Wired remote controller ( 2-Wire )
Indoor unit Controller PCB circuit
When the address number set by auto setting and manual setting are mixed in
one RC group.
When the duplicated address number exists in one RC group.
Check Point 3 : Check Indoor unit controller PCB
1. Wrong wiring of RCgroup 2. Wrong remote address setting 3. Indoor unit controller PCB failure
4. Remote controller failure
Check Point 1 : Wire installation
Wrong wire connection in RCgroup (Please refer to the installation manual)
Change controller PCB and check the Error after setting remote controller address
Check if controller PCB damage
Check Point 2 : Wrong RCgroup setting
The given address number by auto setting (00) and the manual set number (Except 00) were not existing in one RCG.
The remote controller address setting by U.I. were not existing same address.
The duplicated address number is not existing in one RCgroup
Trouble shooting 7
INDOOR UNIT Error Method:
Address Setting Error
In Wired Remote Controller System
Detective Actuators:
Detective details:
Forecast of Cause:
02-22
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 2 time Flash, Timer lamp: 6 time Flash
Economy lamp : Continuous flash.
ERROR CODE : [E : 26]
For AR*G**LSLAP