3.3. Installation the unit

 WARNING

Install the air conditioner in a location which can with-

• 

stand a load of at least five times the weight of the main 

unit and which will not amplify sound or vibration. If the 

installation location is not strong enough, the indoor unit 

may fall and cause injuries.

3.3.1. Preparing indoor unit installation

Remove the intake grille and side cover

Remove the two Air filters.

(1) 

Remove the two Intake grilles. 

(2) 

For 

4

 Left rear drain and 

5

 Left drain: Remove air filters 

and intake grilles at three places. 

Remove the Side cover A (Right side) and Side cover B 

(3) 

(Right and Left side). 

For 

5

 Left drain: Remove both the Side cover A (Right 

and Left side). 

This air conditioner can be set up to intake fresh air.  

(4) 

For information about how to install for fresh-air intake, 

refer to “14. FRESH-AIR INTAKE”.

Air filter

Intake grille

Tapping screw

INDOOR UNIT

Side cover A (Right side)

Side cover B

(Left side)

Side cover B (Right side)

3.3.2. Indoor unit installation

You can use the accessory template to help you install the 

• 

indoor unit.

The template helps you determine the appropriate locations 

• 

for suspension bolts and pipe opening (drain pipe and con-

nection cable).

Drilling position for Suspension bolt

Ceiling

Wall

Template

Drilling position for piping

3.3.3. Location of ceiling suspension bolts

30

Suspension bolt pitch 1600

Dimensions

(Space Required

for Installation)

30

10

155

300

INDOOR UNIT (TOP VIEW)

INDOOR UNIT

Suspension bolt should

extend outward 30 to 75 mm.

Unit : mm

Install the indoor unit on a place having a sufficient 

(1) 

strength so that it withstands against the weight of the 

indoor unit.

The inlet and outlet ports should not be obstructed; the air 

(2) 

should be able to blow all over the room.

Leave the space required to service the air conditioner.

(3) 

Install the unit where connection to the outdoor unit is 

(4) 

easy. 

Install the unit where the connection pipe can be easily 

(5) 

installed. 

Install the unit where the drain pipe can be easily installed.

(6) 

Install the unit where noise and vibrations are not ampli-

(7) 

fied. 

Take servicing, etc., into consideration and leave the spac-

(8) 

es. Also install the unit where the filter can be removed.

Do not install the unit where it will be exposed to direct 

(9) 

sunlight.

3.2. Installation dimension

The ceiling rear height as shown in the figure.

 

• 

Ceiling

INDOOR UNIT

Ceiling

Obstruction

Floor

10 or over

80 or over

150 or over

1000 or over

2500 or ove

r

Unit : mm

[FOR HALF CONCEALED INSTALLATION]

Ceiling panel

Ceiling panel

INDOOR UNIT

 

 

Floor

10 or over 

Obstruction

 

150 or over 

80 or over 

1000 or over

 

2500 or over 

Unit : mm

1125-9379122009.indd   4

2008/11/26   7:57:04

www.enindel.com

Содержание ABYA45LCT

Страница 1: ...ulation 5 INSTALLING DRAIN PIPES 8 6 ELECTRICAL WIRING 9 6 1 Electrical requirement 6 2 Wiring method AIR CONDITIONER INDOOR UNIT Ceiling type PART NO 9379122009 02 7 REMOTE CONTROLLER SETTING 11 7 1 Load batteries R03 LR03 2 7 2 Remote control unit holder installation 8 FUNCTION SETTING 11 8 1 Entering the function setting mode 8 2 Function setting 9 SELECTING THE REMOTE CONTROL UNIT SIGNAL CODE ...

Страница 2: ...ill become abnormally high and cause the piping to rupture If there is a refrigerant leak make sure that it does not exceed the concentration limit If a refrigerant leak exceeds the concentration limit it can lead to accidents such as oxygen starvation Do not touch refrigerant that has leaked from the refriger ant pipe connections or other area Touching the refriger ant directly can cause frostbit...

Страница 3: ...bustible gas leakage Do not install the unit near a source of heat steam or flammable gas Install the indoor unit outdoor unit power supply cable transmission cable and remote control cable at least 1 m away from a television or radio receivers The purpose of this is to prevent TV reception interference or radio noise Even if they are installed more than 1 m apart you could still receive noise und...

Страница 4: ...n for Suspension bolt Ceiling Wall Template Drilling position for piping 3 3 3 Location of ceiling suspension bolts 30 Suspension bolt pitch 1600 Dimensions Space Required for Installation 30 10 155 300 INDOOR UNIT TOP VIEW INDOOR UNIT Suspension bolt should extend outward 30 to 75 mm Unit mm Install the indoor unit on a place having a sufficient 1 strength so that it withstands against the weight...

Страница 5: ... nut to each bolt The two special nuts are provided with the unit The M10 nut must be obtained locally Refer to the figure Bolt Strength N kgf 980 to 1470 100 to 150 Ceiling panel Special nut A Included Special nut B Included M10 Nut Obtained locally 10 to 15 Unit mm 3 3 6 Installing the indoor unit Lift unit so that suspension bolts pass through the suspen 1 sion fittings at the sides four places...

Страница 6: ... that is 15 mm or thicker and if the expected humidity exceeds 80 use heat insulation that is 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the insulation In addition use heat insulation with heat conductivity of 0 045 W m K or less at 20 C 4 PIPE INSTALLATION CAUTION Be more careful that foreign matter oil water etc does not ...

Страница 7: ...ipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than three times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection CAUTION Be sure to apply the pipe against the port on the indoor unit and the outdoor ...

Страница 8: ...correctly within the indoor unit Indoor unit rear view VT wire Drain hose If the drain hose will not be connected to the right rear 3 piping cut the hole cover at the points indicated in Fig a and attach it to the piping hole as shown in Fig b a Cut x 5 Hole cover b 4 4 Installing heat insulation CAUTION After checking for gas leaks refer to the Installation Manual of the outdoor unit perform this...

Страница 9: ...l box cover can cause serious accidents such as electric shock or fire through exposure to dust or water Install sleeves into any holes made in the walls for wiring Otherwise a short circuit could result Install a ground leakage breaker In addition install the ground leakage breaker so that the entire AC main power supply is cut off at the same time Otherwise electric shock or fire could result In...

Страница 10: ...Do not attempt to recharge dry batteries Use the specified wires connect them securely and fasten 3 them so that there is no stress placed on the terminals Use an appropriate screwdriver to tighten the terminal 4 screws Do not use a screwdriver that is too small other wise the screw heads may be damaged and prevent the screws from being properly tightened Do not tighten the terminal screws too muc...

Страница 11: ...control unit are replaced If you use a signal code other than signal code A reset the signal code after replacing the batteries If you do not know the air conditioner signal code setting try each of the signal codes until you find the code which operates the air conditioner NOTE Never mix new and used batteries or batteries of different types Batteries should last about one year under normal use I...

Страница 12: ...FUNCTION SETTING be sure to turn off the power and turn it on again 8 2 Function setting STEP 2 Selecting the Function Number and Setting Value Press the SET TEMP 1 buttons to select the func tion number Press the MODE button to switch between the left and right digits Press the FAN button to proceed to setting the value 2 Press the FAN button again to return to the function number selection Press...

Страница 13: ...ode of the remote control unit to operate only the air conditioner you wish to set four selections possible When two or more air conditioners are installed in a room please contact your retailer to set the individual air conditioner signal codes Confirm the setting of the remote control unit signal code and the printed circuit board setting If these are not confirmed the remote control unit cannot...

Страница 14: ...roller abnormal 2 times 2 times Indoor room temperature sensor error 2 times 3 times Indoor heat exchanger tempera ture sensor middle error 2 times 4 times Indoor heat exchanger tempera ture sensor inlet error 2 times 6 times Float switch operated 3 times 2 times Outdoor discharge pipe tempera ture sensor error 3 times 3 times Outdoor heat exchanger temperature sensor outlet error 3 times 4 times ...

Страница 15: ...t circuit address set up error 31 Master unit Slave unit set up error 32 Connected the indoor number set up error 33 P F C printed circuit board error If C0 appears in the unit number display there is a remote controller error Unit number Error code Content C0 1d Incompatible indoor unit is connected C0 1c Indoor unit remote control ler communication error 13 SPECIAL INSTALLATION METHODS CAUTION W...

Страница 16: ...ndoor unit with the unit number 0 last Within 1 minute 2 When the indoor units are turned on error codes 01 and 31 will be displayed however these error codes will be deleted by setting the remote controller Therefore continue with the setting procedure Set the refrigerant circuit address Assign the same 2 number to all of the indoor units connected to an outdoor unit Refrigerant circuit address F...

Отзывы: