1) Connect the Radar to the data logger using the

wiring guide.

2) Confirm communication with the sensor, by entering the Send

Identification command: 

 a

I! 

in which 

is replaced with the SDI-12

address of the sensor (the example uses address  0, the default
address of the radar)

Command 

0I! 

Response 

0I!013FTS-----RdrStg10198765 

3A.  SET RADAR PARAMETERS 

PIN 

WIRE  

DESCRIPTION 

GND 

Black 

Ground 

12VDC 

Red 

10.6 to 16 VDC Input 

DATA 

White 

SDI-12 Data 

Bare 

Shield Ground 

SET STAGE UNITS:  

The default stage units are feet.  To change use: 

 

a

XSUcc!

  in which the 

a

 is replaced with the SDI-12 address of 

the radar and 

cc

 is replaced with the abbreviated form of stage 

units:

 

STAGE 
UNITS 

ABBREV 

SLOPE VALUE 

Feet 

FT 

1.0 

Inches 

IN 

12.0 

Metres 

0.3048 

Centimetres 

CM 

30.48 

Millimetres 

MM 

304.8 

Custom 

CU 

As Input by user 

Example 

(radar at SDI-address 0):

 

To change stage units to metres  

Command

  0XSUM! 

Response

 

Adjusting stage units 
will automatically 
change the slope 

TAKE MEASUREMENT: 

a

M! 

GET MEASUREMENT: 

aD0

in which the 

a

 is replaced with the SDI-12 address of the 

radar. Use the desired measurement  (M, M1, M2, or M3). 

Example

 (radar at SDI-address 3): 

Command

  3M! 

Command

  3D0! 

Response

  30022 

Response 

3+3.899+1.000000

 

SET CURRENT STAGE: 

a

XSHn!

 

in which the 

is replaced with the SDI-12 address of the radar 

and 

n

 is the stage reading. 

Example 

(radar at SDI-address 3, stage reading = 12.4):

 

Command

 

3XSH12.4! 

Response

 

IMPORTANT!

 Input the current stage reading in the same measurement 

units which were previously set.  Default units are feet. If unsure which units 
of measurement are set, use the Get Stage Unit command (see Section 4) 

In addition to the standard set of SDI-12 commands, the FTS Radar Range Sensor has custom SDI-12 commands (X commands) that 
access specific features of the sensor.  Refer to the Radar Stage Sensor Operating Manual (700-RSS-Man) for a full list and 
explanation of the commands.  In all commands, the 

must be replaced with the SDI-12 address of the radar.

 

?! 

Address query 

Response will be SDI-12 
address 

a

Ab! 

Change address 

b

=the address to change to 

a

XPMc! 

a

XPM!

 

Set power mode 
Get power mode 

c

= H or L  (H = high, L = low 

a

XSU!

 

Get stage units 

Refer to Stage Units table in 
Section 3A 

a

XAOn! 

a

XAO! 

Set analog offset 
Get analog offset 

n = desired output offset 
Range of offset = 0.0 to 20.0 

a

XASn! 

a

XAS! 

Set analog scale 
Get analog scale 

n=4-20 mA output scaling 
value 

3

SETTING UP WITH 

NON-

AXIOM DATALOGGERS 

4

USEFUL SDI-12 COMMANDS

 