54
Table 5: Function Code-to-Register Conversion Examples
Function Code Group
Group
Number
Example
Code
Name
F
Fundamental
Functions
0
F07 (acceleration time 1): (0 x 256) + 7 + 1 = 8
E
Extension
Terminal
Functions
1
E98 (terminal [FWD] function): (1 x 256) + 98 + 1 = 355
C
Control
Functions
2
C20 (jogging frequency): (2 x 256) + 20 + 1 = 533
P
Motor 1
Parameters
3
P03 (motor 1 rated current): (3 x 256) + 3 + 1 = 772
H
High
Performance
Functions
4
H11 (deceleration mode): (4 x 256) + 11 + 1 = 1036
A
Motor 2
Parameters
5
A05 (motor 2 torque boost): (5 x 256) + 5 + 1 = 1286
o
Operational
Functions
6
o01: (6 x 256) + 1 + 1 = 1538
S
Command
Data
7
S05 (frequency command): (7 x 256) + 5 + 1 = 1798
M
Monitor Data 1
8
M09 (output frequency): (8 x 256) + 9 + 1 = 2058
r
Motor 4
Parameters
10
r02 (motor 2 base frequency): (10 x 256) + 6 + 1 = 2563
J
Application
Functions 1
13
J03 (PID proportional gain): (13 x 256) + 3 + 1 = 3332
y
Link Functions
14
y98 (bus link function): (14 x 256) + 98 + 1 = 3683
W
Monitor Data 2
15
W32 (PID output): (15 x 256) + 32 + 1 = 3873
X
Alarm Data 1
16
X00 (alarm history / latest): (16 x 256) + 0 + 1 = 4097
Z
Alarm Data 2
17
Z53 (3
rd
last alarm torque): (17 x 256) + 53 + 1 = 4406
b
Motor 3
Parameters
18
b12 (motor 3 starting frequency): (18 x 256) + 12 + 1 = 4621
d
Application
Functions 2
19
d24 (zero speed control): (19 x 256) + 24 + 1 = 4889
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: [email protected]