HIGH 1330 1120 m h 650 l s 181 CFM 383 MED 1100 930 m h 520 l s 144 CFM 306 LOW 890 750 m h 400 l s 111 CFM 235 QUIET 660 560 m h 270 l s 75 CFM 159 Fan speed Number of rotations r p m UPPER LOWER Airflow HIGH 1330 1120 m h 650 l s 181 CFM 383 MED 1100 930 m h 520 l s 144 CFM 306 LOW 860 730 m h 390 l s 108 CFM 230 QUIET 660 560 m h 270 l s 75 CFM 159 ...

Страница 17: ...ter frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 MODEL AG G12LVCA Cooling ...

Страница 18: ...0 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet Heating z z Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 High Quiet ...

Страница 19: ... 01 16 FLOOR TYPE AG G09 14LVCA FLOOR TYPE AG G09 14LVCA SOUND LEVEL CHECK POINT 88888 Microphone Microphone Airflow 1 m Airflow 1 m ...

Страница 20: ...ERISTICS 999 Model Name AGÛG09LVCA AGÛG12LVCA AGÛG14LVCA Power Supply Voltage V 230 Frequency Hz 50 Max Operating Current A 0 7 Wiring Spec Connection Cable mm2 1 5 Limited wiring length m 21 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 ...

Страница 21: ...CA SAFETY DEVICES 1111 Protection form Model AGÛG09LVCA AGÛG12LVCA AGÛG14LVCA Circuit protection Current fuse PC board 250 V 3 15 A Terminal protection Current thermal fuse 250 V 3 A Fan motor protection Terminal protection program OFF 150 15 C ON 120 15 C ...

Страница 22: ...other than initial setting Operation mode Auto changeover Mode at previous operation Set temperature 24 C Temperature at previous operation Airflow mode AUTO Mode at previous operation Up down air direction swing Standard air direction swing OFF Air direction at previous operation Left right air direction swing Standard air direction swing OFF Air direction at previous operation Circuit diagram ex...

Страница 23: ... 01 20 FLOOR TYPE AG G09 14LVCA FLOOR TYPE AG G09 14LVCA Parts Optional z z Parts name Model name External connect kit UTY XWZX ...

Страница 24: ...ple z z Relay spec Max DC 24 V 10 mA to less than 500 mA Field supply Ex Display Indoor unit control PC board Connected unit Ex Relay unit 1 2 Signal Relay power supply V Connector 10 m DC 24 V Make the distance from the PC board to the connected unit within 10 m ON OFF Operation Stop Indoor unit Output signal Parts Optional z z Parts name Model name External connect kit UTY XWZX ...

Страница 25: ...e SET TEMP 111 button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and proceed to STEP 2 Press the TIMER MODE button and check that the indoor unit can receive signals 222 at the displayed signal code Press the MODE button to accept the signal code and procee...

Страница 26: ...or displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room If the indication is not required select No indication 03 Factory setting Setting Description Function Number Setting Value Standard 400 hours 11 00 Long interval 1 000 hours 01 Short interval 200 hours 02 No indication 03 2 Vertical airflow direction range control In a concealed insta...

Страница 27: ...restart is an emergency function such as for power outage etc Do not attempt to use this function in normal operation Be sure to operate the unit by remote controller or other external input device 6 Room temperature sensor switching Only for wired remote controller When using the Wired remote controller temperture sensor change the setting to Both 01 Factory setting Setting Description Function N...

Страница 28: ...rol for energy saving for cooling Enables or disables the power saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation Factory setting Setting Description Function Number Setting Value Disable 49 00 Enable 01 00 When the outdoor unit is stopped the indoor unit fan operates continuously following the setting on the remote controller 01 ...

Страница 29: ... on the display to the air conditioner signal code Press the MODE button again to return to the clock display The signal code will 444 be changed If no buttons are pressed within 30 seconds after the signal code is displayed the system returns to the original clock display In this case start again from step 1 The air conditioner signal code is set to A prior to shipment Contact your retailer to ch...

Страница 30: ...ller UTY RNN M The room temperature can be controlled by detecting the temperature accurately with built in thermo sensor Simple remote controller UTY RSN M Compact remote controller concentrates on the basic functions such as Start Stop Fan Control Temperature Setting and Operation mode Exterior Parts name Model No Summary External connect kit UTY XWZX Use to connect with various peripheral devic...

Страница 31: ...2 OUTDOOR UNIT SINGLE TYPE AO G09LVCA AO G12LVCA AO G14LVLA DTR_AO129E_01 2012 12 04 ...

Страница 32: ...RANT CIRCUIT 02 03 4 WIRING DIAGRAMS 02 04 5 CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE 02 06 6 ADDITIONAL CHARGE CALCULATION 02 08 7 AIRFLOW 02 09 8 OPERATION NOISE SOUND PRESSURE 02 11 8 1 NOISE LEVEL CURVE 02 11 8 2 SOUND LEVEL CHECK POINT 02 13 9 ELECTRIC CHARACTERISTICS 02 14 10 SAFETY DEVICES 02 15 ...

Страница 33: ...Q ty Rotary 1 Motor output W 750 1 100 Refrigerant Type Global Warming Potential R410A 1975 Charge g 1 050 1 150 Refrigerant oil Type ESTER OIL Enclosure Material Steel Colour Beige Dimensions H W D Net mm 540 790 290 578 790 300 Gross 648 910 380 660 935 400 Weight Net kg 36 40 Gross 40 44 Connenction pipe Size Liquid mm Ø6 35 Ø1 4 in Gas Ø9 52 Ø3 8 in Ø12 70 Ø1 2 in Method Flare Pre charge lengt...

Страница 34: ...14LV DIMENSIONS 222 MODEL AO G09LVCA AO G12LVCA Unit mm MODEL AO G14LVLA INSTALLATION PLACE 100 mm or more 600 mm or more 100 mm or more 200 mm or more 250 mm or more 50 mm or more 540 790 56 290 353 17 540 125 347 578 48 10 320 508 540 20 300 125 60 790 ...

Страница 35: ... 35 mm 1 4 Gas 9 52 mm 3 8 09 12LVCA 12 70 mm 1 2 14LVLA 2 Way valve Strainer Strainer 3 Way valve Muffler 4 Way valve Expansion valve Indoor unit Heat exchanger Outdoor unit Heat exchanger Compressor ThD ThR ThPI ThO ThHO Thermistor Discharge Temp Thermistor Outdoor Temp Thermistor Heat Exchanger Out Temp ThD ThO ThHO Thermistor Room Temp Thermistor Pipe Temp ThR ThPI ...

Страница 36: ... 02 04 OUTDOOR UNIT AO G09 14LV OUTDOOR UNIT AO G09 14LV WIRING DIAGRAMS 444 MODEL AO G09LVCA AO G12LVCA ...

Страница 37: ... 02 05 OUTDOOR UNIT AO G09 14LV OUTDOOR UNIT AO G09 14LV MODEL AO G14LVLA ...

Страница 38: ...it 15 0 863 0 846 10 0 944 0 863 0 846 7 5 0 978 0 944 0 863 0 846 5 1 000 0 978 0 944 0 863 0 846 0 1 000 0 978 0 944 0 863 0 846 Û2 Indoor unit is lower than outdoor unit 5 0 995 0 973 0 939 0 858 0 842 7 5 0 971 0 937 0 856 0 840 10 0 934 0 854 0 838 15 0 794 0 778 COOLING Pipe length m 5 7 5 10 15 20 Height difference H m Û1 Indoor unit is higher than outdoor unit 15 0 915 0 905 10 0 955 0 922...

Страница 39: ... 5 0 982 0 943 0 853 0 824 5 1 000 0 982 0 943 0 853 0 824 0 1 000 0 982 0 943 0 853 0 824 Û2 Indoor unit is lower than outdoor unit 5 0 995 0 977 0 938 0 848 0 820 7 5 0 975 0 936 0 846 0 818 10 0 933 0 844 0 816 15 0 785 0 758 COOLING Pipe length m 5 7 5 10 15 20 Height difference H m Û1 Indoor unit is higher than outdoor unit 15 0 950 0 946 10 0 976 0 958 0 954 7 5 0 984 0 980 0 962 0 958 5 0 9...

Страница 40: ... G12LVCA Refrigerant charge z z MODEL AO G14LVLA Refrigerant charge z z Refrigerant type R410A Refrigerant amount g 1 050 Total pipe length m 15 or less 20 MAX 20g m Additional charge g 0 100 Refrigerant type R410A Refrigerant amount g 1 150 Total pipe length m 15 or less 20 MAX 20g m Additional charge g 0 100 ...

Страница 41: ...g z z MODEL AO G12LVCA Cooling z z Heating z z Number of rotations r p m Airflow 760 1 680 m3 h 467 l s 989 CFM Number of rotations r p m Airflow 680 1 490 m3 h 414 l s 877 CFM Number of rotations r p m Airflow 760 1 680 m3 h 467 l s 989 CFM Number of rotations r p m Airflow 760 1 680 m3 h 467 l s 989 CFM ...

Страница 42: ...UNIT AO G09 14LV OUTDOOR UNIT AO G09 14LV MODEL AO G14LVLA Cooling z z Heating z z Number of rotations r p m Airflow 820 1 910 m3 h 531 l s 1 124 CFM Number of rotations r p m Airflow 750 1 750 m3 h 486 l s 1 030 CFM ...

Страница 43: ...ve band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Octave band sou...

Страница 44: ...ncy Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating z z Octave band sound pressure level dB 0dB 0 0002µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 ...

Страница 45: ... 02 13 OUTDOOR UNIT AO G09 14LV OUTDOOR UNIT AO G09 14LV SOUND LEVEL CHECK POINT 88888 ...

Страница 46: ...c Main Fuse Circuit breaker Current A 20 Power Cable mm2 1 5 2 5 3 Limited wiring length m 15 11 1 The maximum current is the total current of indoor unit and outdoor unit 2 Wiring Spec Selected Sample Selected based on Japan Electrotechnical Standard and Codes Committee E0005 3 Limited wiring length This is the wiring length in case voltage descent is less than 2 When the wiring length becomes lo...

Страница 47: ...12LVCA AO G14LVLA Circuit protection Current fuse Near the terminal 250V 20A 250V 5A Current fuse Main printed circuit board 250V 15A 250V 3 15A Fan motor protection Thermal protection program OFF 100 15 10 C ON 95 15 10 C Compressor protection Thermal protection program Discharge temp OFF 110 C ON After 7 minutes ...