21
・UPS returns by the autoreturn function when the overload is released. However,
when the input deviates from the range of the zero transfer, the return
operation is not done.
・When the overload of 110% or more continues, the output is cut.
・When the
“
SET
”
button is pushed after transfering to the by-pass by the event,
the mode and abnormality when abnormality occurs are displayed. UPS returns
to the normal display when leaving it.
・When the phase match cannot be done even within bypass available, the UPS
doesn't change to the Online operation. And On-Bypass is kept.
4-1-5 Standby
The state that UPS has stopped outputting is indicated. OPERATION LED
blinks for this period. Other states can be displayed with the ▲ button/▼
button. "Standby",
“
HE Standby
”
,
“
Bypass Standby
”
,
“
Battery Standby
”
is
displayed in LCD for this period.
・Battery standby effects only schedule by communication from management
software.
・Bypass standby effects only manual bypass setting.
4-1-6 Converter OFF
Converter OFF indicates the state to have turned off AC/DC, DC/AC,
DC/DC of UPS. OPERATION LED is unlighting, and MODE LED blink every
2 seconds for this period. It changes in this state by alarm generation or
an input abnormal. Other states can be displayed with ▲ button/ ▼
button. "Converter OFF" is displayed in LCD for this period.
・When the
“
SET
”
button is pushed after transfering to the converter OFF by the
internal abnormality, the mode and abnormality when abnormality occurs are
displayed. UPS returns to the normal display when leaving it.
4-1-7 Powerdown
Powerdown indicates the state to have turned off AC/DC, DC/AC,
DC/DC of UPS. MODE LED blink for this period. "Power Down" is
displayed in LCD for this period. The state cannot be transferred from
Power-Down. There is only reset by detaching the plug. Other states can
be displayed with ▲ button/▼ button.
4-1-8 Charging
BATTERY LED blink every 0.5 seconds for fast charging.