C codes: Control Functions
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
C01
Jump Frequency 1
2
3
(Hysteresis width)
0.0 to 400.0
0.1
Hz
Y
Y
0.0
C02
Y
Y
0.0
C03
Y
Y
0.0
C04
0.0 to 30.0
0.1
Hz
Y
Y
3.0
C05
Multistep Frequency 1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0.00 to 400.0 *1
0.01
Hz
Y
Y
0.00
C06
Y
Y
0.00
C07
Y
Y
0.00
C08
Y
Y
0.00
C09
Y
Y
0.00
C10
Y
Y
0.00
C11
Y
Y
0.00
C12
Y
Y
0.00
C13
Y
Y
0.00
C14
Y
Y
0.00
C15
Y
Y
0.00
C16
Y
Y
0.00
C17
Y
Y
0.00
C18
Y
Y
0.00
C19
Y
Y
0.00
C20
Jogging Frequency
0.00 to 400.0 *1
0.01
Hz
Y
Y
0.00
C21
Timer Operation
0: Disable
1: Enable
–
–
N
Y
0
C30
Frequency Command 2
0: UP/DOWN keys on keypad
1: Voltage input to terminal [12] (0 to +10
VDC)
2: Current input to terminal [C1] (4 to 20 mA
DC)
3: Sum of voltage and current inputs to
terminals [12] and [C1]
4: Built-in potentiometer (POT)
7: Terminal command
UP
/
DOWN
control
–
–
N
Y
2
C32
Analog Input Adjustment
for Terminal [12] (Gain)
(Filter time constant)
(Gain base point)
0.00 to 200.0 *1
0.01
%
Y*
Y
100.0
C33
0.00 to 5.00
0.01
s
Y
Y
0.05
C34
0.00 to 100.0 *1
0.01
%
Y*
Y
100.00
C37
Analog Input Adjustment
for Terminal [C1] (Gain)
(Filter time constant)
(Gain base point)
0.00 to 200.0 *1
0.01
%
Y*
Y
100.00
C38
0.00 to 5.00
0.01
s
Y
Y
0.05
C39
0.00 to 100.0 *1
0.01
%
Y*
Y
100.00
C40
Terminal [C1] Input
Range Selection
0: 4 to 20 mA
1: 0 to 20 mA
–
–
N
Y
0
C50
Bias
(Frequency command 1)
(Bias base point)
0.00 to 100.0 *1
0.01
%
Y*
Y
0.00
C51
Bias (PID command 1)
(Bias value)
(Bias base point)
-100.0 to 100.0 *1
0.01
%
Y*
Y
0.00
C52
0.00 to 100.0 *1
0.01
%
Y*
Y
0.00
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor
can display.(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
5-10