1-7. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in Table 7.
Cooling
Heating
Min
Max
Min
Max
Dry
(Table 7 : Compressor Operation Frequency Range)
01-10
AO* G45LETL
16rps
16rps
93rps
----
85rps
----
----
100rps
----
90rps
AO* G54LETL
16rps
16rps
110rps
110rps
44rps
44rps
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Fig.9.
(Fig.9 : Compressor Control at Start-up)
39
90
57
68
180
420
85
(rps)
Upper
limit
speed
(sec)
480
Elapsed time
39
200
57
68
700
840
85
(rps)
Upper
limit
speed
(sec)
1010
Elapsed time
39
90
57
68
210
270
85
(rps)
Upper
limit
speed
(sec)
300
Elapsed time
Ta : Outdoor temperature
< Normal start-up >
Immediate start-up after power-ON (cooling)
Immediate start-up after power-ON (Hearting Ta < 10
℃
)
Immediate start-up after power-ON (Hearting Ta > 10
℃
)
=
45LRLA
45LMLA
45LRTA
45LHTA 54LRLA 54LHTA
Содержание AB* G45LRTA
Страница 3: ...1 DESCRIPTION OF EACH CONTROL OPERATION R410A Cassette Duct Ceiling type INVERTER ...
Страница 36: ......
Страница 37: ...2 TROUBLE SHOOTING R410A Cassette Duct Ceiling type INVERTER ...
Страница 80: ......
Страница 81: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan May 2013 Printed in Japan ...