background image

En-16

15. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the 

operating manual:

Starting and stopping method, operation switching, tem-

(1) 

perature adjustment, timer, air flow switching, and other 

remote control unit operations.

Air filter removal and cleaning, and how to use the air 

(2) 

louvers.

Give the operating and Installation Manuals to the cus-

(3) 

tomer.

If the signal code is changed, explain to the customer how 

(4) 

it changed (the system returns to signal code A when the 

batteries in the remote control unit are replaced). 

*(4) is applicable to using wireless remote control.

14. FRESH-AIR INTAKE

Open up the knockout hole for the fresh-air intake, as 

(1) 

shown in the figure. (If using half-concealed installation, 

open up the top knockout hole instead.) 

For half concealed

installation 

Indoor unit

 CAUTION

When removing the cabinet (iron plate), be careful not 

• 

to damage the indoor unit internal parts and surrounding 

area (outer case).
When processing the cabinet (iron plate), be careful not 

• 

to injure yourself with burrs, etc.

Fasten the round flange (optional) to the fresh-air intake, 

(2) 

as shown in the figure. (If using half-concealed installation, 

attach to the top.) 

Round duct (option parts)  

[After completing “3. INSTALLATION WORK”...]

Connect the duct to the round flange.

(3) 

Seal with a band and vinyl tape, etc. so that air does not 

(4) 

leak from the connection.

Duct

Remote controller setting

(3) 

Turn on all of the indoor units.

1. 

*

Turn on the indoor unit with the unit number 0 last.

(Within 1 minute)

*

2

 When the indoor units are turned on, error codes 

01 and 31 will be displayed; however, these error 

codes will be deleted by setting the remote controller. 

Therefore, continue with the setting procedure.

Set the refrigerant circuit address. (Assign the same 

2. 

number to all of the indoor units connected to an 

outdoor unit.)

Refrigerant circuit  

address

Function Number

Setting Value

02

00~15

Set the “master” and “slave” settings. (Set the indoor 

3. 

unit that is connected to the outdoor unit using a trans-

mission cable as the “master”.)

Function Number

Setting Value

Master

51

00

Slave

01

After completing the function settings, turn off all of the 

4. 

indoor units, and then turn them back on.

If error code 01, 1F, 30, 31, or 32 is displayed, there 

may be an incorrect setting. Perform the remote 

controller setting again.

NOTE

When different indoor unit models are connected using the 

group control system, some functions may no longer be avail-

able.

If the group control system contains multiple units that are 

operated simultaneously, connect and set the units as shown 

below.

Simultaneous

triple

Simultaneous

twin

Standard

pair

Remote

controller

Indoor

unit

Outdoor

unit

Indoor

unit

Indoor

unit

Outdoor

unit

Indoor

unit

Indoor

unit

Indoor

unit

Outdoor

unit

: Transmission cable, Power supply cable
: Remote controller cable

: Bus wire

: Power supply cable

0

1

2

3

4

5

00

01

01

02

02

02

00

00

01

00

01

01

DIP switch setting

(Indoor unit)
Remote controller

setting

adress

Master/Slave

*Make sure that the indoor unit with the unit number 0 is con-

nected to the outdoor unit using a transmission cable.

1125-9379122009.indd   16

2008/11/26   7:57:06

www.enindel.com

Содержание ABYA45LCT

Страница 1: ...ulation 5 INSTALLING DRAIN PIPES 8 6 ELECTRICAL WIRING 9 6 1 Electrical requirement 6 2 Wiring method AIR CONDITIONER INDOOR UNIT Ceiling type PART NO 9379122009 02 7 REMOTE CONTROLLER SETTING 11 7 1 Load batteries R03 LR03 2 7 2 Remote control unit holder installation 8 FUNCTION SETTING 11 8 1 Entering the function setting mode 8 2 Function setting 9 SELECTING THE REMOTE CONTROL UNIT SIGNAL CODE ...

Страница 2: ...ill become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refriger ant pipe connections or other area Touching the refriger ant directly can cause frostbit...

Страница 3: ...bustible gas leakage Do not install the unit near a source of heat steam or flammable gas Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise und...

Страница 4: ...n for Suspension bolt Ceiling Wall Template Drilling position for piping 3 3 3 Location of ceiling suspension bolts 30 Suspension bolt pitch 1600 Dimensions Space Required for Installation 30 10 155 300 INDOOR UNIT TOP VIEW INDOOR UNIT Suspension bolt should extend outward 30 to 75 mm Unit mm Install the indoor unit on a place having a sufficient 1 strength so that it withstands against the weight...

Страница 5: ... nut to each bolt The two special nuts are provided with the unit The M10 nut must be obtained locally Refer to the figure Bolt Strength N kgf 980 to 1470 100 to 150 Ceiling panel Special nut A Included Special nut B Included M10 Nut Obtained locally 10 to 15 Unit mm 3 3 6 Installing the indoor unit Lift unit so that suspension bolts pass through the suspen 1 sion fittings at the sides four places...

Страница 6: ... that is 15 mm or thicker and if the expected humidity exceeds 80 use heat insulation that is 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 20 C 4 PIPE INSTALLATION CAUTION Be more careful that foreign matter oil water etc does not ...

Страница 7: ...ipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than three times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection CAUTION Be sure to apply the pipe against the port on the indoor unit and the outdoor ...

Страница 8: ...correctly within the indoor unit Indoor unit rear view VT wire Drain hose If the drain hose will not be connected to the right rear 3 piping cut the hole cover at the points indicated in Fig a and attach it to the piping hole as shown in Fig b a Cut x 5 Hole cover b 4 4 Installing heat insulation CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this...

Страница 9: ...l box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Install a ground leakage breaker In addition install the ground leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result In...

Страница 10: ...Do not attempt to recharge dry batteries Use the specified wires connect them securely and fasten 3 them so that there is no stress placed on the terminals Use an appropriate screwdriver to tighten the terminal 4 screws Do not use a screwdriver that is too small other wise the screw heads may be damaged and prevent the screws from being properly tightened Do not tighten the terminal screws too muc...

Страница 11: ...control unit are replaced If you use a signal code other than signal code A reset the signal code after replacing the batteries If you do not know the air conditioner signal code setting try each of the signal codes until you find the code which operates the air conditioner NOTE Never mix new and used batteries or batteries of different types Batteries should last about one year under normal use I...

Страница 12: ...FUNCTION SETTING be sure to turn off the power and turn it on again 8 2 Function setting STEP 2 Selecting the Function Number and Setting Value Press the SET TEMP 1 buttons to select the func tion number Press the MODE button to switch between the left and right digits Press the FAN button to proceed to setting the value 2 Press the FAN button again to return to the function number selection Press...

Страница 13: ...ode of the remote control unit to operate only the air conditioner you wish to set four selections possible When two or more air conditioners are installed in a room please contact your retailer to set the individual air conditioner signal codes Confirm the setting of the remote control unit signal code and the printed circuit board setting If these are not confirmed the remote control unit cannot...

Страница 14: ...roller abnormal 2 times 2 times Indoor room temperature sensor error 2 times 3 times Indoor heat exchanger tempera ture sensor middle error 2 times 4 times Indoor heat exchanger tempera ture sensor inlet error 2 times 6 times Float switch operated 3 times 2 times Outdoor discharge pipe tempera ture sensor error 3 times 3 times Outdoor heat exchanger temperature sensor outlet error 3 times 4 times ...

Страница 15: ...t circuit address set up error 31 Master unit Slave unit set up error 32 Connected the indoor number set up error 33 P F C printed circuit board error If C0 appears in the unit number display there is a remote controller error Unit number Error code Content C0 1d Incompatible indoor unit is connected C0 1c Indoor unit remote control ler communication error 13 SPECIAL INSTALLATION METHODS CAUTION W...

Страница 16: ...ndoor unit with the unit number 0 last Within 1 minute 2 When the indoor units are turned on error codes 01 and 31 will be displayed however these error codes will be deleted by setting the remote controller Therefore continue with the setting procedure Set the refrigerant circuit address Assign the same 2 number to all of the indoor units connected to an outdoor unit Refrigerant circuit address F...

Отзывы: