CONTENTS OF FUNCTION SETTING
Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in
•
accordance with the installed condition.
After the power is turned on, perform the Function Setting on the remote control.
The settings may be selected between the following two: Function Number or Setting Value.
•
Settings will not be changed if invalid numbers or setting values are selected.
•
1)
Filter sign
2)
Ceiling height
3)
Cooler room temperature correction
4)
Heater room temperature correction
5)
Auto restart
6)
Indoor room temperature sensor switching function
7)
Remote controller signal code
8)
External input control
9)
Indoor unit fan control for energy saving
1) Filter sign
The indoor unit has a sign to inform the user that it is time to clean the
fi
lter. Select the time setting
for the
fi
lter sign display interval in the table below according to the amount of dust or debris in the
room. If you do not wish the
fi
lter sign to be displayed, select the setting value for "No indication".
( . . .Factory setting)
Setting Description
Function Number
Setting Value
"Standard
(2,500 hours)"
11
00
"Long interval
(4,400 hours)"
01
"Short interval
(1,250 hours)"
02
No indication
03
2) Ceiling height
Select the setting values in the table below according to the height of the ceiling.
( . . .Factory setting)
Setting Description
Function Number
Setting Value
Standard
(2.5m to 3.0m)
20
00
High ceiling
(3.0m or more)
01
3) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
( . . .Factory setting)
Setting Description
Function Number
Setting Value
Standard
30
00
Slightly Lower control
01
Lower control
02
Warmer control
03
4) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.
( . . .Factory setting)
Setting Description
Function Number
Setting Value
Standard
31
00
Lower control
01
Slightly warmer control
02
Warmer control
03
Содержание AB G30LRTE Series
Страница 2: ...1 INDOOR UNIT CEILING TYPE AB G30LRTE AB G36LRTE DTR_AB037E_01 2013 02 28 ...
Страница 12: ... 01 09 CEILING TYPE AB G30 36LRTE CEILING TYPE AB G30 36LRTE WIRING DIAGRAMS 5 MODEL AB G30LRTE AB G36LRTE ...
Страница 34: ...DTR_AO135E_01 2013 02 28 SINGLE TYPE AO G30LETL AO G36LETL 2 OUTDOOR UNIT ...
Страница 39: ... 02 04 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL WIRING DIAGRAMS 4 MODEL AO G30LETL ...
Страница 40: ... 02 05 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL MODEL AO G36LETL ...
Страница 45: ... 02 10 OUTDOOR UNIT AO G30 36LETL OUTDOOR UNIT AO G30 36LETL SOUND LEVEL CHECK POINT 8 2 ...