![Fuji Electric UG220H Series Скачать руководство пользователя страница 155](http://html1.mh-extra.com/html/fuji-electric/ug220h-series/ug220h-series_user-manual_2341966155.webp)
2 - 86
GE Fanuc PLC • 2
(90 series SNP-X)
Available PLC
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
Available Memory
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
29
19200bps
Odd
8
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
1
Function
Item
Setting of PLC
19200bps
Odd
8
1
Comm. Parameter of POD
SNP-X (fixed)
RS-485 [Wiring Diagram 1]
Series 90 micro
(CPU port)
Series 90-30
(CPU port)
Select PLC Type
90 Series
(SNP-X)
PLC
Wiring Diagram
29 GE Fanuc PLC
•
2
Memory
TYPE
Remarks
R
(data register)
0
I
(input)
1
Q
(output)
2
M
(internal relay)
3
G
(global relay)
4
AI
(analog input)
5
AQ
(analog output)
6
T
(temporary memory)
7
S
(system status)
8
Read only
SA
(system status)
9
SB
(system status)
10
SC
(system status)
11
Содержание UG220H Series