equalized time is arrived.
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't
rise to battery equalization voltage point, the solar charge controller will extend the battery
equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still
lower than battery equalization voltage when battery equalized timeout setting is over, the solar
charge control will stop equalization and transfer to float stage.
5.3 Setting parameter and Default Value
Recommended and default parameter setting are listed below.
Parameter
Battery type
Absorp.
Stage
Float
Stage
Equalize
Stage
Equalize
Activation
Absorp.
Time
Equalize
Time
Equalize
Timeout
Equalize
Interval
Unit
volt
volt
volt
En/Disable
Minutes
Minutes
Minutes
Days
Default
AGM/Gel/L
EAD
14.4V
13.7V
14.6V
Disable
150
60
120
30
Option
Flooded
14.2V
13.7V
14.6V
Disable
150
60
120
30