SAFETY DEVICES

10. 

Protection form

Model

AO G30LETL

AO G36LETL

Circuit protection

Current fuse (Near the terminal)

250V 25A 

Current fuse (Filter printed circuit board)

250V 10A 

Current fuse (Main printed circuit board)

 250V 3.15A

Fan motor protection

Thermal protection program

OFF : 140±20°C

ON : 110±20°C

High pressure protection

Pressure switch

OFF : 4.2±0.1MPa

ON : 3.2±0.15MPa

Compressor protection

Thermal protection program (Compressor temp.)

OFF : 120°C

ON : 80°C

Thermal protection program (Discharge temp.)

OFF : 110°C

ON : After 7 minutes

Содержание AB G30LRTE Series

Страница 1: ...DESIGN TECHNICAL MANUAL INDOOR OUTDOOR AO G30LETL AO G36LETL AB G30LRTE AB G36LRTE AIR CONDITIONER Ceiling type ...

Страница 2: ...1 INDOOR UNIT CEILING TYPE AB G30LRTE AB G36LRTE DTR_AB037E_01 2013 02 28 ...

Страница 3: ...E 01 12 7 1 AIR VELOCITY DISTRIBUTION 01 12 7 2 AIRFLOW 01 14 7 3 FRESH AIR CHARACTERISTIC 01 16 8 OPERATION NOISE 01 17 8 1 NOISE LEVEL CURVE 01 17 8 2 SOUND LEVEL CHECK POINT 01 18 9 ELECTRIC CHARACTERISTICS 01 19 10 SAFETY DEVICES 01 20 11 EXTERNAL INPUT OUTPUT 01 21 11 1 EXTERNAL INPUT 01 21 11 2 EXTERNAL OUTPUT 01 22 12 FUNCTION SETTINGS 01 24 12 1 INDOOR UNIT 01 24 12 2 INDOOR UNIT Setting b...

Страница 4: ... simultaneous use possible Wired remote controller and wireless remote controller can be simultaneously used Flexible installation A high installation of the construction of the ceiling and degree of freedom corresponding to height is possible Double auto swing Combination of up down and right left air direction swing allows three dimensional air direction control Since up down air direction flaps...

Страница 5: ...d Operates at normal air flow Mode 1 Air flow becomes greater than normal Auto restart The units restart automatically when the current was returned even when there was a power interruption during operation Room temperature sensor switching Switches from room temperature judgment by room temperature sensor attached to indoor unit body to room temperature judgment by room temperature sensor attache...

Страница 6: ... automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping Switching remote controller signal code A B C D A B C D Mixed up I U I U I U I U I U I U I U I U After code change Code selector switch eliminates unit being wrongly switched Up to 4 codes can be set I U Indoor unit 60min 1 C 2 C Timer setting Cooling ope...

Страница 7: ...6 Selects the fan speed AUTO HIGH MED LOW QUIET START STOP button 7 Pressed to start and stop operation SET button Vertical 8 Air flow direction vertical set button SET button Horizontal 9 Air flow direction horizontal set button SWING button 10 Air flow direction swing button TIMER MODE button 11 Pressed to select the timer mode OFF TIMER ON TIMER PROGRAM TIMER TIMER RESET TIMER SET 12 button Set...

Страница 8: ...00 43300 Input power Cooling Rated kW 2 65 2 93 Max 3 88 4 22 Heating Rated 2 77 3 02 Max 3 88 4 56 Current Cooling Rated A 11 6 12 8 Heating Rated 12 2 13 2 EER Cooling kW kW 3 21 3 21 COP Heating 3 61 3 71 Moisture removal l h pints h 2 5 5 3 3 0 6 3 Maximum operating current Cooling Max A 17 0 18 5 Heating 17 0 20 0 Fan Airflow rate Cooling High m3 h 1660 1900 Med 1500 Low 1200 Quiet 1000 Heati...

Страница 9: ...TE Energy efficiency class Cooling A A Heating Average A A Pdesign Cooling kW 8 5 9 4 Heating Average 8 0 8 7 SEER Cooling kWh kWh 6 10 6 00 SCOP Heating Average 4 20 4 10 Annual energy consumption QCE kWh a 487 548 QHE Average 2662 2965 Sound power level Cooling High dB A 57 60 Heating 60 61 ...

Страница 10: ...ection Liquid 3 Drain piping connection 4 Knock out hole for fresh air 5 Knock out hole for refrigerant piping 6 Hole for lifting bolt Use M10 screw bolt Top view Side view Rear view 1 2 3 4 5 6 30 30 Suspension bolt pitch 1 600 INDOOR UNIT Top view Dimensions Space Required for Installation 10 155 300 INDOOR UNIT Suspension bolt should extend outward 30 to 75 141 Ø200 114 373 Ø200 ...

Страница 11: ...36LRTE INSTALLATION PLACE Unit mm Ceiling 150 or more 80 or more 10 or more 2300 or more 1000 or more INDOOR UNIT Ceiling Obstruction Floor INDOOR UNIT Ceiling pane Ceiling panel 150 or more 80 or more 10 or more 2300 or more 1000 or more Obstruction Floor ...

Страница 12: ... 01 09 CEILING TYPE AB G30 36LRTE CEILING TYPE AB G30 36LRTE WIRING DIAGRAMS 5 MODEL AB G30LRTE AB G36LRTE ...

Страница 13: ... 52 11 20 7 93 3 55 40 6 03 5 20 2 98 6 72 5 23 3 03 6 95 5 68 3 04 7 41 5 70 3 07 7 63 6 16 3 09 8 09 6 13 3 12 8 55 6 53 3 15 46 5 39 5 10 2 92 6 01 5 13 2 97 6 21 5 58 2 99 6 62 5 59 3 02 6 82 6 04 3 03 7 23 6 02 3 06 7 64 6 41 3 09 AFR 31 7 Indoor temperature CDB 18 21 23 25 27 29 32 CWB 12 15 16 18 19 21 23 Outdoor temperature CDB TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC SHC IP TC...

Страница 14: ...54 3 40 11 25 3 47 10 97 3 54 15 10 10 86 2 56 10 60 2 61 10 34 2 67 10 08 2 72 9 82 2 76 20 15 10 85 2 26 10 59 2 30 10 33 2 35 10 07 2 40 9 81 2 43 24 18 11 31 2 27 11 04 2 31 10 77 2 36 10 50 2 41 10 23 2 45 AFR 31 7 Indoor temperature CDB 16 18 20 22 24 Outdoor temperature CDB CWB TC IP TC IP TC IP TC IP TC IP 15 16 9 17 3 97 8 95 4 05 8 73 4 13 8 51 4 22 8 29 4 30 10 11 9 88 4 02 9 65 4 10 9 ...

Страница 15: ... RIGHT AND LEFT 2 1 0 5 0 25 2 3 1 m Unit m s SIDE VIEW FLAP UPWARD HORIZONTAL CENTER 2 1 0 5 0 25 2 3 1 0 m Unit m s SIDE VIEW FLAP CENTER HORIZONTAL CENTER 2 1 0 5 0 25 2 3 1 0 m Unit m s SIDE VIEW FLAP DOWNWARD HORIZONTAL CENTER Note Condition Fan speed High Operation mode FAN 0 1 18 m 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 0 1 m 2 3 4 5 6 7 8 9 10 11 12 13 14 0 1 m 2 3 4 5 6 7 8 9 10 11 12 13...

Страница 16: ...0 25 2 3 1 m Unit m s SIDE VIEW FLAP UPWARD HORIZONTAL CENTER 2 1 0 5 0 25 2 3 1 0 m Unit m s SIDE VIEW FLAP CENTER HORIZONTAL CENTER 2 1 0 5 0 25 2 3 1 0 m Unit m s SIDE VIEW FLAP DOWNWARD HORIZONTAL CENTER Note Condition Fan speed High Operation mode FAN 0 1 18 m 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 0 1 m 2 3 4 5 6 7 8 9 10 11 12 13 14 0 1 m 2 3 4 5 6 7 8 9 10 11 12 13 14 0 1 18 m 2 3 4 5 6 7...

Страница 17: ...r p m Airflow HIGH 1000 m3 h 1660 l s 461 CFM 977 MED 910 m3 h 1500 l s 417 CFM 883 LOW 750 m3 h 1200 l s 333 CFM 706 QUIET 650 m3 h 1000 l s 278 CFM 589 Fan speed Number of rotations r p m Airflow HIGH 1000 m3 h 1660 l s 461 CFM 977 MED 910 m3 h 1500 l s 417 CFM 883 LOW 750 m3 h 1200 l s 333 CFM 706 QUIET 650 m3 h 1000 l s 278 CFM 589 ...

Страница 18: ...irflow HIGH 1100 m3 h 1900 l s 528 CFM 1118 MED 910 m3 h 1500 l s 417 CFM 883 LOW 750 m3 h 1200 l s 333 CFM 706 QUIET 650 m3 h 1000 l s 278 CFM 589 Fan speed Number of rotations r p m Airflow HIGH 1100 m3 h 1900 l s 528 CFM 1118 MED 910 m3 h 1500 l s 417 CFM 883 LOW 750 m3 h 1200 l s 333 CFM 706 QUIET 650 m3 h 1000 l s 278 CFM 589 ...

Страница 19: ...EILING TYPE AB G30 36LRTE CEILING TYPE AB G30 36LRTE FRESH AIR CHARACTERISTIC 7 3 MODEL AB G30LRTE AB G36LRTE 36 30 0 1 2 3 4 5 6 7 mmAq 0 2 4 6 8 Pa 98 0 49 Fresh air flow m3 min Intake duct static pressure 10 ...

Страница 20: ...2μbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Cooling Octave band sound pressure level dB 0dB 0 0002μbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 1...

Страница 21: ... 01 18 CEILING TYPE AB G30 36LRTE CEILING TYPE AB G30 36LRTE SOUND LEVEL CHECK POINT 8 2 Microphone Microphone 1m 1m ...

Страница 22: ...9 Model name AB G30LRTE AB G36LRTE Power supply Voltage V 230 Frequency Hz 50 Max operating current Indoor unit A 0 7 1 Wiring spec Connection cable mm2 1 5 2 5 Limited wiring length m 51 1 Wiring spec Selected Sample Selected based on Japan Electrotechnical Standards and Committee E0005 ...

Страница 23: ...AB G30 36LRTE CEILING TYPE AB G30 36LRTE SAFETY DEVICES 10 Protection form Model AB G30LRTE AB G36LRTE Circuit protection Current fuse PCB 250V 3 15A Fan motor protection Thermal protection program 135 15 C OFF 115 15 C ON ...

Страница 24: ...ion mode Auto changeover Mode at previous operation Set temperature 24 C Temperature at previous operation Air flow mode AUTO Mode at previous operation Up down air direction swing Standard air direction swing OFF Air direction at previous operation Left right air direction swing Standard air direction swing OFF Air direction at previous operation Circuit diagram example Indoor unit control PC boa...

Страница 25: ...uit diagram example Field supply Ex Display Indoor control PC board Connected unit Ex Relay unit 1 2 Signal Relay power supply V Connector Make the distance from the PC board to the connected unit within 10m Relay spec Max 24VDC 10mA to less than 500mA 10 m 24V DC Indoor unit Output signal ON OFF Operation Stop Parts Optional Model name UTY XWZX Wire External output ...

Страница 26: ... prevention control operation Circuit diagram example Field supply Indoor control PC board Connector 1 12 V on off 2 Signal Relay power supply Make the distance from the PC board to the connected unit within 10m Relay spec Rated 12VDC 50mA or less Ex Fan Connected unit Ex Relay unit 10 m ON OFF Operation Stop Indoor fan Output signal Parts Optional Model name UTD ECS5A Wire Fresh air output ...

Страница 27: ...wing table The DIP switches are normally set to make the unit number 00 Factory setting Remote controller address DIP switch No 1 2 3 4 00 OFF OFF OFF OFF 01 ON OFF OFF OFF 02 OFF ON OFF OFF 03 ON ON OFF OFF 04 OFF OFF ON OFF 05 ON OFF ON OFF 06 OFF ON ON OFF 07 ON ON ON OFF 08 OFF OFF OFF ON 09 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON O...

Страница 28: ...L CODE SETTING Press the SET TEMP 1 button to change the signal code between Match the code on the display to the air conditioner signal code initially set to If the signal code does not need to be selected press the MODE button and proceed to STEP 2 Press the TIMER MODE button and check that the indoor unit can receive signals 2 at the displayed signal code Press the MODE button to accept the sig...

Страница 29: ...debris in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting Description Function Number Setting Value Standard 2 500 hours 11 00 Long interval 4 400 hours 01 Short interval 1 250 hours 02 No indication 03 2 Ceiling height Select the setting values in the table below according to the height of the ceiling Factory setting S...

Страница 30: ...alue is 01 room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor 7 Remote controller signal code Change the indoor unit Signal Code depending on the remote controllers Factory setting Setting Description Function Number Setting Value A 44 00 B 01 C 02 D 03 8 External input control Operation Stop mode or Forced stop mode can be selected Factory set...

Страница 31: ... on the display to the air conditioner signal code 4 Press the MODE button again to return to the clock display The signal code will be changed If no buttons are pressed within 30 seconds after the signal code is displayed the system returns to the original clock display In this case start again from step 1 The air conditioner signal code is set to A prior to shipment Contact your retailer to chan...

Страница 32: ... No Summary Wired remote controller UTY RVN M Large and full dot liquid crystal screen wide and large keys easy to press user intuitive arrow key Wired remote controller UTY RNN M Unit control is performed by wired remote controller Simple Remote Controller UTY RSN M Unit control is performed by simple remote controller ...

Страница 33: ...sm allows more flexible installation Round flange UTD RF204 Round flange is used when the fresh air duct is installed Round flange External connect kit UTY XWZX Use to connect with various peripheral devices and air conditioner PC board x 1 x 2 x 1 x 2 External control set UTD ECS5A Use to connect with various peripheral devices and air conditioner PC board Set of 6 ...

Страница 34: ...DTR_AO135E_01 2013 02 28 SINGLE TYPE AO G30LETL AO G36LETL 2 OUTDOOR UNIT ...

Страница 35: ...GERANT CIRCUIT 02 03 4 WIRING DIAGRAMS 02 04 5 CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE 02 06 6 ADDITIONAL CHARGE CALCULATION 02 07 7 AIRFLOW 02 08 8 OPERATION NOISE SOUND PRESSURE 02 09 8 1 NOISE LEVEL CURVE 02 09 8 2 SOUND LEVEL CHECK POINT 02 10 9 ELECTRIC CHARACTERISTICS 02 11 10 SAFETY DEVICES 02 12 ...

Страница 36: ... Heating 3600 3800 Type Q ty Propeller 1 Motor output W 100 100 Sound pressure level Cooling dB A 53 54 Heating 55 55 Sound power level Cooling dB A 68 69 Heating 69 70 Heat exchanger type Dimensions H W D mm 798 900 36 4 798 900 36 4 Fin pitch 1 30 1 30 Rows x Stages 2 38 2 38 Pipe type Copper Fin type Aluminium Compressor Type Q ty Twin Rotary 1 Motor output W 2100 Refrigerant Type Global Warmin...

Страница 37: ...allation of more than one unit When there are obstacles at the back or front sides 600 mm or more 250 mm or more 250 mm or more 300 mm or more 600 mm or more 100 mm or more 300 mm or more 100 m m or m ore 250 mm or more Service space If the space is larger than stated the condition will be the same as those without any obstacles 603 Air flow 900 650 830 370 99 196 21 9 77 31 330 400 170 147 12 Top...

Страница 38: ...3 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL REFRIGERANT CIRCUIT 3 MODELS AO G30LETL AO G36LETL Refrigerant direction Refrigerant pipe diameter Liquid 9 52 mm 3 8 Gas 15 88 mm 5 8 Cooling Heating ...

Страница 39: ... 02 04 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL WIRING DIAGRAMS 4 MODEL AO G30LETL ...

Страница 40: ... 02 05 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL MODEL AO G36LETL ...

Страница 41: ...0 958 0 946 0 932 0 913 0 1 000 0 994 0 983 0 966 0 954 0 939 0 920 2 Indoor unit is lower than outdoor unit 5 1 000 0 994 0 983 0 966 0 954 0 939 0 920 7 5 0 994 0 983 0 966 0 954 0 939 0 920 10 0 983 0 966 0 954 0 939 0 920 20 0 966 0 954 0 939 0 920 30 0 954 0 939 0 920 HEATING Pipe length m 5 7 5 10 20 30 40 50 Height difference H m 1 Indoor unit is higher than outdoor unit 30 0 931 0 914 0 89...

Страница 42: ...TDOOR UNIT AO G30 36LETL ADDITIONAL CHARGE CALCULATION 6 MODELS AO G30LETL AO G36LETL Refrigerant Charge Refrigerant type R410A Refrigerant amount g 2100 Total pipe length m 20 or less 30 40 50 MAX 40g m Additional charge g 0 400 800 1200 ...

Страница 43: ...TING MODEL AO G36LETL COOLING HEATING Number of rotations r p m Airflow 850 m3 h 3600 l s 1000 CFM 2119 Number of rotations r p m Airflow 850 m3 h 3600 l s 1000 CFM 2119 Number of rotations r p m Airflow 900 m3 h 3800 l s 1056 CFM 2236 Number of rotations r p m Airflow 900 m3 h 3800 l s 1056 CFM 2236 ...

Страница 44: ...B 0 0002μbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HEATING Octave band sound pressure level dB 0dB 0 0002μbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 CO...

Страница 45: ... 02 10 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL SOUND LEVEL CHECK POINT 8 2 ...

Страница 46: ...unit and outdoor unit 2 Wiring spec Selected sample Selected based on Japan Electrotechnical Standards and Codes Committee E0005 Model name AO G30LETL AO G36LETL Power supply Voltage V 230 Frequency Hz 50 1 Max operating current A 17 0 20 0 Starting current A 12 2 13 7 2 Wiring spec Main fuse Circuit breaker current A 30 Power cable mm2 3 5 ...

Страница 47: ...fuse Filter printed circuit board 250V 10A Current fuse Main printed circuit board 250V 3 15A Fan motor protection Thermal protection program OFF 140 20 C ON 110 20 C High pressure protection Pressure switch OFF 4 2 0 1MPa ON 3 2 0 15MPa Compressor protection Thermal protection program Compressor temp OFF 120 C ON 80 C Thermal protection program Discharge temp OFF 110 C ON After 7 minutes ...

Отзывы: