Installation and Mounting

 

3-1

 

External/Panel Cut Dimensions

Caution

 

Panel cut dimensions should also meet the above dimensions after the panel
is coated.
Cautions when Close Fit Mounting:

 

When the power supply is AC 200V, keep the maximum ambient temperature
at 45°C. For vertical close-fit mounting, use a power source of 100V AC. 
(In both cases, a fan is recommended as a measure against radiation.)

 

When there is an instrument larger than 70 mm or a wall to the right of
the controller, move it as least 30 mm away.

Cautions when wiring:

 

 

Start by wiring from the left-hand terminals (terminals 1 to 6).

 

 

Use a screw that is the right size on terminals and tighten them with a
torque of about 0.8 N/m.

 

 

Do not attach anything to unused terminals. (Do not use relay terminals.)

installing multiple controllers

45.

63 or more

+0.5
0

45.

73 or more

+0.5

0

Installing multiple controllers horizontally
(In this installing, the waterproof of PXG is lost.)

(48 

×

 n–3)

+0.5
0

+0.5

0

45

PC loader interface

13-18

7-12

1-6

Panel

Packing

Mounting bracket

Terminal screw M3

44.8

48

48

8

79.8

44.8

44.8

48

57

6.2

Panel thickness 1 to 8 mm

13

16

17

18

14

15

7

8

10

11

12

9

1

2

4

5

6

3

SV

PV

Содержание Micro Controller X PXG4

Страница 1: ...ed for continuous and safe use of this equipment Some parts installed on this equipment have a limited life and or may deteriorate with age The warranty period for this unit including accessories is o...

Страница 2: ...auxiliary relay If the output operation frequency is high selecting a SSR SSC drive output type is recommended Proportionate cycles Relay output 30 seconds or more SSR SSC drive output 1 second or mo...

Страница 3: ...ontroller move it as least 30 mm away Cautions when wiring Start by wiring from the left hand terminals terminals 1 to 6 Use a screw that is the right size on terminals and tighten them with a torque...

Страница 4: ...ction 7 8 9 10 Relay output 13 14 Current output 13 14 SSR drive 3 4 14 13 Voltage output Control output 1 15 16 17 18 Thermocouple input 15 16 17 18 A B B Resistance bulb input 15 16 17 18 Current vo...

Страница 5: ...lay and Status Display In monitor mode the PV display shows item names while the SV display shows the input out put values For more details on P P P PA A A AS S S SS S S S PASS see 5 6 Key Lock and Pa...

Страница 6: ...E EF F F FE E E E FEFE is entered as P P P PA A A AS S S SS S S S PASS all of the channels OPE ch to DSP ch can be displayed and set This super password function is useful when you forget the set pass...

Страница 7: ...d d d d7 7 7 7 d7 Differential time 7 Sets the differential time 0 0 to 999 9 sec 60 0 sec h h h hy y y yS S S S7 7 7 7 hyS7 ON OFF control hysteresis 7 Sets the hysteresis when using the ON OFF cont...

Страница 8: ...5 Note1 r r r rt t t tF F F F rTF RSV input filter Sets the time constant for the RSV input filter 0 0 to 120 0 sec 0 0 sec Note1 fixed at 0 8bit PV input underflow 9bit PV input overflow 10bit underr...

Страница 9: ...it2 non excitation output alarm function bit3 hold reset function RST S S S St t t tm m m md d d d STMd Start mode Sets the operation mode when starting up Auto auto mode startup Man manual mode start...

Страница 10: ...et the PID parameter when using fuzzy control Setting fuzzy PID control 7 4 Self tuning Control Self tuning Control is a control which automatically calculate the value of PID under the condi tion tha...

Страница 11: ...ontrol equipment power t SV process value control loop close close open PV Point Set the following parameters before running auto tuning PV input type PV input upper limit PV input lower limit Decimal...

Страница 12: ...r r r r and set the ramp time 6 Display the soak time parameter t t t tm m m m1 1 1 1r r r r and set the soak time 7 Repeat steps 4 through 7 and set the remaining parameters MV MV1 MV2 MV1 MV2 MV lim...

Страница 13: ...er DO2 Starts the specified timer for DO2 2 2 2 23 3 3 3 Start timer DO3 Starts the specified timer for DO3 2 2 2 24 4 4 4 No function Do not set 2 2 2 25 5 5 5 No function Do not set 2 2 2 26 6 6 6 S...

Страница 14: ...ent 96 Time signal 26th segment 97 Time signal 27th segment 98 Time signal 28th segment 99 Time signal 29th segment 100 Time signal 30th segment 101 Time signal 31st segment 102 Time signal 32nd segme...

Страница 15: ...aud rate setting parameter C C C Co o o oM M M M and choose 9600 bps even 9 9 9 96 6 6 6e e e ev v v v This sets the baud rate to 9600 bps and the parity to even 3 Display communication permissions S...

Страница 16: ...value For dual control set S S S Sb b b bo o o o2 2 2 2 the same way 4 Press the key to set the value 1 Display the system menu S S S SY Y Y YS S S S C C C Ch h h h 7 7 7 7 2 Set both ramp SV decline...

Страница 17: ...V No 1 Display the operation menu o o o oP P P PE E E E C C C Ch h h h 1 1 1 1 2 Display the selected PID number S S S Sv v v vn n n n and choose di 3 Display the di function setting d d d di i i i1 1...

Страница 18: ...ent range C Measurement range F Smallest input increment C Input code Resistance bulb JIS IEC Pt 100 0 to 150 32 to 302 0 1 1 1 1 1 0 to 300 32 to 572 0 1 0 to 500 32 to 932 0 1 0 to 600 32 to 1112 1...

Страница 19: ...code is changed turn off the power once and then re start the controller before starting control Aln AL1 to AL3 show the alarm set values ALnh AL1h to AL3h show the alarm set values ALnL AL1L to AL3L...

Страница 20: ...Thermocouple input greatest one among 0 3 FS 1 digit and 1 C or 2 C Resistance bulb input greatest one among 0 3 FS 1 digit and 0 5 C mV input voltage input current input 0 3 FS 1digit Indication res...

Отзывы: