background image

– 8 –

6. HOW  TO  CONNECT  WIRING  TO  THE  TERMINALS

Fig. 31 

Solid wire 

Strand wire 

Loop

Insulation

Strip 15/16”

(25 mm)

Strip 3/8”

(10 mm)

Screw with
special washer 

1. IF  ONE  WIRE  IS  CONNECTED  TO  ONE

TERMINAL  BLOCK

A. For solid core wiring (or F-cable)

(1) Cut the wire end with a wire cutter or wire-

cutting pliers, then strip the insulation to about
15/16” (25 mm) to expose the solid wire.

(2) Using a screwdriver, remove the terminal

screw(s) on the terminal board.

(3) Using pliers, bend the solid wire to form a loop

suitable for the terminal screw.

(4) Shape the loop wire properly, place it on the ter-

minal board and tighten securely with the termi-
nal screw using a screwdriver.

2. IF  TWO  WIRES  ARE  CONNECTED  TO

ONE  TERMINAL  BLOCK.

A. As a rule, round terminal should be used

to connect to the terminal block.

(1) Cut the wire end with a wire cutter or wire-

cutting pliers, then strip the insulation to about
3/8” (10 mm) to expose the strand wiring.

(2) Using a screwdriver, remove the terminal

screw(s) on the terminal board.

(3) Using a round terminal fastener or pliers, secure-

ly clamp a round terminal to each stripped wire
end.

(4) Position the round terminal wire, and replace

and tighten the terminal screw using a screw-
driver.

B. For strand wiring

(1) Cut the wire end with a wire cutter or wire-

cutting pliers, then strip the insulation to about
3/8” (10 mm) to expose the strand wiring.

(2) Using a screwdriver, remove the terminal

screw(s) on the terminal board.

(3) Using a round terminal fastener or pliers, secure-

ly clamp a round terminal to each stripped wire
end.

(4) Position the round terminal wire, and replace

and tighten the terminal screw using a screw-dri-
ver.

Round
terminal 

Terminal
board 

Round
terminal 

Screw with
special washer 

Round terminal 

Wire 

Wire

• Install the drain pipe with downward gradient (1/50 to

1/100) and so there are no rises or traps in the pipe.

• Use general hard polyvinyl chloride pipe (VP25)

[outside diameter 38 mm].

• During installation of the drain pipe, be careful to

avoid applying pressure to the drain port of the
indoor unit.

• When the pipe is long, install supporters (Fig. 27).

• Do not perform air bleeding.

• Always heat insulate (8 mm or over thick) the indoor

side of the drain pipe.

(1) Install insulation for the drain pipe ( See Figs. 28 and

29).

Cut the included insulation material to an appropri-
ate size and adhere it to the pipe.

(2) If "

q

Right rear piping": fasten the drain pipe with

VT wire so that the pipe slopes correctly within the
indoor unit (Fig. 30).

5. DRAIN  PIPING

Fig. 27 

Drain pipe 

Arrange the drain pipe
lower than this position. 

GOOD 

Lifted
up 

BAD 

BAD 

Wave 

End in water 

Supporter

5 to 6.5 ft (1.5 to 2 m)

Fig. 28 

Drain pipe 

Insulation for Drain pipe
(To be obtained locally.  

Length should be at least 8 mm.) 

Indoor unit 
(drain port) 

Drain pipe insulation
(accessories)

Fig. 29 

Indoor unit 

No gap 

Drain pipe insulation 

Drain pipe 

10 mm or over

Fig. 30 

VT wire 

Drain hose 

Indoor unit (rear view)

Terminal block

Содержание 9363005011

Страница 1: ...igerant comes in contact with a flame it produces a toxic gas 5 Do not turn on the power until all installation work is complete Be careful not to scratch the air conditioner when handling it After installation explain correct operation to the customer using the operating manual Let the customer keep this installation installation manual because it is used when the air conditioner is serviced or m...

Страница 2: ...ts should not be obstructed the air should be able to blow all over the room 3 Do not install the unit where it will be exposed to direct sunlight 4 Install the unit where connection to the outdoor unit is easy 5 Install the unit where the drain pipe can be easily installed 6 Take servicing etc into consideration and leave the spaces shown in Fig 1 or 2 Also install the unit where the filter can b...

Страница 3: ...t Installation template For positioning the indoor unit Auxiliary pipe assembly For connecting the piping Indoor capillary tube This part is enclosed with the 30 000 and 36 000 BTU h versions BR sheet 65 x 130 x T5 This part is enclosed with the 30 000 and 36 000 BTU h versions Table 1 ELECTRICAL REQUIREMENT Table 2 Diameter 2 5 1 5 MAX MIN Connection cord mm2 45 000 36 000 BTU h class Small Large...

Страница 4: ...er B Left side Side cover A Right side Fig 5 Drilling position for Suspension bolt Ceiling Wall Template Drilling position for piping Fig 6 30 mm Suspension bolt pitch 1 600 mm 30 mm INDOOR UNIT TOP VIEW Dimensions Space Required for Installation For Half Concealed Installation Suspension bolt pitch should be as shown in Fig 6 Side cover B Right side 1 LOCATION OF CEILING SUSPENSION BOLTS 10 mm 15...

Страница 5: ...ou will set the suspension bolts Note that anchor bolts are M10 bolts to be obtained locally 2 Install the anchor bolts then temporarily attach spe cial nut B included and a locally procured M10 nut to each of the bolts See Fig 11 For Half Concealed Installation When installing the indoor unit in a semi concealed shape make sure to reinforce the insulation of the unit on all sides Drops of water m...

Страница 6: ...n three times When bending the pipe do not bend it as is The pipe will be collapsed In this case cut the heat insulating pipe with a sharp cutter as shown in Fig 17 and bend it after exposing the pipe After bending the pipe as you want be sure to put the heat insulating pipe back on the pipe and secure it with tape Fig 17 Pipe Heat insulating pipe Cutter Cut line Fig 16 Extend the pipe by unwindin...

Страница 7: ...Fig 21 in order to tighten the flare nut correctly Pipe Tightening torque Small pipe 9 53 mm dia 310 to 350 kgf cm 30 4 to 34 3 N m Large pipe 15 88 mm dia 750 to 800 kgf cm 73 5 to 78 4 N m Large pipe 19 05 mm dia 800 to 1 000 kgf cm 78 4 to 98 N m Table 4 Flare nut tightening torque Indoor unit side Outdoor unit side Indoor capillary tube Indoor capil lary tube Brazing all around Fig 23 BR sheet...

Страница 8: ...wiring 2 Using a screwdriver remove the terminal screw s on the terminal board 3 Using a round terminal fastener or pliers secure ly clamp a round terminal to each stripped wire end 4 Position the round terminal wire and replace and tighten the terminal screw using a screw dri ver Round terminal Terminal board Round terminal Screw with special washer Round terminal Wire Wire Install the drain pipe...

Страница 9: ...ting wires with different diameters causes the wires to heat up due to loose connections this method should not be used HOW TO FIX THE CONNECTION CORD After passing the connection cord through the insulation tube fasten it with the cord clamp Use VW 1 0 5 to 1 0 mm thick PVC tube as the insulation tube Fig 34 Insulation tube Insulation tube Cord clamp Fig 36 Cover A Control box 1 Before starting w...

Страница 10: ... Connect a maximum of 2 wires on a single terminal block If 3 or more wires are connected they could become loose and cause heating 2 Crossovers as in q should not be connected when connecting wires between the master unit and slave units and from slave unit to slave unit The system will not operate correctly Indoor unit Outdoor unit Master R Slave Slave Slave qwe qwe qwe qwe qwe S T N E BAD Fig 3...

Страница 11: ...d bottom with nippers file etc 2 Connect the remote controller cord to the remote controller terminal board specified in Fig 46 3 Clamp the remote controller cord sheath with the binder small as shown in Fig 46 4 Cut off the excess binder 2 When remote controller cord embedded 1 Embed the remote controller cord and box 2 Pass the remote controller cord through the hole at the remote controller cas...

Страница 12: ...t running When EE EE blinks at the current time display there is an error inside the air conditioner If the SET TIME button and SET TEMP DAY button are pressed simultaneously for more than three sec onds the self diagnosis check will start and the error contents will be displayed at the current time dis play Fig 49 When the operation lamp lights press the START STOP button and after operation lamp...

Страница 13: ...lamp TIMER lamp VERTICAL SWING lamp Error contents Model information abnormal permanent type Drain abnormal permanent type Indoor fan abnormal Room air temperature thermistor open circuited Room air temperature thermistor shortcircuited Piping thermistor open circuited Piping thermistor short circuited Serial communications abnormal Reverse phase wire connection abnormal Outdoor heat exchange ther...

Отзывы: