42
Generator-powered operation
Generator-pow-
ered operation
The power source is generator-compatible.
The maximum apparent power S
1max
of the power source must be known in order to select
the correct generator output.
The maximum apparent power S
1max
of the power source is calculated as follows:
The generator apparent power S
GEN
needed is calculated using the following rule of
thumb:
A smaller generator may be used when not welding at full power.
IMPORTANT!
The generator apparent power S
GEN
must always be higher than the maxi-
mum apparent power S
1max
of the power source.
When using single-phase devices with a 3-phase generator, note that the specified gener-
ator apparent power is often only available as a whole across all three phases of the gen-
erator. If necessary, obtain further information on the single-phase power of the generator
from the generator manufacturer.
3-phase devices:
S
1max
= I
1max
x U
1
x √3
Single-phase devices:
S
1max
= I
1max
x U
1
See device rating plate or technical data for I
1max
and U
1
values
S
GEN
= S
1max
x 1.35
NOTE!
The voltage delivered by the generator must never exceed the upper or
lower limits of the mains voltage tolerance range. Details of the mains voltage tol-
erance can be found in the "Technical data" section.
Содержание TransSteel 3500 Rob
Страница 2: ...2...
Страница 4: ...4...
Страница 8: ...8...
Страница 20: ...20...
Страница 21: ...General information...
Страница 22: ......
Страница 27: ...Control elements and connections...
Страница 28: ......
Страница 35: ...Installation and commissioning...
Страница 36: ......
Страница 46: ...46...
Страница 47: ...Welding...
Страница 48: ......
Страница 61: ...61 EN Number 3 Number 4 Number 5...
Страница 62: ...62...
Страница 63: ...Setup settings...
Страница 64: ......
Страница 76: ...76...
Страница 77: ...Troubleshooting and maintenance...
Страница 78: ......
Страница 99: ...Appendix...
Страница 100: ...100 Spare parts list TSt 3500 Rob TSt 5000 Rob...
Страница 102: ...102...
Страница 103: ...103...