4
Table 2-1 Name
No
Name
Function
0.5s push When UTL normally, output
1
ON button
3s push
When UTL abnormally, output (On-Battery operation)
2
OFF button
3s push
Output stop
0.5s push
Buzzer stop (The buzzer of that time is stopped.)
Configuration mode(select cntent) : Return to Item display.
3s push
Return from configuration (Only Configuration mode)
3
ESC button
3s push
Self test (Stanby, HE-Standby,On-Line,On-HE only)
0.5s push
Latest alarm display(Automatically return to normal display)
Configuration mode : Select content/Item.
4
SET button
3s push
Go to configuration (All mode)
5
↑ ↓ button
0.5s push
Change the display (Automatically return to initial display)
Configuration mode : Chnage content/Item
ON
State of output
1s ON 1s OFF repeat
State of no output
6
OPERATION
LED
OFF
Converter OFF
ON
Normal
OFF
Hight Effeciency (HE)
0.5s ON 0.5s OFF repeat
Battery
7
MODE LED
2s ON 2s OFF repeat
Bypass
ON
Battery disconnect
0.5s ON 0.5s OFF repeat
Constant Current Charge
Or Immediately before Battery ShutDown
1s ON 1s OFF repeat
Self Test / Low Battery
8
BATTERY
LED
2s ON 2s OFF repeat
Service Battery
ON
Alarm
1s ON 1s OFF repeat
Bypass not available
9
ALARM LED
2s ON 2s OFF repeat
Input abnormal
10
LCD
State display
11
Air-Intake
Air intake area
12
Screw
For the panel assembly
・The buzzer stops momentarily at the above time after it presses it. The function
is not recognized when not pressing it until the buzzer sound stops
momentarily. Press it until the buzzer sound stops momentarily.
Ex)ESC button
Buzzer
0.5s
3s
ON
OFF
ESC Button
ON
OFF