Fujitsu ABYA45LCT Скачать руководство пользователя страница 6

En-6

4.3. Flare connection (pipe connection)

4.3.1. Flaring

Use special pipe cutter and flare tool exclusive for R410A.

• 

Cut the connection pipe to the necessary length with a 

(1) 

pipe cutter.

Hold the pipe downward so that cuttings will not enter the 

(2) 

pipe and remove any burrs.

Insert the flare nut (always use the flare nut attached to 

(3) 

the indoor and outdoor units respectively) onto the pipe 

and perform the flare processing with a flare tool. Use the 

special R410A flare tool, or the conventional flare tool. 

Leakage of refrigerant may result if other flare nuts are 

used.

Protect the pipes by pinching them or with tape to prevent 

(4) 

dust, dirt, or water from entering the pipes. 

B

Die

A
Pipe

Check if [L] is flared uniformly

and is not cracked or scratched.

L

Pipe outside  

diameter  

[mm (in.)]

Dimension A [mm]

Dimension B

-

0

0.4 

[mm]

Flare tool for R410A,  

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional flare tools to flare R410A pipes, 

the dimension A should be approximately 0.5 mm more than 

indicated in the table (for flaring with R410A flare tools) to 

achieve the specified flaring. Use a thickness gauge to meas

-

ure the dimension A.

Pipe outside 

diameter [mm (in.)]

Width across flats

 

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

Use pipe with water-resistant heat insulation.

• 

 CAUTION

Install heat insulation around both the gas and liquid 

• 

pipes. Failure to do so may cause water leaks.  

Use heat insulation with heat resistance above 120 °C. 

(Reverse cycle model only)  

In addition, if the humidity level at the installation loca-

tion of the refrigerant piping is expected to exceed 70 %, 

install heat insulation around the refrigerant piping.  

If the expected humidity level is 70-80 %, use heat 

 

insulation that is 15 mm or thicker and if the expected 

humidity exceeds 80 %, use heat insulation that is 20 mm 

or thicker. If heat insulation is used that is not as thick as 

specified, condensation may form on the surface of the 

insulation.  

In addition, use heat insulation with heat conductivity of 

0.045 W/(m·K) or less (at 20 °C).

4. PIPE INSTALLATION

 CAUTION

Be more careful that foreign matter (oil, water, etc.) does 

• 

not enter the piping than with refrigerant R410A models. 

Also, when storing the piping, securely seal the openings 

by pinching, taping, etc.
While welding the pipes, be sure to blow dry nitrogen gas 

• 

through them.

4.1. Selecting the pipe material

 CAUTION

Do not use existing pipes.

• 

Use pipes that have clean external and internal sides 

• 

without any contamination which may cause trouble dur-

ing use, such as sulfur, oxide, dust, cutting waste, oil, or 

water.
It is necessary to use seamless copper pipes. 

• 

Material : Phosphor deoxidized seamless copper pipes

 

It is desirable that the amount of residual oil is less than  

40 mg/10 m.
Do not use copper pipes that have a collapsed, de-

• 

formed, or discolored portion (especially on the interior 

surface). Otherwise, the expansion valve or capillary tube 

may become blocked with contaminants.
Improper pipe selection will degrade performance. As an 

• 

air conditioner using R410A incurs pressure higher than 

when using conventional refrigerant, it is necessary to 

choose adequate materials.

Thicknesses of copper pipes used with R410A are as shown 

• 

in the table.

Never use copper pipes thinner than those indicated in the 

• 

table even if they are available on the market.

Thicknesses of Annealed Copper Pipes (R410A)

Pipe outside diameter [mm (in.)]

Thickness [mm]

6.35 (1/4)

0.80

9.52 (3/8)

0.80

12.70 (1/2)

0.80

15.88 (5/8)

1.00

19.05 (3/4)

1.20

4.2. Pipe requirement

 CAUTION

Refer to the Installation Manual of the outdoor unit for 

• 

description of the length of connecting pipe or for differ-

ence of its elevation.

Diameter [mm (in.)]

Liquid

9.52 (3/8)

Gas

15.88 (5/8)

Width across

1125-9379122009.indd   6

2008/11/26   7:57:05

www.enindel.com

Содержание ABYA45LCT

Страница 1: ...ulation 5 INSTALLING DRAIN PIPES 8 6 ELECTRICAL WIRING 9 6 1 Electrical requirement 6 2 Wiring method AIR CONDITIONER INDOOR UNIT Ceiling type PART NO 9379122009 02 7 REMOTE CONTROLLER SETTING 11 7 1 Load batteries R03 LR03 2 7 2 Remote control unit holder installation 8 FUNCTION SETTING 11 8 1 Entering the function setting mode 8 2 Function setting 9 SELECTING THE REMOTE CONTROL UNIT SIGNAL CODE ...

Страница 2: ...ill become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refriger ant pipe connections or other area Touching the refriger ant directly can cause frostbit...

Страница 3: ...bustible gas leakage Do not install the unit near a source of heat steam or flammable gas Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise und...

Страница 4: ...n for Suspension bolt Ceiling Wall Template Drilling position for piping 3 3 3 Location of ceiling suspension bolts 30 Suspension bolt pitch 1600 Dimensions Space Required for Installation 30 10 155 300 INDOOR UNIT TOP VIEW INDOOR UNIT Suspension bolt should extend outward 30 to 75 mm Unit mm Install the indoor unit on a place having a sufficient 1 strength so that it withstands against the weight...

Страница 5: ... nut to each bolt The two special nuts are provided with the unit The M10 nut must be obtained locally Refer to the figure Bolt Strength N kgf 980 to 1470 100 to 150 Ceiling panel Special nut A Included Special nut B Included M10 Nut Obtained locally 10 to 15 Unit mm 3 3 6 Installing the indoor unit Lift unit so that suspension bolts pass through the suspen 1 sion fittings at the sides four places...

Страница 6: ... that is 15 mm or thicker and if the expected humidity exceeds 80 use heat insulation that is 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 20 C 4 PIPE INSTALLATION CAUTION Be more careful that foreign matter oil water etc does not ...

Страница 7: ...ipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than three times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection CAUTION Be sure to apply the pipe against the port on the indoor unit and the outdoor ...

Страница 8: ...correctly within the indoor unit Indoor unit rear view VT wire Drain hose If the drain hose will not be connected to the right rear 3 piping cut the hole cover at the points indicated in Fig a and attach it to the piping hole as shown in Fig b a Cut x 5 Hole cover b 4 4 Installing heat insulation CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this...

Страница 9: ...l box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Install a ground leakage breaker In addition install the ground leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result In...

Страница 10: ...Do not attempt to recharge dry batteries Use the specified wires connect them securely and fasten 3 them so that there is no stress placed on the terminals Use an appropriate screwdriver to tighten the terminal 4 screws Do not use a screwdriver that is too small other wise the screw heads may be damaged and prevent the screws from being properly tightened Do not tighten the terminal screws too muc...

Страница 11: ...control unit are replaced If you use a signal code other than signal code A reset the signal code after replacing the batteries If you do not know the air conditioner signal code setting try each of the signal codes until you find the code which operates the air conditioner NOTE Never mix new and used batteries or batteries of different types Batteries should last about one year under normal use I...

Страница 12: ...FUNCTION SETTING be sure to turn off the power and turn it on again 8 2 Function setting STEP 2 Selecting the Function Number and Setting Value Press the SET TEMP 1 buttons to select the func tion number Press the MODE button to switch between the left and right digits Press the FAN button to proceed to setting the value 2 Press the FAN button again to return to the function number selection Press...

Страница 13: ...ode of the remote control unit to operate only the air conditioner you wish to set four selections possible When two or more air conditioners are installed in a room please contact your retailer to set the individual air conditioner signal codes Confirm the setting of the remote control unit signal code and the printed circuit board setting If these are not confirmed the remote control unit cannot...

Страница 14: ...roller abnormal 2 times 2 times Indoor room temperature sensor error 2 times 3 times Indoor heat exchanger tempera ture sensor middle error 2 times 4 times Indoor heat exchanger tempera ture sensor inlet error 2 times 6 times Float switch operated 3 times 2 times Outdoor discharge pipe tempera ture sensor error 3 times 3 times Outdoor heat exchanger temperature sensor outlet error 3 times 4 times ...

Страница 15: ...t circuit address set up error 31 Master unit Slave unit set up error 32 Connected the indoor number set up error 33 P F C printed circuit board error If C0 appears in the unit number display there is a remote controller error Unit number Error code Content C0 1d Incompatible indoor unit is connected C0 1c Indoor unit remote control ler communication error 13 SPECIAL INSTALLATION METHODS CAUTION W...

Страница 16: ...ndoor unit with the unit number 0 last Within 1 minute 2 When the indoor units are turned on error codes 01 and 31 will be displayed however these error codes will be deleted by setting the remote controller Therefore continue with the setting procedure Set the refrigerant circuit address Assign the same 2 number to all of the indoor units connected to an outdoor unit Refrigerant circuit address F...

Отзывы: