Menu J: Current saturation value (SATURATE CUR)
The FCX-AII pressure transmitters
intended for use in nuclear power
plants are delivered configured
with an enabled write protection
and a saturation current set at 3.2mA at
its low value and 21.6mA at its high value.
The reconfiguration of these settings must
be done before the write protection is lifted
according to the provision specified on page
35. After all the operations are complete, the
write protection must be replaced.
The value of the min/max output signal (low
limit=SAT LO, high limit=SATO HI) and the
extended function (NORMAL= standard
setting, EXP. = extended setting) can be
configured.
In the normal position the values of the
min/max output signal are set to 3.8 and
20.8.
To expand the limits of the min/max output
signal values, option 3 on the screen “J”,
(SPEC/NORMAL) must be selected to
programme the output signal.
• Modification of the value of the min. output
signal (lower limit) by programming “EXP”.
The value of the output signal can be
changed by pressing the buttons on the
<INC> or <DEC>.
3.2MA ≤ substitute value (UNDER
SCALE) ≤ saturation current (lower limit)
≤ 4.0mA
• Modification of the value of the max. output
signal (upper limit)
Follow the same procedure as for the
programming of the lower limit value. Choose
the upper limit by pressing 2 .
Change the value of the output signal by
using the keys <INC> or <DEC>.
20.0mA maximum saturation current ≤
substitute value (OVER SCALE) 21.6my
* The output signal corresponding to the
substitute value is programmable in the
menu “9”.
1
CL
J:
SATURATE CUR
< 1 >SAT LO Y.YmA
< 2 >SAT HI YY.YmA
< 3 >SPEC XXXXXX
2
ENT
SATURATE LO
2 SATURATE HI
3 SPEC
1
J-1:
SATURATE CUR
SATURATE LO
Y.YmA
J-2:
SATURAT CHNG
SATURATE LO
Y.YmA
3
J-2:
SATURAT CHNG
SATURATE LO
Y.YmA
CHNG OK?< ENT/CL >
4
INC
INC
< CHANGE >< CL >
SATURATE LO
(Lower limit value of
saturation current)
Press <INC> or <DEC> to change
the saturation current value.
(See above)
< INC > < ENT> < CL >
DEC
INC
Y.YmA
4.0mA
3.9mA
3.7mA
3.8mA
3.6mA
3.5mA
3.4mA
3.3mA
3.2mA
CL
1
CHNG
CL
CL
J:
SATURATE CUR
< 1 >SAT LO Y.YmA
< 2 >SAT HI YY.YmA
< 3 >SPEC XXXXXX
5
ENT
1
J-1:
SATURATE CUR
SELECT SPEC
XXXXXX
J-1:
SATURATE CUR
SELECT SPEC
XXXXXX
CHNG OK?< ENT/CL>
6
INC
INC
SPEC
XXXXXX part
:
NORMAL=Standard spec.
EXP.=Extended spec.
DEC
INC
NORMAL
EXP.
CL
3
Menu No.K
Menu No.K
Menu No.I
Menu No.I
< INC> < ENT> < CL>
Important