5. COOL AIR PREVENTION CONTROL (Heating mode)
6. DRY OPERATION
Refer to the Fig. 3-1, 3-2.
During the dry mode operation, the fan speed setting can not be changed.
7. [For AU*G45/ 54LRTA, AR*G45LMLA, AB*G45LRTA]
MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)
Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.3-1.
8. [For AU*G45/ 54LRTA, AR*G45LMLA, AB*G45LRTA]
INDOOR UNIT FAN (CONTROL FOR ENERGY SAVING (Cooling mode))
Switch the airflow at cooling mode, and the indoor fan motor will run as shown in Fig.3-1.
It depends on the Function setting "Indoor unit fan control for energy saving".
01-08
The maximum value of the indoor fan speed is set as shown in Fig.8, based on the detected
temperature by the indoor heat exchanger sensor on heating mode.
When the compressor does not operate, the indoor fan motor operates [S-Lo] or [Stop] mode.
( Fig.8 : Cool Air Prevention Control )
[ AU*G45/ 54LRLA, AB*G45LRTA ]
[ AR*G45LMLA ]
*Hi
or setting fan mode
*Lo
or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
Cool air
prevention
S-Lo
S-Lo
42°C
30°C
34°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
Hi
*Me+
or setting fan mode
*Lo
or setting fan mode
*Lo
or setting fan mode
*Lo
or setting fan mode
39°C
37°C
37°C
32°C
24°C
*Lower speed is selected.
42°C
30°C
34°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
Hi
*Me+
or setting fan mode
*Lo
or setting fan mode
39°C
37°C
37°C
32°C
24°C
*Lower speed is selected.
*Lower speed is selected.
Hi
*Lo
or setting fan mode
*Lo
or setting fan mode
37°C
29°C
32°C
24°C
Indoor heat exchanger
temperature rises
Indoor heat exchanger
temperature drops
*Lower speed is selected.
13 min. later
13 min. later
[ AR*G45/ 54LHTA ]
Setting fan mode
stop
27°C
Indoor heat exchanger
temperature
Setting fan mode
Lo
27°C
Indoor heat exchanger
temperature
13 min. later