EXTERNAL INPUT
5-2-1.
CONTROL INPUT (Operation / Stop or Forced stop)
Corresponding indoor units : All indoor units
The air conditioner can be remotely operated by means of the following on-site work.
"Operation / Stop" mode or "Forced stop" mode can be selected with function setting of indoor unit.
Unit operation is started at the following contents by adding the contact input of a commercial ON /
OFF switch to a connector on the external control PC board and turning it ON.
Unit operation
Initial starting after turned power on
Other than initial starting
Operation mode
Auto changeover
Mode at previous operation
Set temperature
24°C
Temperature at previous operation
Air flow mode
AUTO
Mode at previous operation
Up-down air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Left-right air direction (swing)
Standard air direction (swing OFF)
Air direction at previous operation
Circuit diagram example
z
When function setting is "Operation / Stop" mode
●
When function setting is "Forced stop" mode
●
Remote controller
On
On
On
Input signal
On
Off
Indoor unit
Operation
Stop
Command
Forced stop
Normal
Remote control
operation invalidity
Indoor unit
control PC board
Connector
1
2
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10 m.
Contact capacity : 5VDC or more, 15mA or more.
Please use the non-polar relays and switches.
Surely insulate with
insulation tape etc. since
this wire is not used.
*10 m
Connected unit
Ex.) Switch
ON
OFF
Operation
Stop
Input signal
Indoor unit
Содержание AB*G18LVTB Series
Страница 59: ... 02 34 INDOOR UNIT SINGLE INDOOR UNIT SINGLE DUCT TYPE 55555 MODEL AR G36LM AR G45LM ...
Страница 60: ... 02 35 INDOOR UNIT SINGLE INDOOR UNIT SINGLE HIGH STATIC PRESSURE DUCT TYPE 55555 MODEL AR G45LH AR G54LH ...
Страница 61: ... 02 36 INDOOR UNIT SINGLE INDOOR UNIT SINGLE CEILING TYPE 55555 MODEL AB G36LR AB G45LR AB G54LR ...
Страница 107: ... 02 82 INDOOR UNIT SINGLE INDOOR UNIT SINGLE SOUND LEVEL CHECK POINT 88888 CASSETTE TYPE Microphone Microphone 1 5 m ...
Страница 147: ... 03 34 INDOOR UNITS SIMULTANEOUS MULTI INDOOR UNITS SIMULTANEOUS MULTI DUCT TYPE 55555 MODEL AR G22LM AR G24LM ...
Страница 208: ...4 OUTDOOR UNIT AIR CONDITIONER 3 phase type Single Simultaneous multi system DTR_SSM001E_03 CHAPTER04 2013 02 22 ...
Страница 214: ... 04 05 OUTDOOR UNIT OUTDOOR UNIT REFRIGERANT CIRCUIT 333 SINGLE 33333 MODEL AO G36LA AO G45LA AO G54LA ...
Страница 215: ... 04 06 OUTDOOR UNIT OUTDOOR UNIT SIMULTANEOUS MULTI TWIN 33333 MODEL AO G36LA AO G45LA AO G54LA ...
Страница 216: ... 04 07 OUTDOOR UNIT OUTDOOR UNIT SIMULTANEOUS OPERATION MULTI TRIPLE 33333 MODEL AO G36LA AO G45LA AO G54LA ...
Страница 217: ... 04 08 OUTDOOR UNIT OUTDOOR UNIT WIRING DIAGRAMS 444 MODEL AO G36LA AO G45LA AO G54LA ...
Страница 224: ... 04 15 OUTDOOR UNIT OUTDOOR UNIT SOUND LEVEL CHECK POINT 77777 Microphone 1m Microphone Air Flow ...
Страница 227: ...5 SYSTEM DESIGN AIR CONDITIONER 3 phase type Single Simultaneous multi system DTR_SSM001E_03 CHAPTER05 2013 02 22 ...
Страница 345: ...6 OPTIONAL PARTS AIR CONDITIONER 3 phase type Single Simultaneous multi system DTR_SSM001E_03 CHAPTER06 2013 02 22 ...
Страница 346: ...CONTENTS 6 OPTIONAL PARTS 1 BRANCH PIPES 06 01 2 CONTROLLER 06 04 3 CASSETTE GRILLE 06 05 4 OTHERS optional parts 06 06 ...