![Fujitsu ABYA12-24LBTH Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/fujitsu/abya12-24lbth/abya12-24lbth_installation-manual_118056015.webp)
En-15
* The last command has priority.
* The indoor units within the same remote controller group
operates in the same mode.
• When function setting is “Emergency stop” mode
In the case of “Edge” input
Connector
Input signal
Command
Ch1 of
CN6 or CN17
OFF
→
ON
Emergency stop
ON
→
OFF
Normal
In the case of “Pulse” input
Connector
Input signal
Command
CN6 or CN17
Ch1
OFF
→
ON
Emergency
stop
Ch2
OFF
→
ON
Normal
* All indoor units of same refrigerant system stops when
Emergency stop operates.
• When function setting is “Forced stop” mode
In the case of “Edge” input
Connector
Input signal
Command
Ch1 of
CN6 or CN17
OFF
→
ON
Forced stop
ON
→
OFF
Normal
In the case of “Pulse” input
Connector
Input signal
Command
CN6 or CN17
Ch1
OFF
→
ON
Forced stop
Ch2
OFF
→
ON
Normal
* When the forced stop is triggered, indoor unit stops and
Start/Stop operation by a remote controller is restricted.
* When forced stop function is used with forming a
remote controller group, connect the same equipment
to each indoor unit within the group.
• Selection method of functions
“Start/Stop” mode or “Emergency stop” mode, “Forced stop”
mode can be selected with function setting of indoor unit.
(2) External output terminals
• When picking up output signals for operating status,
abnormal conditions or indoor unit status.
Wiring methods and speci
fi
cations
1
2
3
4
P.C.B
CN16
*4
+
+
-
-
-
-
DC power supply
12 - 24V *2
Connected load
*3
connected unit
Connected load
*3
Connected load
*3
*2 Provide a DC12 to 24V power supply. Select a power
supply capacity with an ample surplus for the connected
load.
*3 The allowable current is 30mA or less. Provide a load
resistance such that the current becomes 30mA or less.
*4 Polarity is [+] for pin 1 and [-] for pins 2-4. Connect correctly.
Do not impress a voltage exceeding 24V across pins 1-2, 1-3,
and 1-4.
Operation behavior
Connector
Output voltage
Status
CN16
External
output1
Pins 1-2
0V
Stop
DC 12-24 V *2
Operation
External
output2
Pins 1-3
0V
Normal
DC 12-24 V *2
Error
External
output3
Pins 1-4
0V
Indoor unit fan stop
DC 12-24 V *2
Indoor unit fan
operation
A twisted pair cable (22AWG) should be used. Maximum
length of cable is 150 m.
* Use an external input and output cable with appropriate
external dimension, depending on the number of cables to
be installed.
9367701070-05_IM_EN.indd 15
9367701070-05_IM_EN.indd 15
2011-9-16 8:45:10
2011-9-16 8:45:10