2 - 82
1747-KE
Set up the parameters for 1747-KE, using the software specifically designed for this purpose.
DF1 Port Setup Menu
Baudrate
: 19200
Bits Per Character
: 8
Parity
: Even
Stop Bits
: 1
DF1 Full-Duplex Setup Parameters
Duplicate Packet Detection
: Enabled
Checksum
: BCC
Constant Carrier Detect
: Disabled
Message Timeout
: 400
Hardware Handshaking
: Disabled
Embedded Response Detect
: Auto Detect
ACK Timeout( 5ms)
: 90
ENQuiry Retries
: 3
NAK Received Retries
: 3
Wiring
The following is a diagram to show the wiring of the cable which connects POD to PLC.
RS-232C
Wiring Diagram 1
D-sub 25pin(Male: )
FG
SD
RD
RS
CS
1
2
3
4
5
DCD
RXD
PLC
D-sub 9pin(Female: )
TXD
DTR
1
2
3
4
5
COM
DSR
6
7
8
RTS
CTS
SG
7
POD (CN1)
*
Use twist shielded cables.