4 | Technology
20
M0691622_en | Installation instructions TM 320-550
Additional data for regulation (EU) 2015/1189
Description
TM 500
TM 500
1)
TM 550
Heating up mode
automatic
Condensing boiler
No
Solid fuel boiler for combined heat and power
No
Combined heating system
No
Storage tank volume
Characteristics when operated exclusively with the preferred fuel
Useful heat delivered at rated heat output (P
n
)
kW
499
-
-
Useful heat delivered at 30% of rated heat output (P
p
)
149.7
-
-
Fuel efficiency at rated heat output (η
n
)
%
82.8
-
-
Fuel efficiency at 30% of rated heat output (η
p
)
81.5
-
-
Auxiliary current consumption at rated heat output
(el
max
)
kW
1.190
-
-
Auxiliary current consumption at 30% of rated heat
output (η
p
)
0.450
-
-
Auxiliary current consumption in standby mode (P
SB
)
0.024
-
-
1. TM 500 with 501 kW nominal output (available only in the UK)
Regulation (EU) 2015/1189 – emissions in [mg/m³]
1)
Annual space heating emissions of dust (PM)
≤ 30
Annual space heating emissions of gaseous organic compounds
(GOC)
≤ 20
Annual space heating emissions of carbon monoxide (CO)
≤ 380
Annual space heating emissions of nitrogen oxides (NO
x
)
≤ 200
1. The emissions of dust, gaseous organic compounds, carbon monoxide and nitrogen oxides are stated in a standardised form based on dry flue gas with a oxygen content of 10 % and
under standard conditions at 0°C and 1013 millibar