4. RAS 

4.1  Major System Memory Related to NA and IPU-II Errors 

The following shows the major system memory related to NA and T-link errors. 

Address Name 

Description 

%MX254.2.10.2.3 

NA BUS error (serious 
failure)  

Turns on with NA bus disconnection when fail-soft is disabled. 

%MX254.2.10.2.5 

NA I/O module error 
(serious failure) 

This turns on when an error occurs to the IPU-II node, which is 
connected to the NA, without degeneracy setting (including a 
node failure, disconnection of power supply, and stop of 
communication due to an IPU-II error). 

%MX254.2.10.4.3  

NA BUS error (minor 
failure) 

  Turns on with NA bus disconnection when fail-soft is enabled. 

%MX254.2.10.4.5 

NA I/O module error 
(minor failure) 

Turns on with an error in a slave T-link station connected to the 
NA (including slave station failure, power interruption, and 
communication interruption due to a T-link error) when fail-soft is 
enabled. 

%MX254.2.10.4.11   

Break in NA EQ cable 

Turns on with a break in the NA EQ cable with the NA 
equalization configuration using NA EQ. 

%MX254.2.10.52.1 

NA BUS configuration 
information 
(operation/minor failure) 

Turns on when the NA connected to the NA BUS is normal or in 
the minor failure status. 

%MX254.2.10.54.1 

NA BUS error information 
(serious/minor failure) 

Turns on when the NA connected to the NA BUS is in the serious 
or minor failure status. 

%MW254.2.10.116.1  

%MW254.2.10.116.6 

NA SLOT1 configuration 
information 

NA SLOT6 configuration 
information 

This turns on when the network card is mounted in SLOT1 and 
operation is normal or in the case of minor failure. 

This turns on when the network card is mounted in SLOT6 and 
operation is normal or in the case of minor failure. 

%MW254.2.10.117.1  

%MW254.2.10.117.6 

NA SLOT1 error 
information 

NA SLOT6 error 
information 

This turns on when the network card is mounted in SLOT1 and 
operation is normal or in the case of minor failure. 

This turns on when the network card is mounted in SLOT6 and 
operation is normal or in the case of minor failure. 

%MW254.2.10.128 to 
135  

NA SLOT1 I/O station 
configuration information 

When the T-link I/O station connected to NA SLOT1 is normal or 
in the minor failure status, the relevant I/O station No. turns on. 

%MW254.2.10.136 to 
143  

NA SLOT1 I/O station 
error information 

When the T-link I/O station connected to NA SLOT1 is in the 
serious or minor failure status, the relevant I/O station No. turns 
on. 

%MW254.2.10.144 to 
151  

NA SLOT2 I/O station 
configuration information 

When the T-link I/O station connected to NA SLOT2 is normal or 
in the minor failure status, the relevant I/O station No. turns on. 

%MW254.2.10.152 to 
159 

  NA SLOT2 I/O station 
error information 

When the T-link I/O station connected to NA SLOT2 is in the 
serious or minor failure status, the relevant I/O station No. turns 
on. 

 
The bit ON/OFF combinations and NA statuses for NA BUS configuration information (%MX254.2.10.52.1) and error 
information (%MX254.2.10.68.1) are as follows. 

Configuration 
information 

Error 
information 

NA status 

OFF  

OFF  

Does not exist 

ON  

OFF 

Normal 

ON ON 

 

Minor 

failure 

OFF   

ON   

Serious failure or dropped out 

 
The bit ON/OFF combinations and I/O station statuses for I/O station configuration information (%MW254.2.10.128–, 144–) 
and error information (%MW254.2.10.136–, 152–) are as follows. 

Configuration 
information 

Error 
information 

NA status 

OFF  

OFF  

Does not exist 

ON  

OFF 

Normal 

ON ON 

 

Minor 

failure 

OFF   

ON   

Serious failure or dropped out 

 

IPU-II 

Содержание MICREX-View XX

Страница 1: ......

Страница 2: ...LM IOM and rack for mounting them TLM T link interface module mounted on IPU I One set is mounted on one rack in the case of T link single configuration and 1T duplicated configuration Two sets are se...

Страница 3: ...released by The Institute of Electrical and Electronics Engineers Inc IEEE STP cable Cable incorporating electromagnetism shielding treatment by the use of foils on the surface and by braiding out of...

Страница 4: ...00PDY T link T link PE link PE link DPCS F 18 CSH2LGYY 00YYY IPU 19 CSH2LGYY 00YDY IPU DPCS F 20 CSH2LGYP 00YYY IPU PE link 21 CSH2LGYP 00PYY IPU PE link PE link 22 CSH2LGYP 00YDY IPU PE link DPCS F 2...

Страница 5: ...erminal The terminal for the connection of the FG cable The screw diameter of the terminal is M4 4 NA BUS connector NA BUS Connector for the connection of the XCS 3000 and NA Connect this connector to...

Страница 6: ...r not operating due to a serious failure configuration definition error etc SLOT No 2 Green Light on Operating correctly Blinking Minor failure Light off Being initialized or not operating due to a se...

Страница 7: ...us Color Green Red Green Red Power off being reset Power supply OFF during resetting failure of NA Starting up Operating correctly operating Operating correctly standby Serious module failure CPU erro...

Страница 8: ...ck It is connected to the internal TLC unit Two T link systems can be connected per slot as shown in the following figure The right side is for the CH1 channel and the left side is for the CH2 channel...

Страница 9: ...In the case of IPU II Outer appearance of IPU II It has a structure of a BNC connector as shown below There is no connector on the cable side Front view of outer appearance Top view of outer appearan...

Страница 10: ...e contact pin and crimp the pin with the crimp tool as shown below Subsequently slide the ferrule over the cable 4 Insert the the body knurl into between the shield wire and the insulator 5 Slide the...

Страница 11: ...esistors 50 on both ends of a coaxial cable Specifications of BNC termination resistor Manufacturer OSADA Model B 144F BNGT5 6 Length of coaxial cable The maximum cable length is 185 m the minimum cab...

Страница 12: ...the protective cover on the BNC connector of the NA mounted with the IPU II master a Connection of BNC T valve Connect the BNC T valve to the BNC connector of the IPU II master b Connection of 10Base2...

Страница 13: ...ve cover in the state where the cables are connected to the T valve d State after mounting Fix the protective cover by the upper and lower caps The mounted protective cover protects the metallic parts...

Страница 14: ...ith RJ45 connector of Ethernet as illustrated below Pin No Signal name I O Function 1 TXD send data 2 TXD I O send data 3 RXD I O receive data 4 NC1 NC 1 5 NC1 NC 1 6 RXD receive data 7 NC2 NC 1 8 NC2...

Страница 15: ...onsidered please contact our sales office in your region SLOT6 SLOT6 SLOT5 SLOT5 SLOT1 SLOT1 SLOT2 SLOT2 FG FG DC24V DC24V SLOT No SLOT No NA STATUS NA STATUS 1 2 3 4 ON ON ERR ERR RUN RUN ALM ALM RST...

Страница 16: ...laced by the XCS 3000 NA configuration Therefore the already discontinued I Os are also listed as the connectable devices Contact our sales person in each case as to whether those I Os are still avail...

Страница 17: ...ctly Figure 1 2 2 2T Duplex Configuration T link only IPU II for 2T duplex XCS 3000 standby system CSH1 CSH1 PU1A PU1A 00FHY 00FHY 5 75 0 75 0 0 0 0 6 4 6 4 6 4 6 4 44 0 44 5 75 10 FL net V3 based LAN...

Страница 18: ...uration Single Maximum 8 nodes can be connected in one IPU II circuit Duplication IO unit Maximum 8 nodes can be mounted Connected device Devices connectable by Ibus module of ACS Definition of IO gro...

Страница 19: ...o not install the equipment in a place where it is directly exposed to the air current of a ventilation fan etc 3 Do not mount a module in a slot adjacent to the bus interface module BIM 4 Do not moun...

Страница 20: ...to 150 mV 16 points isolated in a batch AAIS02 Resistance temperature detector slip resistance inp ut module resistance temperature detector JIS Pt100 JPt100 slip resistance 0 to 3 k 12 points isolat...

Страница 21: ...station failure power interruption Break in IPU II cable NA failure power interruption Break in NA BUS cable Steady electrical noise in IPU II or NA BUS cables In station fail soft operation is a func...

Страница 22: ...CSH1 PU1A PU1A 00FHY 00FHY 5 75 0 75 0 0 0 0 6 4 6 4 6 4 6 4 44 0 44 5 75 10 IPU NA XCS 3000 CPU shutdown B I M I O M I O M I O M B I M I O M I O M I O M Error with an BIM not set for fail soft NA BU...

Страница 23: ...nterruption etc Break in IPU II cable break in the NA BUS cable 1 Output control When any of the above error occurs each IPU II IOM holds or zero clears the output value according to the setting from...

Страница 24: ...are as follows Prefix SX bus station No HW No NA station No Slot No Node No Word address Bit address Item Setting value Prefix IX IW ID QX QW QD SX bus station No 254 fixed HW No 2 fixed at 2 for the...

Страница 25: ...the figure below or 32 digital outputs red in the figure below Set the NA system definition as follows NA BUS XCS 3000 IOM station No CSH1 CSH1 PU1A PU1A 00FHY 00FHY 5 75 0 75 0 0 0 0 6 4 6 4 6 4 6 4...

Страница 26: ...Station No Station No IOM Word address Bit address First Di module in IPU II 0 0 0 0 Second Do module in IPU II QX254 2 1 1 0 1 0 0 Prefix to line number Station No Station No IOM Word address Bit add...

Страница 27: ...der the NA can be used as templates of addresses by pasting the information onto an Excel file with the following procedure Using this function can reduce the work load of IPU II address input Open th...

Страница 28: ...low the device models column A general specifications column B and word addresses column C are generated Use the word addresses prepared in this process by copying them in Excel and paste them onto th...

Страница 29: ...hat takes place when an error occurs in a system located under the NA Error cause Remarks on operation Error pattern of IPU II system located under NA Error in EPC module or IPU II circuit Pattern 1 B...

Страница 30: ...3000 NA is performed CSH1 CSH1 PU1A PU1A 00FHY 00FHY 5 75 0 75 0 0 0 0 6 4 6 4 6 4 6 4 44 0 44 5 75 10 FL net V3 based LAN duplex NA BUS NA XCS 3000 standby system CSH1 CSH1 PU1A PU1A 00FHY 00FHY 5 7...

Страница 31: ...U1A 00FHY 00FHY 5 75 0 75 0 0 0 0 6 4 6 4 6 4 6 4 44 0 44 5 75 10 FL net V3 based LAN duplex NA BUS NA XCS 3000 standby system CSH1 CSH1 PU1A PU1A 00FHY 00FHY 5 75 0 75 0 0 0 0 6 4 6 4 6 4 6 4 44 0 44...

Страница 32: ...plication In the following diagram the IOMs in the thick frame are the duplicated IOMs CSH1 CSH1 PU1A PU1A 00FHY 00FHY 5 75 0 75 0 0 0 0 6 4 6 4 6 4 6 4 44 0 44 5 75 10 FL net V3 based LAN duplex NA B...

Страница 33: ...ounted in SLOT6 and operation is normal or in the case of minor failure MW254 2 10 117 1 MW254 2 10 117 6 NA SLOT1 error information NA SLOT6 error information This turns on when the network card is m...

Страница 34: ...I O station error information MW254 2 10 136 to 143 details the numbers in boxes show station numbers NA SLOT2 I O station configuration information MW254 2 10 144 to 151 details the numbers in boxes...

Страница 35: ...on of IPU II communication circuit interruption of power supply in the node station error in BIM etc The detailed RAS displays the number of node station where an error is occurring In addition in the...

Страница 36: ...M The detailed RAS displays the number of node station where an error is occurring In the configuration tree display the IOM station where an error is occurring is displayed in the minor failure state...

Отзывы: