- (05-86) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
PRECAUTION
About fresh air intake kit
z
The Fresh Air Intake Kit can be installed onto cassette type air conditioners.
•
The volume of ventilated air provided by the Fresh Air Intake Kit may be unable to fulfill ventilation
•
regulations in all countries.
On such occasions we ask that this kit be used along with Energy recovery ventilators.
When intaking outside air please ensure correct air-conditioning design as based on air-
•
conditioning load calculations.
As outside air is not being processed an increase in outside air load can affect air conditioning.
Installation location
z
Area that generate substances that adversely affect the equipment, such as sulfuric gas,chlorine
•
gas,add,or alkali it will cause the copper pipes and brazed joints to corrode,which can cause
refrigerant leakage.
Area with high salt content,such as at the seaside. It will deteriorate metal parts, causing the
•
parts to fall or the unit to leak water.
Be certain to use electric dampers and shutters to avoid infiltration of cold air, wind and fog
•
during shutdown in areas with cold climates, strong winds, or where fogs are common.
Please ensure the product is installed a distance of at least three times the duct diameter away
•
from exterior wall air inlets, or air exhausts for the prevention of short circuits.
Temperature conditions
z
Condensation may form on the product when outside air temperature is low, and the temperature
•
and humidity surrounding the product are high. Don't intake the air of below 0°C into the fresh air
intake kit.
The upper limit of the product’s temperature range should respond to the outdoor temperature
•
range.
About duct fan
z
When installing the duct fan, connect the drive relay (field supplied) and operate with the indoor
•
unit.
Please ensure the intake air volume is below 10% of the product’s air volume HI. When
•
the intaken air volume becomes too large there the operating noise may increase and room
temperature detection may be affected.
About the duct connection
z
Procure a duct with internal diameter that fits the external diameter of the duct flange.
•
Please note that regulations of some countries may require the use of a nonflammable duct.
•
If the duct penetrates a fire-retarding division or other fire-proofing measures, the installation
•
of fire dampers, or a construction that does not adversely affect fire control measures is a
regulatory requirement of some countries.
When using metallic ducts please ensure metals (i.e., metal lath, wire lath, stainless sheeting) are
•
electrically insulated. (A short occurring by electrical connection can cause fire)
Please ensure to thermally insulate connected ducts to prevent condensation.
•
Please make certain that netting or other measures are installed in parts exposed to the outside
•
air to prevent infiltration of small animals such as birds and insects.
Please be certain to install external air filters to parts exposed to the outside air for heat
•
exchanger protection of indoor equipment.
Please avoid the infiltration of rain water by installing outside ducts with an incline of at least 1/30,
•
and fitting hoods on openings.
Содержание AB*G18LVTB Series
Страница 59: ... 02 34 INDOOR UNIT SINGLE INDOOR UNIT SINGLE DUCT TYPE 55555 MODEL AR G36LM AR G45LM ...
Страница 60: ... 02 35 INDOOR UNIT SINGLE INDOOR UNIT SINGLE HIGH STATIC PRESSURE DUCT TYPE 55555 MODEL AR G45LH AR G54LH ...
Страница 61: ... 02 36 INDOOR UNIT SINGLE INDOOR UNIT SINGLE CEILING TYPE 55555 MODEL AB G36LR AB G45LR AB G54LR ...
Страница 107: ... 02 82 INDOOR UNIT SINGLE INDOOR UNIT SINGLE SOUND LEVEL CHECK POINT 88888 CASSETTE TYPE Microphone Microphone 1 5 m ...
Страница 147: ... 03 34 INDOOR UNITS SIMULTANEOUS MULTI INDOOR UNITS SIMULTANEOUS MULTI DUCT TYPE 55555 MODEL AR G22LM AR G24LM ...
Страница 208: ...4 OUTDOOR UNIT AIR CONDITIONER 3 phase type Single Simultaneous multi system DTR_SSM001E_03 CHAPTER04 2013 02 22 ...
Страница 214: ... 04 05 OUTDOOR UNIT OUTDOOR UNIT REFRIGERANT CIRCUIT 333 SINGLE 33333 MODEL AO G36LA AO G45LA AO G54LA ...
Страница 215: ... 04 06 OUTDOOR UNIT OUTDOOR UNIT SIMULTANEOUS MULTI TWIN 33333 MODEL AO G36LA AO G45LA AO G54LA ...
Страница 216: ... 04 07 OUTDOOR UNIT OUTDOOR UNIT SIMULTANEOUS OPERATION MULTI TRIPLE 33333 MODEL AO G36LA AO G45LA AO G54LA ...
Страница 217: ... 04 08 OUTDOOR UNIT OUTDOOR UNIT WIRING DIAGRAMS 444 MODEL AO G36LA AO G45LA AO G54LA ...
Страница 224: ... 04 15 OUTDOOR UNIT OUTDOOR UNIT SOUND LEVEL CHECK POINT 77777 Microphone 1m Microphone Air Flow ...
Страница 227: ...5 SYSTEM DESIGN AIR CONDITIONER 3 phase type Single Simultaneous multi system DTR_SSM001E_03 CHAPTER05 2013 02 22 ...
Страница 345: ...6 OPTIONAL PARTS AIR CONDITIONER 3 phase type Single Simultaneous multi system DTR_SSM001E_03 CHAPTER06 2013 02 22 ...
Страница 346: ...CONTENTS 6 OPTIONAL PARTS 1 BRANCH PIPES 06 01 2 CONTROLLER 06 04 3 CASSETTE GRILLE 06 05 4 OTHERS optional parts 06 06 ...