50
3
Selection and application
3-3 Selective trip applications
Table 3-7 (b) Selective trip coordination between MCCB and 24kV power fuse
Transformer Capacity (kVA)
50
75
100
125
160
200
250
315
400
500
630
800
1,000 1,250 1,600 2,000
Primary current (A)
1.5
2.2
2.9
3.6
4.7
5.8
7.3
9.2
11.6
14.5
18.2
23.1
29
36
46.5
58
Secondary current (A)
72
108
144
180
230
290
360
455
576
720
910
1,160 1,440 1,800 2,300 2,890
% impedance (%)
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
Primary short-circuit current when
the secondary side of the transformer
shorts (A)
36
54
72
90
115
145
180
228
288
360
455
464
576
720
920
1,156
Secondary short-circuit current (kA)
1.8
2.7
3.6
4.5
5.8
7.3
9.0
11.4
14.4
18.0
22.8
23.2
28.8
36.0
46.0
57.8
Primary PF. Rated current
DIN/VDE 0670 Part 402(A)
6
6
10
10
16
16
25
25
32
40
50
63
63
80
80
80
Series
MCCB type
Breaking capacity
Icu/Ics (kA)
400V IEC 60947-2
MCCB Rated
current
(A)
Note 1 Selective trip coordination is not available.
Note 2 Selective trip coordination is available. (Instantaneous trip current must be adjusted
for coordination.)
Note 3 Selective trip coordination is available. Make sure however that the short-circuit
current where the MCCB is installed is less than its breaking capacity.
Note 4 Selective trip coordination is available.
AAG
BW32
1.5/1
3, 5, 10, 15, 20
30, 32
Note 3
BW50
1.5/1
5, 10, 15, 20, 30
32, 40, 50
Note 3
BW100
1.5/1
60, 63, 75, 100
Note 3
EAG
BW50
2.5/2
5, 10, 15, 20, 30
32, 40, 50
Note 4 Note 3
BW63
2.5/2
60, 63
Note 4 Note 3
BW100
10/5
50, 60, 63, 75
100
Note 4
Note 3
BW160
18/9
125
Note 1
Note 4
Note 3
150, 160
Note 1
Note 4
Note 3
BW250
18/9
175, 200
Note 1
Note 4
Note 3
225, 250
Note 1
Note 4
Note 3
BW400
30/15
250
Note 1
Note 4
Note 3
300, 350
Note 1
Note 4
Note 3
400
Note 1
Note 4
Note 3
BW630
36/18
500, 600, 630
Note 1
Note 4
Note 3
BW800
36/18
700
Note 1
Note 4
Note 3
800
Note 1
Note 4 Note 3
JAG
BW125
30/15
15, 20, 30, 40, 50
60
Note 4
Note 3
75, 100, 125
Note 1
Note 4
Note 3
BW160
30/15
125
Note 1
Note 4
Note 3
150, 160
Note 1
Note 4
Note 3
BW250
30/15
175, 200
Note 1
Note 4
Note 3
225, 250
Note 1
Note 4
Note 3
SAG
BW32
2.5/2
3, 5, 10, 15, 20
30, 32
Note 4 Note 3
BW50
7.5/4
5, 10, 15, 20, 30
32, 40, 50
Note 4
Note 3
BW63
7.5/4
60, 63
Note 4
Note 3
BW125
36/18
15, 20, 30, 40, 50
60
Note 4
Note 3
75, 100, 125
Note 1
Note 4
Note 3
BW160
36/18
125
Note 1
Note 4
Note 3
150, 160
Note 1
Note 4
Note 3
BW250
36/18
175, 200
Note 1
Note 4
Note 3
225, 250
Note 1
Note 4
Note 3
BW400
36/18
250
Note 1
Note 4
Note 3
300, 350
Note 1
Note 4
Note 3
400
Note 1
Note 4
Note 3