61
3
Selection and application
3-5 Motor circuit applications
Table 3-14 Selection of line protection MCCB and ELCB (for reference)
(a) 230V AC 3-phase induction motor
Contactor
type
Thermal
overload
relay type
Motor ratings
MCCB
rated
current
(A)
Icu (kA)
Current
(A)
Output
(kW)
2.5
5
10
25
36
50
85
100
125
SC-03
TR-0N/3
1.3
0.2
5
BW32AAG
BW32SAG
BW50SAG
2.3
0.4
5
BW32AAG
BW32SAG
BW50SAG
3.5
0.75
10
BW32AAG
BW32SAG
BW50SAG
BW50RAG
15
BW125JAG
BW125SAG BW125RAG BW50HAG
6.9
1.5
20
BW32AAG
BW32SAG
BW50SAG
BW50RAG
BW125JAG
BW125SAG BW125RAG BW50HAG
9.5
2.2
30
BW32AAG
BW32SAG
BW50SAG
BW50RAG
BW125JAG
BW125SAG BW125RAG BW50HAG
SC-4-0
TR-5-1N/3
15.5
3.7
40
BW50AAG
BW50EAG
BW50SAG
BW50RAG
BW125JAG
BW125SAG BW125RAG BW50HAG
SC-N1
TR-N2/3
21
5.5
50
BW50AAG
BW50EAG
BW50SAG
BW50RAG
BW125JAG
BW125SAG BW125RAG BW50HAG
SC-N2
27.5
7.5
60
BW125JAG
BW125SAG BW125RAG BW50HAG
75
BW100AAG
BW100EAG
SC-N2S
TR-N3/3
40
11
100
BW125JAG
BW125SAG BW125RAG BW50HAG
SC-N3
54
15
100
BW125JAG
BW125SAG BW125RAG BW50HAG
SC-N4
TR-N5/3
68
18.5
125
BW125JAG
BW125SAG BW125RAG BW50HAG
SC-N5
SC-N5A
84
22
125
BW160EAG BW160JAG
BW160SAG BW160RAG BW250HAG
SC-N6
TR-N6/3
116
30
175
BW250EAG BW250JAG BW250SAG BW250RAG BW250HAG
SC-N7
TR-N7/3
137
37
225
BW250EAG BW250JAG BW250SAG BW250RAG BW250HAG
SC-N8
TR-N8/3
166
45
250
BW250EAG BW250JAG BW250SAG BW250RAG BW250HAG
SC-N10
TR-N10/3
200
55
350
BW400EAG BW400SAG BW400RAG BW400HAG
SC-N11
TR-N12/3
272
75
500
BW630EAG
BW630RAG BW630HAG
SC-N12
332
90
500
BW630EAG
BW630RAG BW630HAG
380
110
500
BW630EAG
BW630RAG BW630HAG
Notes 1 : The model numbers to use for direct-on-line starters are given for electromagnetic contractors.
2 : The model numbers for AC3-class electromagnetic contactors are given.
3 : The catalog values are given for the rated motor current (catalog number 24B2-E-0087) for Fuji 3-phase totally enclosed fan-cooled models (4-pole,
200V/50Hz with feet).