8-3
8.4 Compliance with EMC Standards
8.4.1 General
The CE marking on inverters does not ensure that the entire equipment including our CE-marked products is
compliant with the EMC Directive. Therefore, CE marking for the equipment shall be the responsibility of the
equipment manufacturer. For this reason, Fuji Electric’s CE mark is indicated under the condition that the
product shall be used within equipment meeting all requirements for the relevant Directives. Instrumentation of
such equipment shall be the responsibility of the equipment manufacturer.
Generally, machinery or equipment includes not only our products but other devices as well. Manufacturers,
therefore, shall design the whole system to be compliant with the relevant Directives.
EMC certification testing is performed using the following wiring distances between the inverter and
motor (shielded wire):
・
FRN0006LM2A-4
□
to FRN0091LM2A-4
□
・
FRN0011LM2A-7
□
, FRN0018LM2A07
□
:
10m
8.4.2 Recommended installation procedure
To make the machinery or equipment fully compliant with the EMC Directive, the motor and inverter have to be
wired by certified technicians in strict accordance with the procedure given below.
1) Use shielded wires for the motor cable and route the cable as short as possible. Firmly clamp the shield to
the specified point or the grounded metal plate inside the inverter. Further, connect the shielding layer
electrically to the grounding terminal of the motor.
2) For connection to inverter's control terminals and for connection of the RS-485 communication or CAN-Bus
signal cable, use shielded wires. Clamp the shields firmly to the grounded metal plate.
3) Place the inverter on a grounded metal plate such as the surface of a panel, as shown in Figure 8.1. If
radiated noise emissions exceed the standard, place the inverter and any peripheral equipment inside a
metal control panel.
Figure 8.1 Installation inside a Panel
4) If radiated noise emissions exceed the requirement by the standard, place a ferrite core on the input side of
the inverter, as shown in Figure 8.2
FRENIC-Lift
Ferrite
Core
L1/R
L2/S
L3/T
G
From
Power
Supply
Figure 8.2 Installation for ferrite core
FRENIC-LIFT