Description
Q’ty
Application
STANDARD PARTS
CONNECTION PIPE REQUIREMENT
The following installation parts are furnished.
Use them as required.
1
1
2
Small
4
Large
4
4
4
1
1
1
2
1
Drain hose insulation
VT wire
Coupler heat insulator
(large)
Nylon fastener
Special nut A
(large flange)
Coupler heat insulator
(small)
Adhesive type
70 x 230
For indoor side
pipe joint
(large pipe)
For fixing the
coupler heat
insulator
For installing
indoor unit
For fixing the drain
hose L 280 mm
For indoor side
pipe joint
(small pipe)
INDOOR UNIT ACCESSORIES
Special nut B
(small flange)
For installing
indoor unit
Installation template
For positioning
the indoor unit
Auxiliary pipe assembly
For connecting
the piping
Indoor capillary tube
(This part is
enclosed with the
30,000 and 36,000
BTU/h versions.)
BR sheet
65 x 130 x T5
(This part is
enclosed with the
30,000 and 36,000
BTU/h versions.)
Table 1
ELECTRICAL REQUIREMENT
Table 2
Diameter
2.5
1.5
MAX
MIN
Connection
cord (mm
2
)
45,000 / 36,000
BTU/h class
Small
Large
9.53 mm
19.05 mm
30,000
BTU/h class
9.53 mm
15.88 mm
●
Use 0.7 mm to 1.2 mm thick pipe.
●
Use pipe with water-resistant heat insulation.
●
Use pipe that can withstand a pressure of 3,040 kPa.
●
Always use H07RN-F or equivalent as the connec-
tion cord.
●
Install the disconnection device with a contact gap
of at least 3 mm nearby the units. (Both indoor unit
and outdoor unit)
,,
@@
AA
BB
CC
ÀÀ
ÁÁ
ÂÂ
ÃÃ
– 3 –