44
3
Selection and application
3-3 Selective trip applications
●
AC230V MCCB
[Unit : kA]
Main circuit
breaker
BX100HAE
BX160HAE
BX250HAE
BX400HAE
BX630HAE
BX800HAE
BX1000HAE BX1250HAE BX1600HAE
Protective
characteristics
Ternary trip-element (long-time delay, short-time delay, instantaneous)
In [A]
40
100
160
250
400
630
800
1000
1250
1600
Control unit
5
5
5
5
5
5
5
5
5
5
Branch circuit breaker
Icu [kA] (sym)
100
100
100
100
100
100
85
85
85
85
BW32AAG BW50AAG
2.5
0.5
1.2
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
BW50EAG BW63EAG
5
0.5
1.2
2.0
2.5
4.0
5
5
5
5
5
BW100AAG
5
1.2
2.0
2.5
4.0
5
5
5
5
5
BW100EAG
25
1.2
2.0
2.5
4.0
5.8
25
25
25
25
BW250EAG
36
2.0
2.5
4.0
5.8
36
36
36
36
BW400EAG
50
4.0
5.8
50
50
50
50
BW630EAG
50
5.8
50
50
50
50
BW800EAG
50
50
50
50
50
BW32SAG
5
0.5
1.2
2.0
2.5
4.0
5
5
5
5
5
BW50SAG BW63SAG
10
0.5
1.2
2.0
2.5
4.0
5.8
10
10
10
10
BW125JAG
50
0.5
1.2
2.0
2.5
4.0
5.8
50
50
50
50
BW250JAG
50
2.0
2.5
4.0
5.8
50
50
50
50
BW400SAG
85
4.0
5.8
85
85
85
85
BW50RAG BW63RAG
25
0.5
1.2
2.0
2.5
4.0
5.8
25
25
25
25
BW125RAG
100
0.5
1.2
2.0
2.5
4.0
5.8
85
85
85
85
BW250RAG
100
2.0
2.5
4.0
5.8
85
85
85
85
BW400RAG
100
4.0
5.8
85
85
85
85
BW630RAG
100
5.8
85
85
85
85
BW800RAG
100
85
85
85
85
BW50HAG
125
0.5
1.2
2.0
2.5
4.0
5.8
85
85
85
85
BW125HAG
125
0.5
1.2
2.0
2.5
4.0
5.8
85
85
85
85
BW250HAG
125
2.0
2.5
4.0
5.8
85
85
85
85
BW400HAG
125
4.0
5.8
85
85
85
85
BW630HAG
125
5.8
85
85
85
85
BW800HAG
125
85
85
85
85
BX100HAE
100
85
85
85
85
85
85
85
85
85
85
BX160HAE
100
85
85
85
85
85
85
85
85
BX250RAE
90
85
85
85
85
85
85
85
BX250HAE
100
85
85
85
85
85
85
85
BX400RAE
85
85
85
85
85
85
85
BX400HAE
100
85
85
85
85
85
85
BX630RAE
85
85
85
85
85
85
BX630HAE
100
85
85
85
85
85
Table 3-6 (a) Selective trip coordination