13
TN4FCXA2
j
-EDF-
E
Capteur
Vis
Models FKC, FKG, FKA
FKD Models, FKB, FKM
Grower washer
Transmitter
Bracket
Flat washer
Flange mechanisms
M8x12 screw
Grower washer
M8x12 screw
Flat washer
Bracket
Transmitter
On tube
Models FKC, FKG, FKA
FKD Models, FKB, FKM
Mount the transmitter on the tube using the U-bracket provided
for this purpose. Apply a tightening torque of approximately
15N.m. The diameter of the tube must be 2” (60.5 mm)
The wall
Secure the bracket to the wall using screws M8
With flange
Introduce the flange of the transmitter to the front of that
of the the piping or the tank mechanism. Fasten them
together with a set of appropriate bolts to the flanges used.
Fit the universal bracket on the transmitter as shown below:
The transmitter must be
mounted on its bracket
with the M8 screws, flat
washers and Grower
washers provided, maintaining a
screw tightening torque of 15 N.m
for the A4-70 screws.
Mounting the universal bracket
Mounting
• The transmitter is heavy. Handle with caution.
• the installation and connection conditions listed must be observed.
• Improper handling may cause incorrect operation of the transmitter.
• During the installation, ensure that no object likely to cause malfunction or even hazards is
located inside the electronic unit.
• When a device is under voltage in ADF zone:
- Do not change the position of the local indicator.
- Do not change the position of the electronic unit.
• The isolation valves must be selected on the basis of the maximum line pressure. The connection
accessories of the transmitter are provided by the user. If the connections valves and accessories
are under-sized, there is a risk of leakage of hazardous gas or liquid.
• The pipes must be sized according to the process/pressure temperature standards.
• As the membranes are very fragile, please take precautions when handling them.
• Do not bend the capillaries excessively
DANGER
Important