Conformity with Canadian standards and U.S. standards (Continued)
5. Install CSA or UL certified fuses or Circuit breaker between the power supply and the inverter, referring to
the table below.
Power supply
voltage
Nom
inal
ap
plied
m
otor (kW)
Inverter type
Fuse rating [A]
(Class)
Circuit breaker (MCCB)
or
RCD/ELCB etc
[A]
With
DCR
Without
DCR
With
DCR
Without
DCR
Thr
ee
-phase
400
V
2.2
FRN0006LM2A-4
o
-
10
-
4.0
FRN0010LM2A-4
o
5.5
FRN0015LM2A-4
o
15
7.5
FRN0019LM2A-4
o
20
11
FRN0025LM2A-4
o
30
15
FRN0032LM2A-4
o
40
18.5
FRN0039LM2A-4
o
75
22
FRN0045LM2A-4
o
50
100
30
FRN0060LM2A-4
o
75
125
37
FRN0075LM2A-4
o
100
45
FRN0091LM2A-4
o
150
Si
n
g
le
-
Ph
a
se
200V
2.2
FRN0011LM2A-7
o
30
(Class J)
40
(Class J)
-
4.0
FRN0018LM2A-7
o
60
(Class J)
80
(Class J)
L1/R
L2/S
L3/T
24V+
24V-
Fuses
Three-
Phase
400V
MC
Disconnect
MCCB
or
RCD/ELCB, etc.
( )
Power
supply
24VDC
(*1)
R0
T0
(*1)
L1/L
L2/N
24V+
24V-
Fuses
Single-
Phase
200V
MC
Disconnect
MCCB
or
RCD/ELCB, etc.
( )
Power
supply
24VDC
(*1)
Note:
A box (
o
) replaces an alphabetic letter depending on the shipping destination.
o
Shipping destination: E (Europe) or A (Asia)
*1) Not more than 6A (RMS) fuses or not more than 5A (RMS) breakers for 24V power supply and control power supply (R0 and
T0).