–7–
[7] Reset SW
This switch is used to reset the NA. Press the button for 3 seconds or more to reset the NA.
[8] Toggle SW
Not used. Set to "ON" at all times.
[9] Mode SW
Set to "1" at all times.
[10] SLOT 1 to 6
Network cards are mounted according to the models of NA.
Refer to 1.5 “Models of NA” to see which network cards are mounted.
The outer appearances of slots for respective network cards are as follows.
[In the case of T-link]
The slot has a terminal block structure as shown below. T-link is connected in this terminal block. It is
connected to the internal TLC unit. Two T-link systems can be connected per slot as shown in the following
figure.
The right side is for the CH1 channel, and the left side is for the CH2 channel. The terminal block is
removable.
A T-link termination resistor is attached between T1 and T2 for each channel.
For the terminating station, make the termination resistor stay attached.
For midpoint stations of T-link, remove the termination resistors and attach a termination resistor between T1
and T2 for the terminating station.
The screw diameter of the terminal is M3.5.
CH2
CH2
T2
T2
T2
T2
T1
T1
T1
T1
SD
SD
SD
SD
NC
NC
CH1
CH1
NC
NC
SD
SD
T2
T2
T1
T1
SD
SD
T2
T2
T1
T1
T-link terminal block
fastening screws
Содержание MICREX-View XX
Страница 1: ......