1-1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is 2°C higher than a set temperature,
the compressor operation frequency will attain to maximum performance.
* If the room temperature is 2.5°C lower than a set temperature, the compressor
will be stopped.
* When the room temperature is b2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
minimum
frequency
maximum
frequency
16rps
16rps
16rps
16rps
93rps
90rps
85rps
100rps
AU* G45LRLA
AR* G45LMLA
AB* G45LRTA
AR* G45LHTA
AU* G54LRLA
AR* G54LHTA
Hi
Me
Lo
Qu
93rps
93rps
78rps
73rps
75rps
75rps
68rps
56rps
68rps
68rps
56rps
47rps
44rps
44rps
44rps
29rps
100rps
100rps
85rps
76rps
78rps
78rps
73rps
62rps
73rps
73rps
62rps
50rps
44rps
44rps
44rps
29rps
85rps
85rps
78rps
68rps
77rps
77rps
68rps
62rps
76rps
76rps
68rps
56rps
---
---
---
---
90rps
90rps
85rps
73rps
85rps
85rps
76rps
68rps
81rps
81rps
73rps
62rps
---
---
---
---
A zone
B zone
C zone
AU* G45LRLA
AR* G45LMLA
AB* G45LRTA
AU* G54LRLA
D-F zone
A zone
B zone
C zone
D-F zone
A zone
B zone
C zone
AR* G45LHTA
AR* G54LHTA
D-F zone
( Table 1 : Compressor Frequency Range )
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
01-01
A zone
B zone
C zone
D-F zone
Fan speed mode
1. DESCRIPTION OF EACH CONTROL OPERATION
Outdoor air
temperature
A zone
B zone
C zone
D zone
E zone
F zone
When the room
temperature rises
When the room
temperature drops
36°C
32°C
21°C
12°C
2°C
34°C
30°C
19°C
10°C
0°C
Содержание AB* G45LRTA
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Страница 36: ......
Страница 37: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Страница 80: ......
Страница 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2013 Printed in Japan ...