E01 to E03
Terminal [X1] to [X3] Function
E98, E99
Terminal [FWD] and [REV] Function
Function codes E01 to E03, E98 and E99 allow you to assign commands to terminals [X1] to
[X3], [FWD], and [REV] which are general-purpose, programmable, digital input terminals.
These function codes may also switch the logic system between normal and negative to
define how the inverter logic interprets either ON or OFF status of each terminal. The default
setting is normal logic system "Active ON." So, explanations that follow are given in normal
logic system "Active ON."
In the case of digital input, you can assign commands to the switching means for the run
command and its operation and the reference frequency (e.g.,
SS1
,
SS2
,
SS4
,
SS8
,
Hz2/Hz1
,
Hz/PID
,
IVS
, and
LE
). Be aware that switching any of such signals may cause a
sudden start (running) or an abrupt change in speed.
An accident or physical injury may result.
Function code data
Terminal commands assigned
Symbol
Active ON
Active OFF
0
1000
Select multistep frequency (0 to 15 steps)
SS1
1
1001
SS2
2
1002
SS4
3
1003
SS8
4
1004
Select ACC/DEC time
RT1
6
1006
Enable 3-wire operation
HLD
7
1007
Coast to a stop
BX
8
1008
Reset alarm
RST
9
1009
Enable external alarm trip
THR
10
1010
Ready for jogging
JOG
11
1011
Select frequency command 2/1
Hz2/Hz1
13
Enable DC braking
DCBRK
17
1017
UP (Increase output frequency)
UP
18
1018
DOWN (Decrease output frequency)
DOWN
19
1019
Enable data change with keypad
WE-KP
20
1020
Cancel PID control
Hz/PID
21
1021
Switch normal/inverse operation
IVS
24
1024
Enable communications link via RS-485
LE
33
1033
Reset PID integral and differential components
PID-RST
34
1034
Hold PID integral component
PID-HLD
90
1090
Traverse On
TRV
91
1091
Traverse Up Offset
TRV UP_OFFSET
92
1092
Traverse Dn Offset
TRV DN_OFFSET
Any negative logic (Active OFF) command cannot be assigned to the functions
marked with "
" in the "Active OFF" column.
The "Enable external alarm trip" and "Force to stop" are fail-safe terminal commands.
For example, when data = 9 in "Enable external alarm trip," "Active OFF" (alarm is
triggered when OFF); when data = 1009, "Active ON" (alarm is triggered when ON).